ДСТУ IEC 61850-7-4:2014 сторінка 18 з 39
For a description of this LN, see IEC 61850-5 (LN PPFR). This LN shall be used for the underpower factor part of PPFR.
|
PUPF class |
||||
|
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
|
LNName |
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|||
|
Data objects |
||||
|
Status information |
||||
|
Str |
ACD |
Start |
M |
|
|
Op |
ACT |
Operate |
T |
M |
|
ВI kA |
SPS |
Blocked below minimum operating current |
0 |
|
|
BlkV |
SPS |
Blocked below minimum operating voltage |
0 |
|
|
Controls |
||||
|
OpCntRs |
INC |
Resettable operation counter |
0 |
|
|
Settings |
||||
|
StrVal |
ASG |
Start value |
0 |
|
|
OpDITmms |
ING |
Operate delay time |
о |
|
|
RsDITmms |
ING |
Reset delay time |
0 |
|
|
BlkValA |
ASG |
Block value (minimum operating current) |
о |
|
|
BlkVaIV |
ASG |
Block value (minimum operating voltage) |
о |
|
-
LN: Voltage controlled time overcurrent Name: PVOC
|
For a description of this LN, see IEC 61850-5.PVOC class |
||||
|
Data object name |
Common data class |
Explanation |
T |
M/O/C |
|
LNName |
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|||
|
Data objects |
||||
|
Status information |
||||
|
Str |
ACD |
Start |
M |
|
|
Op |
ACT |
Operate |
T |
M |
|
Controls |
||||
|
OpCntRs |
INC |
Resettable operation counter |
0 |
|
|
Settings |
||||
|
AVCrv |
CURVE |
Operating curve type (for voltage controlled current curve) |
0 |
|
|
AVChr33 |
CSG |
Multiline curve characteristic definition |
c |
|
|
TmACrv |
CURVE |
Operating curve type (for current) |
0 |
|
|
TmAChr33 |
CSG |
Multiline curve characteristic definition |
c |
|
|
AVSt |
CSD |
Active curve characteristic |
0 |
|
|
TmASt |
CSD |
Active curve characteristic |
0 |
|
|
TmMult |
ASG |
Time dial multiplier |
о |
|
|
MinOpTmms |
ING |
Minimum operate time |
о |
|
|
MaxOpTmms |
ING |
Maximum operate time |
О |
|
|
OpDITmms |
ING |
Operate delay time |
о |
|
|
TypRsCrv |
ENG |
Type of reset curve |
О |
|
|
RsDITmms |
ING |
Reset delay time |
О |
|
|
NOTE AVChr33 refers to the attribute AVCrv.setCharact = 33 etc. TmAChr33 refers to the attribute TmACrv.setCharact = 33 etc. |
||||
-
LN: Volts per Hz Name: PVPH
For a description of this LN, see IEC 61850-5. One instance of PVPH shall be used per protection stage.
|
PVPH class |
||||
|
Data object name |
Common data class |
Explanation |
T |
MIDI C |
|
LNName |
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|||
|
Data objects |
||||
|
Status information |
||||
|
Str |
ACD |
Start |
M |
|
|
Op |
ACT |
Operate |
T |
M |
|
Controls |
||||
|
OpCntRs |
INC |
Resettable operation counter |
О |
|
|
Settings |
||||
|
VHzCrv |
CURVE |
Operating curve type |
О |
|
|
VHzChr33 |
CSG |
Multiline curve characteristic definition |
С |
|
|
VHzSt |
CSD |
Active curve characteristic |
О |
|
|
StrVal |
ASG |
Volts per hertz start value |
О |
|
|
OpDITmms |
ING |
Operate delay time |
О |
|
|
TypRsCrv |
ENG |
Type of reset curve |
о |
|
|
RsDITmms |
ING |
Reset delay time |
О |
|
|
PVPH class |
||||
|
Data object name |
Common data class |
Explanation |
T |
N1/0/ c |
|
TmMult |
ASG |
Time dial multiplier |
О |
|
|
MinOpTmms |
ING |
Minimum operate time |
0 |
|
|
MaxOpTmms |
ING |
Maximum operate time |
о |
|
|
NOTE VHzChr33 refers to the attribute VHzCrv.setCharact = 33 etc. |
||||
-
LN: Zero speed or underspeed Name: PZSU
For a description of this LN, see IEC 61850-5.
|
.. ■■ ■ ■ ' . . ". ■■■ PZSU class |
||||
|
Data object name |
Common data class |
Explanation |
T |
N1/0/ C |
|
LNName |
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|||
|
Data objects |
||||
|
Status information |
||||
|
Str |
ACD |
Start |
M |
|
|
Op |
ACT |
Operate |
T |
M |
|
Controls |
||||
|
OpCntRs |
INC |
Resettable operation counter |
0 |
|
|
Settings |
||||
|
StrVal |
ASG |
Start value (speed) |
0 |
|
|
OpDITmms |
ING |
Operate delay time |
0 |
|
|
RsDITmms |
ING |
Reset delay time |
0 |
|
-
Logical nodes for power quality events LN Group: Q
-
Modelling remarks
-
This group of logical nodes refers to the modelling of power quality events detection and analysis functions. The models are based on the principles used for modelling protection functions. .
There is a one-to-one relationship between the power quality event logical nodes in IEC 61850-5 and the logical node class definitions in this standard.
-
LN: Frequency variation Name: QFVR
For a description of this LN, see IEC 61850-5.
|
QFVR class |
||||
|
Data object name |
Common data class |
Explanation |
T |
N1/0/ C |
|
LNName |
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|||
|
Data objects |
||||
|
Status information |
||||
|
VarStr |
SPS |
Start of the frequency variation event |
M |
|
|
UnHzStr |
SPS |
Start (underfrequency variation event in progress) |
о |
|
|
OvHzStr |
SPS |
Start (overfrequency variation event in progress) |
о |
|
|
VarEnd |
SPS |
Event finished but not reset |
T |
о |
|
QFVR class |
||||
|
Data object name |
Common data class |
Explanation |
T |
MIDI C |
|
Measured and metered values |
||||
|
HzVaTm |
MV |
Frequency variation duration of the last completed event |
0 |
|
|
HzVaMag |
MV |
Frequency variation magnitude of the last completed event |
0 |
|
|
EvtCnt |
HST |
Event counter histogram (HzVaTm, HzVaMag) |
0 |
|
|
Controls |
||||
|
OpCntRs |
INC |
Resettable counter operation |
о |
|
|
Settings |
||||
|
UnHzStrVal |
ASG |
Underfrequency set point |
0 |
|
|
OvHzStrVal |
ASG |
Overfrequency set point |
0 |
|
-
LN: Current transient Name: QITR
For a description of this LN, see IEC 61850-5.
|
QITR class |
||||
|
Data object name |
Common data class |
Explanation |
T |
М/О/ C |
|
LNName |
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|||
|
Data objects |
||||
|
Status information |
||||
|
VarStr |
SPS |
Start of the event |
M |
|
|
VarEnd |
SPS |
Event finished but not reset |
T |
0 |
|
Measured and metered values |
||||
|
ATrsTm |
MV |
Current transient duration |
0 |
|
|
MaxATrs |
MV |
Maximum current transient value |
0 |
|
|
EvtCnt |
HST |
Event counter histogram (ATrsTm, MaxATrs) |
о |
|
|
Controls |
||||
|
OpCntRs |
INC |
Resettable counter operation |
0 |
|
|
Settings |
||||
|
StrVal |
ASG |
Current transient start value |
0 |
|
-
LN: Current unbalance variation Name: QIUB
For a description of this LN, see IEC 61850-5.
|
QIUB class |
||||
|
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
|
LNName |
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|||
|
Data objects |
||||
|
Status information |
||||
|
VarStr |
SPS |
Start of the event |
M |
|
|
VarEnd |
SPS |
Event finished but not reset |
T |
0 |
|
Measured and metered values |
||||
|
AVaTm |
MV |
Current unbalance variation duration |
0 |
|
|
MaxAVa |
MV |
Maximum unbalance deviation value |
0 |
|
|
EvtCnt |
HST |
Event counter histogram |
о |
|
|
QIUB class |
||||
|
Data object name |
Common data class |
Explanation |
T |
N1/0/ C |
|
Controls |
||||
|
OpCntRs |
INC |
Resettable counter operation |
О |
|
|
Settings |
||||
|
UnbDetMth |
ENG |
Unbalance detection method |
О |
|
|
StrVal |
ASG |
Current unbalance start value |
О |
|
Побачили розбіжність з офіційним текстом?