For a description of this LN, see IEC 61850-5 (LN PPFR). This LN shall be used for the underpower factor part of PPFR.

PUPF class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start


M

Op

ACT

Operate

T

M

ВI kA

SPS

Blocked below minimum operating current


0

BlkV

SPS

Blocked below minimum operating voltage


0

Controls

OpCntRs

INC

Resettable operation counter


0

Settings

StrVal

ASG

Start value


0

OpDITmms

ING

Operate delay time


о

RsDITmms

ING

Reset delay time


0

BlkValA

ASG

Block value (minimum operating current)


о

BlkVaIV

ASG

Block value (minimum operating voltage)


о



  1. LN: Voltage controlled time overcurrent Name: PVOC

For a description of this LN, see IEC 61850-5.PVOC class

Data object name

Common data class

Explanation

T

M/O/C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start


M

Op

ACT

Operate

T

M

Controls

OpCntRs

INC

Resettable operation counter


0

Settings

AVCrv

CURVE

Operating curve type (for voltage controlled current curve)


0

AVChr33

CSG

Multiline curve characteristic definition


c

TmACrv

CURVE

Operating curve type (for current)


0

TmAChr33

CSG

Multiline curve characteristic definition


c

AVSt

CSD

Active curve characteristic


0

TmASt

CSD

Active curve characteristic


0

TmMult

ASG

Time dial multiplier


о

MinOpTmms

ING

Minimum operate time


о

MaxOpTmms

ING

Maximum operate time


О

OpDITmms

ING

Operate delay time


о

TypRsCrv

ENG

Type of reset curve


О

RsDITmms

ING

Reset delay time


О

NOTE AVChr33 refers to the attribute AVCrv.setCharact = 33 etc. TmAChr33 refers to the attribute TmACrv.setCharact = 33 etc.



  1. LN: Volts per Hz Name: PVPH

For a description of this LN, see IEC 61850-5. One instance of PVPH shall be used per protection stage.

PVPH class

Data object name

Common data class

Explanation

T

MIDI C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start


M

Op

ACT

Operate

T

M

Controls

OpCntRs

INC

Resettable operation counter


О

Settings

VHzCrv

CURVE

Operating curve type


О

VHzChr33

CSG

Multiline curve characteristic definition


С

VHzSt

CSD

Active curve characteristic


О

StrVal

ASG

Volts per hertz start value


О

OpDITmms

ING

Operate delay time


О

TypRsCrv

ENG

Type of reset curve


о

RsDITmms

ING

Reset delay time


О



PVPH class

Data object name

Common data class

Explanation

T

N1/0/ c

TmMult

ASG

Time dial multiplier


О

MinOpTmms

ING

Minimum operate time


0

MaxOpTmms

ING

Maximum operate time


о

NOTE VHzChr33 refers to the attribute VHzCrv.setCharact = 33 etc.



  1. LN: Zero speed or underspeed Name: PZSU

For a description of this LN, see IEC 61850-5.

.. ■■ ■ ■ ' . . ". ■■■ PZSU class

Data object name

Common data class

Explanation

T

N1/0/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start


M

Op

ACT

Operate

T

M

Controls

OpCntRs

INC

Resettable operation counter


0

Settings

StrVal

ASG

Start value (speed)


0

OpDITmms

ING

Operate delay time


0

RsDITmms

ING

Reset delay time


0



  1. Logical nodes for power quality events LN Group: Q

    1. Modelling remarks

This group of logical nodes refers to the modelling of power quality events detection and analysis functions. The models are based on the principles used for modelling protection functions. .

There is a one-to-one relationship between the power quality event logical nodes in IEC 61850-5 and the logical node class definitions in this standard.

  1. LN: Frequency variation Name: QFVR

For a description of this LN, see IEC 61850-5.

QFVR class

Data object name

Common data class

Explanation

T

N1/0/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

VarStr

SPS

Start of the frequency variation event


M

UnHzStr

SPS

Start (underfrequency variation event in progress)


о

OvHzStr

SPS

Start (overfrequency variation event in progress)


о

VarEnd

SPS

Event finished but not reset

T

о

QFVR class

Data object name

Common data class

Explanation

T

MIDI C

Measured and metered values

HzVaTm

MV

Frequency variation duration of the last completed event


0

HzVaMag

MV

Frequency variation magnitude of the last completed event


0

EvtCnt

HST

Event counter histogram (HzVaTm, HzVaMag)


0

Controls

OpCntRs

INC

Resettable counter operation


о

Settings

UnHzStrVal

ASG

Underfrequency set point


0

OvHzStrVal

ASG

Overfrequency set point


0



  1. LN: Current transient Name: QITR

For a description of this LN, see IEC 61850-5.

QITR class

Data object name

Common data class

Explanation

T

М/О/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

VarStr

SPS

Start of the event


M

VarEnd

SPS

Event finished but not reset

T

0

Measured and metered values

ATrsTm

MV

Current transient duration


0

MaxATrs

MV

Maximum current transient value


0

EvtCnt

HST

Event counter histogram (ATrsTm, MaxATrs)


о

Controls

OpCntRs

INC

Resettable counter operation


0

Settings

StrVal

ASG

Current transient start value


0



  1. LN: Current unbalance variation Name: QIUB

For a description of this LN, see IEC 61850-5.

QIUB class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

VarStr

SPS

Start of the event


M

VarEnd

SPS

Event finished but not reset

T

0

Measured and metered values

AVaTm

MV

Current unbalance variation duration


0

MaxAVa

MV

Maximum unbalance deviation value


0

EvtCnt

HST

Event counter histogram


о



QIUB class

Data object name

Common data class

Explanation

T

N1/0/ C

Controls

OpCntRs

INC

Resettable counter operation


О

Settings

UnbDetMth

ENG

Unbalance detection method


О

StrVal

ASG

Current unbalance start value


О