5.18.5 LN: Power cable Name: ZCAB

For a description of this LN, see IEC 61850-5.

ZCAB class

Data object name

Common data class

Explanation

T

MIDI C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.





ZCAB class

Data object name

Common data class

Explanation

T

N1/0/ C

Data objects

Descriptions

EEName

DPL

External equipment name plate


0

Status information

EEHealth

ENS

External equipment health


0

OpTmh

INS

Operation time


0



5.18.6 LN: Capacitor bank Name: ZCAP

For a description of this LN, see IEC 61850-5.

ZCAP class

Data object name

Common data class

Explanation

T

N1/0/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Descriptions

EEName

DPL

External equipment name plate


О

Status information

EEHealth

ENS

External equipment health


о

OpTmh

INS

Operation time


о

DschBIk

SPS

Blocked due to discharge


м

Controls

CapDS

SPC (Capacitor bank device status


м



5.18.7 LN: Converter Name: ZCON

For a description of this LN, see IEC 61850-5.

ZCON class

Data object name

Common data class

Explanation

T

N1/0/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Descriptions

EEName

DPL [External equipment name plate

|O

Status information

EEHealth

ENS

External equipment health


О

OpTmh

INS

Operation time


0

Settings

VArRtg

ASG

Rated bidirectional VArs


0

VRtg

ASG

Rated voltage


о



  1. LN: Generator Name: ZGEN

For a description of this LN, see IEC 61850-5. ZGEN has to be used for all generators not modelled elsewhere in IEC 61850.

ZGEN class

Data object name

Common data class

Explanation

T

N1/0/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



ZGEN class

Data object name

Common data class

Explanation

T

N1/0/ C

Data objects

Descriptions

EEName

DPL

External equipment name plate


О

Status information

EEHealth

ENS

External equipment health


о

OpTmh

INS

Operation time


о

GnSt

ENS

Generator state


м

OpNoLod

SPS

Operation at no load


м

RotDir

ENS

Phase rotation (Clockwise | Counter-Clockwise | Unknown)


м

OpUnExt

SPS

Operation at under-excitation


м

OpOvExt

SPS

Operation at over-excitation


м

LosOil

SPS

Loss of oil


о

LosVac

SPS

Loss of vacuum


О

PresAlm

SPS

Low pressure alarm


о

Controls

GnCtl

DPC

Generator control


м

DExt

SPC

De-excitation


м

AuxSco

SPC

Auxiliary supply change over


О

ReactPwrR

SPC

Reactive power raise


О

React PwrL

SPC

Reactive power lower


о

Measured and metered values

GnSpd

MV

Generator speed


о

Settings

DmdPwr

ASG

Demanded power


О

PwrRtg

ASG

Rated power


о

VRtg

ASG

Rated voltage


О



  1. LN: Gas insulated line Name: ZGIL

For a description of this LN, see IEC 61850-5.

: ZGIL class

Data object name

Common data class

Explanation

T

N1/0/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Descriptions

EEName

DPL

External equipment name plate


О

Status information

EEHealth

ENS

External equipment health


о

OpTmh

INS

Operation time


О



5.18.10 LN: Power overhead line Name: ZLIN

For a description of this LN, see IEC 61850-5. ZLIN represents an overhead line with all physical characteristics. .

ZLIN class

Data object name

Common data class

-Explanation

T

N1/0/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.





ZLIN class

Data object name

Common data class

Explanation

T

М/О/ C

Data objects

Descriptions

EEName

DPL

External equipment name plate


О

Status information

EEHealth

ENS

External equipment health


0

OpTmh

INS

Operation time


О

Settings

LinLenkm

ASG

Line length in km


О

RPs

ASG

Positive-sequence line resistance


О

XPs

ASG

Positive-sequence line reactance


О

RZer

ASG

Zero-sequence line resistance


О

XZer

ASG

Zero-sequence line reactance


О

ZPsMag

ASG

Positive-sequence line impedance value


О

ZPsAng

ASG

Positive-sequence line impedance angle


О

ZZerMag

ASG

Zero-sequence line impedance value


О

ZZerAng

ASG

Zero-sequence line impedance angle


О

RmZer

ASG

Mutual resistance


О

XmZer

ASG

Mutual reactance


О

ZmZerMag

ASG

Mutual impedance value


О

ZmZerAng

ASG

Mutual impedance angle


О



5.18.11 LN: Motor Name: ZMOT

For a description of this LN, see IEC 61850-5.

ZMOT class

Data object name

Common data class

Explanation

T

MIDI C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Descriptions

EEName

DPL

External equipment name plate


0

Status information

EEHealth

ENS

External equipment health


о

OpTmh

INS

Operation time


о

LosOil

SPS

Loss of oil


О

LosVac

SPS

Loss of vacuum


О

PresAlm

SPS

Low pressure alarm


о

Controls

DExt

SPC

De-excitation '


м



5.18.12 LN: Reactor Name: ZREA

For a description of this LN, see IEC 61850-5.

j ZREA class

Data object name

Common data class

Explanation

T

MIDI C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.





ZREA class

Data object name

Common data class

Explanation

T

М/О/ c

Data objects ■ ■' ■ ■ : ' . . . .

Descriptions

EEName

DPL

External equipment name plate


о

Status information -

EEHealth

ENS

External equipment health


0

OpTmh

INS

Operation time


о

Settings

VRtg

ASG

Rated voltage


О

ARtg

ASG

Rated current


о

VARtg

ASG

Rated apparent power


о

VArRtg

ASG

Rated reactive power


О