1. LN: Ramp function Name: FRNIP

Logical node FRMP shall be used as a generic ramp. The LN is required due to the fact that the data object attributes of the ASG common data class do not contain all of the information required to achieve a full ramping function with divergent up and down trends.

FRMP class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Adj St

ENS

State of adjustment process


0

Measured and metered values

Out

MV

Ramp output


M

ErrTerm

MV

Control loop termination error value


0

Settings .

RmpUp

ASG

Ramping rate on a upward trend


0

RmpDn

ASG

Ramping rate on a downward trend


0

StepPs

ASG

Step size when turning from negative to positive direction


о

StepNg

ASG

Step size when turning from positive to negative direction


0



  1. LN: Set-point control function Name: FSPT

Logical node FSPT shall be used to provide the common characteristics found in all controller or regulator type logical nodes. The LN can be standalone or cascaded with other logical nodes to form a complete controller.



FSPT class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Loc

SPS

Local control behaviour


о

SptDvAlm

SPS

Deviation alarm


о

SptUp

SPS

Setpoint going up (raising)


о

SptDn

SPS

Setpoint going up (lowering)


о

SptDir

SPS

Setpoint direction


О

SptEndSt

ENS

End status of set-point control


О

Adj St

ENS

Adjustment status


о

Measured Values

SptMem

MV

Setpoint in memory


М

ErrTerm

MV

Control loop termination error value


о

Out

MV

Output


О

Controls

SptChg

ВАС

Setpoint change (raise, lower)


О

SptVal

APC

Setpoint


м

Auto

SPC

Automatic operation


о

Settings

MaxRst

ASG

Maximum restriction


о

MinRst

ASG

Minimum restriction


о

DvAlm

ASG

Deviation alarm


О



  1. LN: Action at over threshold Name: FXOT

Logical node FXOT shall be used to set a high-level threshold value to be used in control sequences. If a second level is necessary, a second instance can be modelled. FXOT can typically be used whenever a protection, control or alarm function is based on other physical measurements than primary electrical data.

FXOT class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Op

ACT

Level of action reached

T

M

Settings

StrVal

ASG

Start level set-point


c

OpDITmms

ING

Operate delay time [ms]


0

StrCrv

CSG

Start level curve


c

RsDITmms

ING

Reset operate delay time [ms]


о

Condition: Start level shall be given as a singular point or as a curve.



  1. LN: Action at under threshold Name: FXUT

Logical node FXUT shall be used to set a low-level threshold value to be used in control sequences. If a second level is necessary, a second instance can be modelled. FXUT can

typically be used whenever a protection, control or alarm function is based on other physical measurements than primary electric data.

FXUT class

Data object name

Common data class

Explanation

T

MIDI C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- lnstance-!D according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Op

ACT

Level of action reached

T

M

Settings

StrVal

ASG

Start level set-point


C

OpDITmms

ING

Operate delay time [ms]


0

StrCrv

CSG

Start level curve


C

RsDITmms

ING

Reset operate delay time [ms]


0

Condition: Start level shall be given as a singular point or as a curve.



  1. Logical nodes for generic references LN Group: G

    1. Modelling remarks

The logical nodes of group G shall be used only for modelling functions without a dedicated logical node with appropriate semantics. Therefore, no description and requirements for the logical nodes of group G are given in IEC 61850-5.

  1. LN: Generic automatic process control Name: GAPC

This node shall be used only to model in a generic way the processing/automation of functions that are not predefined by one of the groups A, С, M, P, or R. If needed, all data objects listed in Clause 6 of this standard can be used single or multiple for a dedicated application of LN GAPC. Data objects with proper semantic meaning should be preferred. The extension rules according to IEC 61850-7-1, Clause 14 shall be followed.

GAPC class

Data object name

Common data class

Explanation

T

MIDI C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

LocKey

SPS

Local or remote key


0

Loc

SPS

Local control behaviour


0

Auto

SPC

Automatic operation


О

Str1

ACD

Start


0

0p1

ACT

Operate

T

0

Alm1

SPS

Generic single alarm


0

Wm1

SPS

Generic single warning


О

Ind1

SPS

Generic single indication


О

Controls

OpCntRs

INC

Resettable operation counter


О

LocSta

SPC

Switching authority at station level


о

SPCSO1

SPC

Single point controllable status output


О

DPCSO1

DPC

Double point controllable status output


О

GAPC class

Data object name

Common data class

Explanation

T

М/О/ c

ISCSO1

INC

Integer status controllable status output


0

Settings

StrVaH

ASG

Start value


о



  1. LN: Generic process I/O Name: GGIO

This node shall be used only to model in a generic way process devices that are not predefined by the groups S, T, X, Y, or Z. If needed, all data objects listed in Clause 6 can be used single or multiple for a dedicated application of LN GGIO. Data objects with proper semantic meaning should be preferred. The extension rules according to IEC 61850-7-1, Clause 14 shall be followed.

GGIO class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Descriptions

EEName

DPL

External equipment name plate


о

Status information

EEHealth

ENS

External equipment health


о

LocKey

SPS

Local or remote key


О

Loc

SPS

Local control behaviour


о

Intlnl

INS

Integer status input


о

Alm1

SPS

General single alarm


О

Wrn1

SPS

General single warning


о

Indi

SPS

General indication (binary input)


о

Measured and metered values

An)n1

MV

Analogue input


о

AnOutl

APC

Controllable analogue output


о

CntRsI

BCR

Counter, resettable


о

Controls

OpCntRs

INC

Resettable operation counter


о

LocSta

SPC

Switching authority at station level


о

SPCSO1

SPC

Single point controllable status output


о

DPCSO1

DPC

Double point controllable status output


О

ISCSO1

INC

Integer status controllable status output


о



  1. LN: Generic log Name: GLOG

The LN GLOG refers to a function which allows to log not only changed data itself but also any related data being defined in the settings of LN GLOG. The logging is started by the changed data object (TrgRefl) or by the operator (LogTrg). The logged data are identified by the references to the related source data objects in the data model.



GLOG class

Data object name

Common data class

Explanation

T

MIDI C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Logged Status information, Measured and metered values, Controls, Settings

Access via LOG only


Included value assigned to InRefl


0

Controls

OpCntRs

INC

Counts the events logged (resettable)


0

LogTrg

SPC

Trigger logging by operator


0

Settings

LogRef

ORG

Reference to Log


о

TrgRefl

ORG

Trigger reference shows the receiving trigger signal


0

InRefl

ORG

Reference to data objects / data attributes to include in LOG according to IEC 61850-7-2, when the configured trigger was active


о