|
Data object name |
Semantics |
|||||
|
TddOddA |
Current total demand distortion (according to IEEE 519, odd components, phase-related) |
|||||
|
TddOddAmp |
Current total demand distortion (according to IEEE 519, odd components, non-phase-related) |
|||||
|
TestRsI |
Test results value is TRUE if passed and FALSE if failed |
|||||
|
ThdA |
Current total harmonic or interharmonic distortion (different methods, phase-related) |
|||||
|
ThdAmp |
Current total harmonic or interharmonic distortion (different methods, non-phase-related) |
|||||
|
ThdATmms |
Total harmonic or interharmonic distortion current alarm delay time in ms after the ThdAVal has been exceeded |
|||||
|
ThdAVal |
Total harmonic or interharmonic distortion amperes alarm setting - value entered in %. Thd values above this threshold cause an alarm. |
|||||
|
ThdEvnA |
Current total harmonic or interharmonic distortion (even components, phase-related) |
|||||
|
ThdEvnAmp |
Current total harmonic or interharmonic distortion (different methods, even components, nonphase-related) |
|||||
|
ThdEvnPhV |
Phase to ground voltage total harmonic or interharmonic distortion (different methods, even components, phase-related) |
|||||
|
ThdEvnPPV |
Phase to phase voltage total harmonic or interharmonic distortion (different methods, even components, phase-related) |
|||||
|
ThdEvnVol |
Phase voltage total harmonic or interharmonic distortion (different methods, even components, non-phase-related) |
|||||
|
ThdOddA |
Current total harmonic or interharmonic distortion (different methods, odd components, phase- related) |
|||||
|
ThdOddAmp |
Current total harmonic or interharmonic distortion (different methods, odd components, nonphase-related) |
|||||
|
ThdOddPhV |
Phase to ground voltage total harmonic or interharmonic distortion (different methods, odd components, phase-related) |
|||||
|
ThdOddPPV |
Phase to phase voltage total harmonic or interharmonic distortion (different methods, odd components, phase-related) |
|||||
|
ThdOddVol |
Phase to ground voltage total harmonic or interharmonic c components, non-phase-related) |
istortion (different methods, odd |
||||
|
ThdPhV |
Phase to ground voltage total harmonic or interharmonic c related) |
istortion (different methods, phase- |
||||
|
ThdPPV |
Phase to phase voltage total harmonic or interharmonic distortion (different methods, phase- related) |
|||||
|
ThdVol |
Voltage total harmonic or interharmonic distortion (different methods, non-phase-related) |
|||||
|
ThdVTmms |
Total harmonic or interharmonic distortion voltage alarm time delay in ms after the ThdVVal has been exceeded |
|||||
|
ThdVVal |
Total harmonic or interharmonic distortion alarm setting - value entered in %. Thd values above this threshold cause an alarm. |
|||||
|
Tmlms |
Time constant 1 [ms] |
|||||
|
Tmlldms |
Time constant 1 (lead) [ms] |
|||||
|
Tm2ms |
Time constant 2 [ms] |
|||||
|
Tm2ldms |
Time constant 2 (lead) [ms] |
|||||
|
Tm3ms , |
Time constant 3 [ms] |
|||||
|
TmAcc |
Number of significant bits in the Fraction Of Second in the time accuracy part of the time stamp. See IEC 61850-7-2. |
|||||
|
TmAChr33 |
Multiline curve characteristic definition. It is not multiple instantiable within one LN instance |
|||||
|
TmACrv |
Characteristic curve for protection operation of the form: у = f(x), where x is the current (A) and у is the time (Tm). The integers representing the different curves are given in the definition of CDC CURVE in IEC 61850-7-3. |
|||||
|
TmASt |
Delivers the active curve characteristic |
|||||
|
TmChgDayTm |
Local time of next change to daylight saving time |
|||||
|
TmChgStdTm |
Local time of next change to standard time |
|||||
|
Data object name |
Semantics |
|||||
|
TmChStl |
Time channel status (up/down) |
|||||
|
TmDIChr |
Time delay linear or inverse characteristic. |
|
||||
|
|
Timer delay |
Value |
|
|||
|
Linear |
TRUE |
|||||
|
Inverse characteristic |
FALSE |
|||||
|
|
|
|
||||
|
TmDIMod |
Operate time delay mode. TRUE = on, FALSE = off |
|||||
|
TmDT |
Indicating if for this location daylight saving time is in effect now. |
|||||
|
TmExc |
TRUE = Maximum allowed time exceeded (LN CPOW) |
|||||
|
TmMult |
This data object is the time dial multiplier or time dial setting mainly used for protection. |
|||||
|
TmOfsTmm |
Offset of local time from UTC in minutes |
|||||
|
TmTmpChr33 |
Multiline curve characteristic definition. It is not multiple instantiable within one LN instance. |
|||||
|
Tmp |
The temperature of a specified component or in a specified volume (usually in °С) |
|||||
|
TmpAlm |
Temperature alarm because of an abnormal condition (FALSE = normal, TRUE = alert) |
|||||
|
TmpMax |
Maximum temperature |
|||||
|
TmpRI |
Relation between temperature and maximum temperature |
|||||
|
TmSrc |
Current time source |
|||||
|
TmSrcSetl |
Time source setting (“1588” in case the time source is a IEEE 1588 source or dotted IP-address) |
|||||
|
TmSyn |
Time synchronized according to IEC 61850-9-2 |
|
||||
|
|
TmSyn |
Value |
|
|||
|
Synchronized by a global area clock signal |
2 |
|||||
|
Synchronized by a local area clock signal |
1 |
|||||
|
Synchronized by an external area clock signal |
0 |
|||||
|
|
|
|
||||
|
TmTa |
Armature time constant Ta[s] (unsaturated) |
|||||
|
TmTdp |
D-axis short circuit transient time constant Td’ [s] (unsaturated) |
|||||
|
TmTds |
D-axis short-circuit sub-transient time constant Td"[s] (unsaturated) |
|||||
|
TmTmpCrv |
Characteristic curve for protection operation of the form: у = f(x), where x is the temperature (Tmp) and у is the time (Tm). The integers representing the different curves are given in the definition of CDC CURVE in IEC 61850-7-3. |
|||||
|
TmTmpSt |
Delivers the active curve characteristic |
|||||
|
TmTqOp |
Q-axis open circuit transient time constant TqO' [s] (unsaturated) |
|||||
|
TmTqOs |
Q-axis open circuit sub-transient time constant Tq0”[s] (unsaturated) |
|||||
|
TmTqp |
Q-axis short circuit transient time constant Tq’ [sj (unsaturated) |
|||||
|
TmTqs |
Q-axis short circuit sub-transient time constant Tq ’’[s] (unsaturated) |
|||||
|
TotTmms |
Total time of synchronising process |
|||||
|
TmUseDT |
Flag indicating if this location is using daylight saving time |
|||||
|
TmVChr33 |
Multiline curve characteristic definition. It is not multiple instantiable within one LN instance. |
|||||
|
TmVCrv |
Characteristic curve for protection operation of the form: у = f(x), where x is the voltage (V) and у is the time (Tm). The integers representing the different curves are given in the definition of CDC CURVE in IEC 61850-7-3. |
|||||
|
TmVSt |
Delivers the active curve characteristic |
|||||
|
Torq |
Drive torque |
|||||
|
TotPF |
Average power factor for a three-phase circuit (per unit) |
|||||
|
TotVA |
Total apparent power in a three-phase circuit |
|||||
|
TotVAh |
Net apparent energy since last rest - |
|||||
|
Data object name |
Semantics |
|||||
|
TotVAr |
Total reactive power in a three-phase circuit |
|||||
|
TotVArh |
Net reactive energy since last reset |
|||||
|
TotW |
Total real power in a three-phase circuit |
|||||
|
TotWh |
Net real energy since last reset |
|||||
|
TpcBIk |
Teleprotection in blocked state |
|||||
|
TpcRxMod |
Teleprotection application mode in receive direction for each command (unused, blocking, permissive, direct, unblocking, status) |
|||||
|
TpcTxMod |
Teleprotection application mode in transmit direction for each command (unused, blocking, permissive, direct, unblocking, status) |
|||||
|
TPTrTmms / |
Three-pole delay time in milliseconds before the breaker failure tries to retrip the failed breaker |
|||||
|
Tr 7 |
Trip is the command to open the breaker when issued in case of fault by PTRC |
|||||
|
TrBeh |
Indicates for the next Trip if single pole tripping is allowed or three-pole tripping requested. |
|||||
|
|
Trip behavior |
Value |
|
|||
|
Single pole tripping |
1 |
|||||
|
Undefined (default) |
2 |
|||||
|
Three pole tripping |
3 |
|||||
|
|
|
|
||||
|
TrgMod |
Disturbance recorder trigger mode. The source of the external trigger is a local issue. |
|||||
|
|
Trigger Mode |
Value |
|
|||
|
Internal |
1 |
|||||
|
External |
2 |
|||||
|
Both |
3 |
|||||
|
|
|
|
||||
|
TrgRef |
Trigger reference shows the receiving trigger signal. It can be multiple in one LN-lnstance. |
|||||
|
TrMod |
This data object represents a type of trip function; 3ph means only 3phase tripping possible, 1ph or 3ph means PTRC with 1 and 3 phase tripping possibility and first trip depending on fault type. |
|||||
|
TrPlsTmms |
Trip pulse time is the minimum pulse time for breaker operation. |
|||||
|
TxBIk |
Blocking information to be transmitted to the other side (teleprotection blocking signal) |
|||||
|
TxCnt |
Number of sent messages |
|||||
|
TxPrm |
Permissive information to be transmitted to the other side (teleprotection permissive signal) |
|||||
|
TxTr |
Direct trip information to be transmitted to the other side |
|||||
|
TypRsCrv |
This is the type of the reset curve that is used to co-ordinate the reset with electromechanical relays that do not reset instantaneously. |
|||||
|
|
Reset curve |
Value |
|
|||
|
None |
1 |
|||||
|
Definite time delayed reset |
2 |
|||||
|
Inverse reset |
3 |
|||||
|
|
|
|
||||
|
UHFPaDsch |
UHF level of partial discharge |
|||||
|
UnbDetMth |
Unbalance detection method is the method used to detect the unbalanced condition based on measured or calculated phase or sequence components of the monitored by the logical node system parameters. |
|||||
|
|
Unbalance detection method |
Value |
|
|||
|
Negative sequence |
1 |
|||||
|
Zero sequence |
2 |
|||||
|
Negative sequence / positive sequence |
3 |
|||||
|
Zero sequence / positive sequence |
4 |
|||||
|
Phase vectors comparison |
5 |
|||||
|
Others |
6 |
|||||
|
|
|
|
||||
|
|
||||||
|
Data object name |
Semantics |
|||||||
|
UnBlkMod |
This data object is the unblock function mode. |
|
||||||
|
|
Unblock function mode |
Value |
|
|||||
|
Off |
1 |
|||||||
|
Permanent |
2 |
|||||||
|
Time window |
3 |
|||||||
|
|
|
|
||||||
|
UnBlkJmms |
Unblocking time |
|||||||
|
UnHzStr |
Start (underfrequency variation event in progress) |
|||||||
|
UnHzStrVal |
Underfrequency start point |
|||||||
|
Up |
Last count direction upward |
|||||||
|
UrcbTrk |
Access service tracking for unbuffered report control block |
|||||||
|
UsvcbTrk |
Access service tracking for unicast sampled values control block |
|||||||
|
UseCyc |
Actual set maximum number of cycles for any cyclic process, for example used for the autorecloser |
|||||||
|
V1Clc |
Average value U- at side 1 of the breaker. The side is not standardized; Common use: = reference voltage or running voltage. |
|||||||
|
V2Clc |
Average value ІЛ) at side 2 of the breaker. The side is not standardized; Common use: U2- variable voltage or incoming voltage. |
|||||||
|
VA |
Phase apparent power |
|||||||
|
VAr |
Phase reactive power (Q) |
|||||||
|
VAdj |
This data object allows to switch off the voltage matching function of an automatic synchroniser; TRUE = ON; FALSE = OFF |
|||||||
|
VAdpFact |
Adaptation factor U-l U2'. Equalising factor for the average values of the two voltages and U2. The data object is used to correct measuring errors or deviation in the ratio of the VT. |
|||||||
|
VarStr |
Start of the frequency variation event |
|||||||
|
VarEnd |
Event finished but not reset |
|||||||
|
Vbr |
Vibration level [mm/s2] |
|||||||
|
VbrAlmSpt |
Vibration alarm level set-point |
|||||||
|
VbrTrpSpt |
Vibration trip level set-point |
|||||||
|
VChr |
Voltage adjustment characteristic: definition of the rate of change of the voltage regulator. The value is 1/s. |
|||||||
|
VerWdDir |
Vertical wind direction |
|||||||
|
VerWdSpd |
Average vertical wind speed [usually in m/s] |
|||||||
|
VHzChr33 |
Multiline curve characteristic definition. It is not multiple instantiable within one LN instance. |
|||||||
|
VHzCrv |
Characteristic curve for protection operation of the form: у = f(x), where x is the frequency (Hz) and у is the voltage (V). The integers representing the different curves are given in the definition of CDC CURVE in IEC 61850-7-3. |
|||||||
|
VHzSt |
Delivers the active curve characteristic |
|||||||
|
Vlnd |
This data object indicates whether the voltage difference (average value) between the two voltages to be synchronised is within the set limits or not. FALSE = value within the limits; TRUE = value outside the limits. |
|||||||
|
VlnvTms |
Voltage adjustment pulse interval: defines the time between two adjusting pulses |
|||||||
|
VNom |
This data object is used to set the nominal secondary voltage (input voltage to the synchroniser), in case the measuring voltages are connected hardwired to the synchroniser. |
|||||||
|
Vim |
Volumetric content of a container, reservoir, dam or tank [usually in m3] |
|||||||
|
VlmCap |
Maximum volume onto which container can be filled |
|||||||
|
Vol |
AC voltage non-phase-related or DC voltage |
|||||||
|
VolAmp |
Apparent power measurement of a non-three-phase circuit |
|||||||
|
VolAmpr |
Volt-amperes reactive of a non-three-phase circuit |
|||||||
|
Data object name |
Semantics |
|||||||
|
VolChgRte |
Rate of voltage change (change over time) |
|||||||
|
VolNgGnd |
Voltage between positive pole and earth |
|||||||
|
VolPsGnd |
Voltage between negative pole and earth |
|||||||
|
VolResoPt |
Voltage at the resonance point in compensated networks |
|||||||
|
VOvSt |
TRUE = indicates voltage override control status |
|||||||
|
VRed |
TRUE = voltage reduction is active to reduce load side voltage below the normal setting |
|||||||
|
VRed Vai |
Reduction of band centre (percent) when voltage step x is active |
|||||||
|
VRtg |
Rated voltage, intrinsic property of the device, which cannot be set/changed from remote |
|||||||
|
VStr |
Value of the voltage that must be reached for a dedicated action to be started of the related function |
|||||||
|
VTrsTm |
Voltage transient duration |
|||||||
|
VVa |
Voltage variation magnitude of the last completed event |
|||||||
|
WaTm |
Voltage variation duration of the last completed event |
|||||||
|
W |
Phase active power (P) |
|||||||
|
WacTrg |
The number of times the watchdog circuit has reset the device since the counter reset. |
|||||||
|
Wrn |
General warning. It can be multiple in one LN-instance. |
|||||||
|
Watt |
Real power in a non-three-phase circuit |
|||||||
|
WeiMod |
This data object is the weak end infeed function mode. NOTE Normal are values 1, 3 and 4. |
|||||||
|
|
Weak end infeed mode |
Value |
|
|||||
|
Off |
1 |
|||||||
|
Operate |
2 |
|||||||
|
Echo |
3 |
|||||||
|
Echo and operate |
4 |
|||||||
|
|
|
|
||||||
|
WeiOp |
Operate signal from week end infeed function |
|||||||
|
WeiTmms |
Co-ordination time for weak end feed function in ms |
|||||||
|
WetBlbTmp |
Wet bulb temperature [usually in °С] |
|||||||
|
WdGustSpd |
Maximum wind gust speed [usually in m/s] |
|||||||
|
WrmStr |
The number of warm starts made by the physical/logical device since the last reset |
|||||||
|
XZer |
Zero sequence line reactance |
|||||||
|
XPs |
Positive sequence line (reach) reactance |
|||||||
|
X2 |
Negative sequence reactance X2 [per unit] (unsaturated) |
|||||||
|
Xd |
D-axis synchronous reactance Xd [per unit] (unsaturated) |
|||||||
|
Xdp |
D-axis transient synchronous reactance Xd' [per unit] (unsaturated) |
|||||||
|
Xds |
D-axis reactance Xd" [per unit] (unsaturated) |
|||||||
|
XmZer |
Mutual reactance coupling from parallel line |
|||||||
|
Xq |
Q-axis synchronous reactance Xq [per unit] (unsaturated) •• |
|||||||
|
Xqp |
Q-axis transient reactance Xq’ [per unit] (unsaturated) |
|||||||
|
Xqs |
Q-axis sub-transient reactance Xq" [per unit] (unsaturated) |
|||||||
|
Z |
Line impedance of all phases in a three-phase system (ZL1, ZL2, LZ3) |
|||||||
|
ZZerAng |
Zero sequence source angle, near end (A) |
|||||||
|
ZZerMag |
Zero sequence source magnitude, remote end (B) |
|||||||
|
ZPsAng |
Positive sequence line angle |
|||||||
|
ZPsMag |
Positive sequence line magnitude |
|||||||
|
ZeroEna |
Zero sequence current supervision enabled (TRUE) |
|||||||