SIML class

Data object name

Common data class

Explanation

T

М/С/ c

C2H6ppm

MV

Measurement of C2Hg in ppm


0

O2ppm

MV

Measurement of O2 in ppm


о

CmbuGas

MV

Measurement of total dissolved combustible gases (TDCG)


0

FltGas

MV

Fault gas volume in Buchholz relay


0

Controls

OpCntRs

INC

Resettable operation counter


о



  1. LN: Tap changer supervision Name: SLTC

This LN is used for supervision of tap changer. It is used to assess the condition of the tap changer.

SLTC class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

OtIFil

SPS

Oil filtration running


о

MotDrvBIk

SPS

Motor drive overcurrent blocking


0

VacCelAlm

SPS

Circuit status of vacuum cell (ANSI)


0

OilFilTr

SPS

Oil filter unit trip


0

Measured and metered values

Torq

MV

Drive torque


0

MotDrvA

MV

Motor drive current


о

AbrPrt

MV

Abrasion (in %) of parts subject to wear


о

Controls

OpCntRs

INC

Resettable operation counter


о



  1. LN: Supervision of operating mechanism Name: SOPM

This LN is used for supervision of operating mechanism for switches. It is used to assess the condition of the operating mechanism and can be used to indicate a possible malfunction in the future.

Today, different technologies for operating mechanisms are available. Typically operating mechanisms for circuit breakers contain an energy storage to provide the required switching energy within a short time. Examples for today’s storage medias are springs or compressed gas. To operate the switch, the energy is transferred by means of a mechanical or hydraulical linkage. A charger motor is used to compensate energy losses due to leakages or to recharge the storage after a switch operation.

The proposed attributes cover the status of the relevant components both of the hydraulic system and the spring system. Depending on the used technology, some of the attributes are not applicable. This LN can also be used for simple operating mechanisms that are directly driven by a motor.SOPM class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

MotOp

SPS

Indicates if the motor is running


0

MotStrAlm

SPS

Alarm for number of motor starts exceeds MotAlmNum


0

HyAlm

SPS

Hydraulic alarm


0

HyBIk

SPS

Block of operation due to hydraulic


0

EnBIk

SPS

Energy block


о

EnAlm

SPS

Energy alarm


0

MotAlm

SPS

Motor operating time exceeded


о

HeatAlm

SPS

Heater alarm


О

ChalntvTms

INS

Time interval between last two charging operations


о

MotStr

INS

Number of motor starts


о

Measured and metered values

En

MV

Stored energy (e.g. stored energy or remaining energy)


о

HyPres

MV

Hydraulic pressure


О

HyTmp

MV

Hydraulic temperature


о

MotTm

MV

Operating time of the motor


о

MotA

MV

Motor current


О

Tmp

MV

Temperature inside the drive cubicle


о

Controls

OpCntRs

INC

Resettable operation counter


о

Settings

MotAlmTms

ING

Alarm level for motor run time in s


о

MotStrNum

ING

Alarm level for number of motor starts


о

MotStrTms

ING

Time interval for acquisition of motor starts


о



  1. LN: Monitoring and diagnostics for partial discharges Name: SPDC

For a description of this LN, see IEC 61850-5. IEC 60270 should be applied.

SPDC class

Data object name

Common data class

Explanation

T

М/О/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

PaDschAlm

SPS

Partial discharge alarm


c

OpCnt

INS

Operation counter


M

Measured and metered values

AcuPaDsch

MV

Acoustic level of partial.discharge


c



SPDC class

Data object name

Common data class

Explanation

T

м/с/ c

AppPaDsch

MV

Apparent charge of partial discharge, peak level (PD)


c

NQS

MV

Average discharge current


c

UhfPaDsch

MV

UHF level of partial discharge


c

Controls

OpCntRs

INC

Resettable operation counter


о

Settings

CtrHz

ASG

Center frequency of measurement unit according to IEC 60270


о

BndWid

ASG

Bandwidth of measurement unit according to IEC 60270


О

Condition C: depending on the functionality, at least one of the data objects AcuPaDsch, UHFPaDch, NQS, AppPaDsch or PaDschAlm shall be used.



  1. LN: Power transformer supervision Name: SPTR

This LN is used for supervision of power transformer. It is used to asses the condition of the power transformer.

SPTR class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

HPTmpAlm

SPS

Winding hotspot temperature alarm


о

HPTmpOp

SPS

Winding hotspot temperature operate


о

HPTmpTr

SPS

Winding hotspot temperature trip

T

О

MbrAlm

SPS

Leakage supervision alarm of tank conservator membrane


о

CGAIm

SPS

Core ground alarm


о

HeatAlm

SPS

Heater alarm


о

Measured and metered values

AgeRte

MV

Aging rate


О

BotTmp

MV

Bottom oil temperature


о

CoreTmp

MV

Core temperature


о

HPTmpCIc

MV

Calculated winding hotspot temperature


о

Controls

OpCntRs

INC

Resettable operation counter


о



  1. LN: Circuit switch supervision Name: SSWI

This LN is used for supervision of all switches, such as disconnectors, earthing switches, etc. except circuit breakers. It is used to assess the condition of the switch and is closely related to LN SOPM. Most attributes are used to supervise the operation time of the switch and contact movement. Deviations from nominal values can be used to indicate a possible malfunction of the switch in the future. Abrasion of parts gives an indication when to maintain the switch. For the special requirements of a circuit breaker, the abrasion, etc. is defined in LN SCBR. The supervision SSWI is per phase.


SSWI class

Data object name

Common data class

Explanation

T

М/О/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

OpTmAlm

SPS

Switch operating time exceeded


0

OpCntAlm

SPS

Number of operations (modelled in XSWI) has exceeded the alarm level for number of operations


о

OpCntWrn

SPS

Number of operations (modelled in XSWI) exceeds the warning limit


о






OpTmWrn

SPS

Warning when operation time reaches the warning level


О

OpTmh

INS

Time since installation or last maintenance in hours


О

MechHealth

ENS

Mechanical behaviour alarm


о

Measured and metered values

AccAbr

MV

Cumulated abrasion of parts subject to wear


О

AuxSwTmOpn

MV

Auxiliary switches timing open


о

AuxSwTmCIs

MV

Auxiliary switches timing close


о

RctTmOpn

MV

Reaction time measurement open


о

RctTmCIs

MV

Reaction time measurement close


о

OpSpdOpn

MV

Operation speed open


о

OpSpdCIs

MV

Operation speed close


О

OpTmOpn

MV

Operation time open


О

OpTmCIs

MV

Operation time close


о

Stk

MV

Contact stroke


о

OvStkOpn

MV

Overstroke open


о

OvStkCls

MV

Overstroke close


о

ColA

MV

Coil current


о

Tmp

MV

Temperature e.g. inside drive mechanism


о

Controls

OpCntRs

INC

Resettable operation counter


о

Settings

OpAlmTmh

ING

Alarm level for operation time in hours


о

OpWrnTmh

ING

Warning level for operation time in hours


О

OpAlmNum

ING

Alarm level for number of operations


о

OpWrnNum

ING

Warning level for number of operations


о