SIML class |
||||
Data object name |
Common data class |
Explanation |
T |
М/С/ c |
C2H6ppm |
MV |
Measurement of C2Hg in ppm |
|
0 |
O2ppm |
MV |
Measurement of O2 in ppm |
|
о |
CmbuGas |
MV |
Measurement of total dissolved combustible gases (TDCG) |
|
0 |
FltGas |
MV |
Fault gas volume in Buchholz relay |
|
0 |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
о |
LN: Tap changer supervision Name: SLTC
This LN is used for supervision of tap changer. It is used to assess the condition of the tap changer.
SLTC class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
OtIFil |
SPS |
Oil filtration running |
|
о |
MotDrvBIk |
SPS |
Motor drive overcurrent blocking |
|
0 |
VacCelAlm |
SPS |
Circuit status of vacuum cell (ANSI) |
|
0 |
OilFilTr |
SPS |
Oil filter unit trip |
|
0 |
Measured and metered values |
||||
Torq |
MV |
Drive torque |
|
0 |
MotDrvA |
MV |
Motor drive current |
|
о |
AbrPrt |
MV |
Abrasion (in %) of parts subject to wear |
|
о |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
о |
LN: Supervision of operating mechanism Name: SOPM
This LN is used for supervision of operating mechanism for switches. It is used to assess the condition of the operating mechanism and can be used to indicate a possible malfunction in the future.
Today, different technologies for operating mechanisms are available. Typically operating mechanisms for circuit breakers contain an energy storage to provide the required switching energy within a short time. Examples for today’s storage medias are springs or compressed gas. To operate the switch, the energy is transferred by means of a mechanical or hydraulical linkage. A charger motor is used to compensate energy losses due to leakages or to recharge the storage after a switch operation.
The proposed attributes cover the status of the relevant components both of the hydraulic system and the spring system. Depending on the used technology, some of the attributes are not applicable. This LN can also be used for simple operating mechanisms that are directly driven by a motor.SOPM class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
MotOp |
SPS |
Indicates if the motor is running |
|
0 |
MotStrAlm |
SPS |
Alarm for number of motor starts exceeds MotAlmNum |
|
0 |
HyAlm |
SPS |
Hydraulic alarm |
|
0 |
HyBIk |
SPS |
Block of operation due to hydraulic |
|
0 |
EnBIk |
SPS |
Energy block |
|
о |
EnAlm |
SPS |
Energy alarm |
|
0 |
MotAlm |
SPS |
Motor operating time exceeded |
|
о |
HeatAlm |
SPS |
Heater alarm |
|
О |
ChalntvTms |
INS |
Time interval between last two charging operations |
|
о |
MotStr |
INS |
Number of motor starts |
|
о |
Measured and metered values |
||||
En |
MV |
Stored energy (e.g. stored energy or remaining energy) |
|
о |
HyPres |
MV |
Hydraulic pressure |
|
О |
HyTmp |
MV |
Hydraulic temperature |
|
о |
MotTm |
MV |
Operating time of the motor |
|
о |
MotA |
MV |
Motor current |
|
О |
Tmp |
MV |
Temperature inside the drive cubicle |
|
о |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
о |
Settings |
||||
MotAlmTms |
ING |
Alarm level for motor run time in s |
|
о |
MotStrNum |
ING |
Alarm level for number of motor starts |
|
о |
MotStrTms |
ING |
Time interval for acquisition of motor starts |
|
о |
LN: Monitoring and diagnostics for partial discharges Name: SPDC
For a description of this LN, see IEC 61850-5. IEC 60270 should be applied.
SPDC class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
PaDschAlm |
SPS |
Partial discharge alarm |
|
c |
OpCnt |
INS |
Operation counter |
|
M |
Measured and metered values |
||||
AcuPaDsch |
MV |
Acoustic level of partial.discharge |
|
c |
SPDC class |
||||
Data object name |
Common data class |
Explanation |
T |
м/с/ c |
AppPaDsch |
MV |
Apparent charge of partial discharge, peak level (PD) |
|
c |
NQS |
MV |
Average discharge current |
|
c |
UhfPaDsch |
MV |
UHF level of partial discharge |
|
c |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
о |
Settings |
||||
CtrHz |
ASG |
Center frequency of measurement unit according to IEC 60270 |
|
о |
BndWid |
ASG |
Bandwidth of measurement unit according to IEC 60270 |
|
О |
Condition C: depending on the functionality, at least one of the data objects AcuPaDsch, UHFPaDch, NQS, AppPaDsch or PaDschAlm shall be used. |
LN: Power transformer supervision Name: SPTR
This LN is used for supervision of power transformer. It is used to asses the condition of the power transformer.
SPTR class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
HPTmpAlm |
SPS |
Winding hotspot temperature alarm |
|
о |
HPTmpOp |
SPS |
Winding hotspot temperature operate |
|
о |
HPTmpTr |
SPS |
Winding hotspot temperature trip |
T |
О |
MbrAlm |
SPS |
Leakage supervision alarm of tank conservator membrane |
|
о |
CGAIm |
SPS |
Core ground alarm |
|
о |
HeatAlm |
SPS |
Heater alarm |
|
о |
Measured and metered values |
||||
AgeRte |
MV |
Aging rate |
|
О |
BotTmp |
MV |
Bottom oil temperature |
|
о |
CoreTmp |
MV |
Core temperature |
|
о |
HPTmpCIc |
MV |
Calculated winding hotspot temperature |
|
о |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
о |
LN: Circuit switch supervision Name: SSWI
This LN is used for supervision of all switches, such as disconnectors, earthing switches, etc. except circuit breakers. It is used to assess the condition of the switch and is closely related to LN SOPM. Most attributes are used to supervise the operation time of the switch and contact movement. Deviations from nominal values can be used to indicate a possible malfunction of the switch in the future. Abrasion of parts gives an indication when to maintain the switch. For the special requirements of a circuit breaker, the abrasion, etc. is defined in LN SCBR. The supervision SSWI is per phase.
SSWI class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
OpTmAlm |
SPS |
Switch operating time exceeded |
|
0 |
OpCntAlm |
SPS |
Number of operations (modelled in XSWI) has exceeded the alarm level for number of operations |
|
о |
OpCntWrn |
SPS |
Number of operations (modelled in XSWI) exceeds the warning limit |
|
о |
|
|
|
|
|
OpTmWrn |
SPS |
Warning when operation time reaches the warning level |
|
О |
OpTmh |
INS |
Time since installation or last maintenance in hours |
|
О |
MechHealth |
ENS |
Mechanical behaviour alarm |
|
о |
Measured and metered values |
||||
AccAbr |
MV |
Cumulated abrasion of parts subject to wear |
|
О |
AuxSwTmOpn |
MV |
Auxiliary switches timing open |
|
о |
AuxSwTmCIs |
MV |
Auxiliary switches timing close |
|
о |
RctTmOpn |
MV |
Reaction time measurement open |
|
о |
RctTmCIs |
MV |
Reaction time measurement close |
|
о |
OpSpdOpn |
MV |
Operation speed open |
|
о |
OpSpdCIs |
MV |
Operation speed close |
|
О |
OpTmOpn |
MV |
Operation time open |
|
О |
OpTmCIs |
MV |
Operation time close |
|
о |
Stk |
MV |
Contact stroke |
|
о |
OvStkOpn |
MV |
Overstroke open |
|
о |
OvStkCls |
MV |
Overstroke close |
|
о |
ColA |
MV |
Coil current |
|
о |
Tmp |
MV |
Temperature e.g. inside drive mechanism |
|
о |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
о |
Settings |
||||
OpAlmTmh |
ING |
Alarm level for operation time in hours |
|
о |
OpWrnTmh |
ING |
Warning level for operation time in hours |
|
О |
OpAlmNum |
ING |
Alarm level for number of operations |
|
о |
OpWrnNum |
ING |
Warning level for number of operations |
|
о |