7 HYDRAULIC DESIGN CRITERIA
LH, ОН and ННР
The design density shall be no less than the appropriate value given in this clause when all the ceiling or roof sprinklers in the room concerned, or in the area of operation, whichever is the fewer, plus any in-rack sprinklers and supplementary sprinklers, are in operation. The minimum requirements for design density and area of operation for LH, OH and HHP classes are given in Table 3. For HHS systems, 7.2 shall be applied.
Note For pre-calculated systems, the design criteria are achieved by the application of water supply and piping requirements stated elsewhere in this standard (see 7.3, 9.3.2.2 and 10.7)
.Таблиця 3 - Вихідні дані для розрахунку систем захисту приміщень класів LH, ОН і ННР
Table 3 - Design criteria for LH, OH and ННР
Клас пожежної небезпеки Hazard Class |
Розрахункова інтенсивність зрошування, мм/хв Design Density, mm/min |
Площа для розрахунку, м2 Area of Operation, m2 |
|
Водозаповнена система або система попередньої дії Wet or pre-action |
Повітряна або водоповітряна система Dry or alternate |
||
LH |
2,25 |
84 |
Не допускається. Застосовувати як для приміщень класу ОН1 Not allowed Use ОН1 |
ОН1 |
5,0 |
72 |
90 |
ОН2 |
5,0 |
144 |
180 |
ОНЗ |
5,0 |
216 |
270 |
ОН4 |
5,0 |
360 |
Не допускається. Застосовувати як для приміщень класу ННР1 Not allowed Use ННР1 |
ННР1 |
7,5 |
260 |
325 |
ННР2 |
10,0 |
260 |
325 |
ННРЗ |
12,5 |
260 |
325 |
ННР4 |
Дренчерна система (див. примітку) deluge (see Note) |
||
Примітка. Потрібне спеціальне обґрунтування. Цей стандарт не поширюється на дренчерні системи. Note Needs special consideration. Deluge systems are not covered by this standard. |
Складські приміщення з високою пожежною небезпекою HHS
Загальні положення
Спосіб захисту, визначення розрахункової інтенсивності зрошування та розрахункової площі залежать від горючості виробу (або декількох виробів) та його упаковки (у тому числі піддонів), а також способу та висоти складування.
Для різних способів складування необхідно застосовувати специфічні обмеження, описані у розділі 6.
Захист із використанням спринклерів, розміщених тільки на стелі або даху
У таблиці 4 наведено значення розрахункової інтенсивності та площі для розрахунку відповідно до категорії та максимальної допустимої висоти складування для різних типів складування у разі використання спринклерів, розміщених тільки поблизу від поверхні стелі або даху. Зокрема, значення висоти складування, наведені у таблиці, вважаються максимальними, за яких забезпечується ефективність захисту спринклерною системою, коли спринклери розміщено лише поблизу від поверхні стелі або даху.
Примітка 1. Відстань між точкою, яка відповідає максимально допустимій висоті складування, та стельовими або даховими спринклерами не повинна перевищувати 4 м.
Якщо висота складування перевищує наведені граничні значення або якщо відстань між верхньою поверхнею складованих виробів та перекриттям або дахом перевищує 4 м, необхідно встановлювати проміжні внутрішньосте- лажні спринклери згідно з 7.2.3.
Примітка 2. Зміна висоти складування, висоти будівлі та стельового проміжку (відстані за вертикаллю між стельовими або даховими спринклерами та верхньою поверхнею складованих виробів) суттєво впливає на ефективність захисту спринклерною системою та необхідну розрахункову інтенсивність зрошування.
Внутріиіньостелажні спринклери, які розміщуються на проміжних рівнях
Якщо у внутрішньостелажному просторі на проміжних рівнях розміщено більше ніж 50 спринклерів, то вони не повинні живитися від того самого вузла керування, що й дахові або стельові спринклери. Діаметр проходу вузла керування повинен бути не меншим за 100 мм.
7.2 High Hazard Storage - HHS
General
The type of protection and determination of the design density and area of operation are dependent on the combustibility of the product (or mix of products) and its packaging (including the pallet) and the method and height of storage.
Specific limitations apply to the various types of storage methods as detailed in clause 6.
Ceiling or roof protection only
Table 4 specifies the appropriate design density and area of operation according to the category and maximum permitted storage height for the various types of storage with roof or ceiling protection only. More specifically, the storage heights indicated in the table are considered the maximum for efficient sprinkler protection where sprinklers are only provided at the roof or ceiling.
Note 1 The distance between the maximum permitted storage height and the roof or ceiling sprinklers should not exceed 4 m.
Where storage heights exceed these limits or where the distance between the top of the storage and the roof or ceiling exceeds 4 m, intermediate levels of in-rack sprinklers shall be provided as per 7.2.3 below.
Note 2 Storage height, building height and ceiling clearance (the vertical distance between the roof or ceiling sprinklers and the top of the storage) are all significant variables contributing to the effectiveness and required design density of sprinkler protection.
Intermediate level in-rack sprinklers
Where more than 50 intermediate level sprinklers are installed in the racks, they shall not be fed from the same control valve set as the roof or ceiling sprinklers. The control valve set shall be not less than 100 mm diameter.
Мінімальне значення розрахункової інтенсивності зрошування для дахових або стельових спринклерів повинно становити 7,5 мм/хв для розрахункової площі 260 м2. У разі складування виробів вище рівня, на якому встановлено проміжні спринклери, розрахункові критерії для дахових або стельових спринклерів повинні відповідати значенням, наведеним у таблиці 5.
Для гідравлічного розрахунку необхідно приймати випадок одночасної роботи трьох спринклерів, які знаходяться у гідравлічно най- віддаленішому місці на кожному рівні розміщення внутрішньостелажних спринклерів; у цьому разі для розрахунку береться до трьох рівнів. Якщо ширина проходів між стелажами становить 2,4 м або більше, то для розрахунку необхідно брати лише один стелаж. Якщо ширина проходів між стелажами менша ніж 2,4м, але не менша ніж 1,2 м, то для розрахунку необхідно брати два стелажі. Якщо ширина проходів між стелажами менша ніж 1,2 м, то для розрахунку необхідно брати три стелажі.
Примітка. Не обов'язково розглядати випадок одночасного спрацьовування більше ніж трьох рядів спринклерів у вертикальній площині, а також більше ніж трьох рядів спринклерів у горизонтальній площині.
Внутрішньостелажні спринклери та пов'язані з ними стельові спринклери повинні бути завжди повністю розраховуваними (див. 13.1.1).
Примітка. Мінімальний тиск на будь-якому спринклерному зрошувачі, який працює, становить 2,0 бар (див. 13.4.4).
The design density for the roof or ceiling sprinklers shall be a minimum of 7,5 mm/min over an area of operation of 260 m2. If goods are stored above the highest level of intermediate protection, the design criteria for the roof or ceiling sprinklers shall be taken from Table 5.
For the purposes of hydraulic calculation it shall be assumed that 3 sprinklers are operating simultaneously at the most hydraulically remote position on each level of in-rack sprinklers, up to a maximum of three levels. Where rack aisles are 2,4 m or more in width only one rack need be assumed to be involved. Where rack aisles are less than 2,4 m but greater than or equal to 1,2 m in width, two racks shall be assumed to be involved. Where rack aisles are less than 1,2 m in width, three racks shall be assumed to be involved.
Note It is not necessary to assume simultaneous operation of more than three rows of sprinklers in the vertical plane nor more than three rows of sprinklers in the horizontal plane.
In-rack sprinklers and the associated ceiling sprinklers shall always be fully calculated (see 13.1.1).
Note The minimum pressure at any operating sprinkler is 2,0 bar (see 13.4.4)
.
Таблиця 4 - Вихідні дані для розрахунку систем для захисту приміщень класу HHS з використанням спринклерів, розміщених тільки поблизу від поверхні стелі або даху
Table 4 - Design criteria for HHS with roof or ceiling protection only
Конфігурація складування |
Максимальна допустима висота |
Розрахункова інтенсивність зрошування, |
Розрахункова площа (для водозаповненої системи або системи попередньої дії) |
|||
складування (примітка 1) |
|
|||||
Maximum permitted storage height (see Note 1), m |
||||||
Storage configuration |
Категорія Category I |
Категорія Category II |
Категорія Category III |
Категорія Category IV |
мм/хв Design density mm/min |
(примітка 2), м Area of operation (wet or preaction system (see Note 2)), m2 |
ST1 Безстелажне або штабельне складу- |
5,3 6,5 7,6 |
4,1 5,0 5,9 6,7 7,5 |
2,9 3,5 4,1 4,7 5,2 |
1,6 2,0 2,3 2,7 3,0 |
7,5 10,0 12,5 15,0 17,5 |
260 |
вання Free standing or block stacking |
|
|
5,7 6,3 6,7 7,2 |
3,3 3,6 3,8 4,1 4,4 |
20,0 22,5 25,0 27,5 30,0 |
300 |
ST2 Складування на стоякових піддонах на стелажах в один ряд; Post pallets in single rows ST4 Складування на піддонах на стелажах Palletized racks |
4,7 5,7 6,8 |
3,4 4,3 5,0 5,6 6,0 |
2,2 2,6 3,2 3,7 4,1 |
1,6 2,0 2,3 2,7 3,0 |
7,5 10,0 12,5 15,0 17,5 |
260 |
|
|
4,4 4,8 5,3 5,6 6,0 |
3,3 3,6 3,8 4,1 4,4 |
20,0 22,5 25,0 27,5 30,0 |
300 |
|
ST3 Складування на стоякових піддонах на стелажах у декілька рядів; Post pallets in multiple rows ST5 і/ and ST6 Складування на суцільних або несуцільних полицях Solid or slatted shelves |
4,7 5,7 |
3,4 4,2 5,0 |
2,2 2,6 3,2 |
1,6 2,0 2,3 2,7 3,0 |
7,5 10,0 12,5 15,0 17,5 |
260 |
Кінець табл. 4
Примітка 1. Відстань за вертикаллю від підлоги до відбивачів спринклерів зменшена на 1 м або найвище значення, наведене у таблиці, залежно від того, яке із значень менше.
Note 1 The vertical distance from the floor to the sprinkler deflectors, minus 1 m, or the highest value shown in the table, whichever is the lower.
Примітка 2. He рекомендується застосовувати повітряні та водоповітряні системи для захисту складських приміщень класу HHS особливо у разі складування матеріалів з високою горючістю (вищих категорій) та більшої висоти складування. Якщо існує необхідність встановлення повітряної або водоповітряної системи, розрахункову площу необхідно збільшити на 25 %.
Note 2 Dry and alternate systems should be avoided on High Hazard storage especially with the more combustible products (the higher categories) and the higher storage. Should it nonetheless be necessary to install a dry or alternate system, the area of operation should be increased by 25 %.
Таблиця 5 - Вихідні дані для розрахунку стельових або дахових спринклерів у разі застосування з внутрішньостелажними спринклерами
Table 5 - Design criteria for roof or ceiling sprinklers with in-rack sprinklers
Конфігурація складування Storage configuration |
Максимальна допустима висота складування над верхнім рівнем розміщення внутрішньостелажних спринклерів (примітка 1), м Maximum permitted storage height above the top level of in-rack protection (see Note 1), m |
Розрахункова інтенсивність зрошування, мм/хв Design density mm/min |
Розрахункова площа (для водозаповненої системи або системи попередньої дії) (примітка 2), м2 Area of operation (wet or preaction system (see Note 2)), m2 |
|||
Категорія Category I |
Категорія Category II |
Категорія Category III |
Категорія Category IV |
|||
ST4 Складування на піддонах на стелажах Palletized racks |
3,5 |
3,4 |
2,2 2,6 3,2 3,5 |
1,6 2,0 2,3 2,7 |
7,5 10,0 12,5 15,0 |
260 |
ST5 і/and ST6 Складування на суцільних або несуцільних полицях Solid or slatted shelves |
3,5 |
3,4 |
2,2 2,6 3,2 |
1,6 2,0 2,3 2,7 |
7,5 10,0 12,5 15,0 |
260 |
Примітка 1. Відстань за вертикаллю від найвищого рівня розміщення внутрішньостелажних спринклерів до верхнього рівня складованих виробів. Note 1 The vertical distance from the highest level of in-rack sprinklers to the top of the storage. Примітка 2. He рекомендується застосовувати повітряні та водоповітряні системи для захисту складських приміщень класу HHS особливо у разі складування матеріалів з високою горючістю (вищих категорій) та більшої висоти складування. Якщо існує необхідність встановлення повітряної або водоповітряної системи, розрахункову площу необхідно збільшити на 25 %. Note 2 Dry and alternate systems should be avoided on High Hazard storage especially with the more combustible products (the higher categories) and the higher storage. If it is, nonetheless, necessary to install a dry or alternate system, the area of operation should be increased by 25%. |
Клас пожежної небезпеки Hazard Class |
Витрата, л/хв Flow l/min |
Тиск на вузлі керування, бар Pressure at the control valve set bar |
Максимальна необхідна витрата, л/хв Maximum demand flow l/min |
Тиск на вузлі керування, бар Pressure at the control valve set bar |
LH (захист водозаповненою системою або системою попередньої дії) LH (Wet and pre-action) |
225 |
2,2+ ps |
|
— |
ОН1 Захист водозаповненою системою або системою попередньої дії ОН1 Wet and pre-action |
375 |
1.0 +ps |
540 |
0,7 + ps |
ОН1 Захист повітряною або водоповітряною системами; Dry and alternate ОН2 Захист водозаповненою системою або системою попередньої дії Wet and pre-action |
725 |
1,4+ PS |
1000 |
1,0+ ps |
ОН2 Захист повітряною або водоповітряною системами; Dry and alternate ОНЗ Захист водозаповненою системою або системою попередньої дії Wet and pre-action |
1100 |
1,7 + PS |
1350 |
1,4 + PS |
ОНЗ Захист повітряною або водоповітряною системами; Dry and alternate ОН4 Захист водозаповненою системою або системою попередньої дії Wet and pre-action |
1800 |
2,0+ ps |
2100 |
1.5+ ps |
Примітка. ps- втрата статичного напору через різницю висоти між спринклером, розміщеним на максимальній висоті у певній трубопровідній мережі, і манометром “С” вузла керування, бар. Note ps is the static head loss due to the height of the highest sprinkler in the array concerned above the control valve set ‘C’ gauge, in bar. |