For a description of this LN, see IEC 61850-5 (LN PPFR). This LN shall be used for the underpower factor part of PPFR.
PUPF class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
Str |
ACD |
Start |
|
M |
Op |
ACT |
Operate |
T |
M |
ВI kA |
SPS |
Blocked below minimum operating current |
|
0 |
BlkV |
SPS |
Blocked below minimum operating voltage |
|
0 |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
0 |
Settings |
||||
StrVal |
ASG |
Start value |
|
0 |
OpDITmms |
ING |
Operate delay time |
|
о |
RsDITmms |
ING |
Reset delay time |
|
0 |
BlkValA |
ASG |
Block value (minimum operating current) |
|
о |
BlkVaIV |
ASG |
Block value (minimum operating voltage) |
|
о |
LN: Voltage controlled time overcurrent Name: PVOC
For a description of this LN, see IEC 61850-5.PVOC class |
||||
Data object name |
Common data class |
Explanation |
T |
M/O/C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
Str |
ACD |
Start |
|
M |
Op |
ACT |
Operate |
T |
M |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
0 |
Settings |
||||
AVCrv |
CURVE |
Operating curve type (for voltage controlled current curve) |
|
0 |
AVChr33 |
CSG |
Multiline curve characteristic definition |
|
c |
TmACrv |
CURVE |
Operating curve type (for current) |
|
0 |
TmAChr33 |
CSG |
Multiline curve characteristic definition |
|
c |
AVSt |
CSD |
Active curve characteristic |
|
0 |
TmASt |
CSD |
Active curve characteristic |
|
0 |
TmMult |
ASG |
Time dial multiplier |
|
о |
MinOpTmms |
ING |
Minimum operate time |
|
о |
MaxOpTmms |
ING |
Maximum operate time |
|
О |
OpDITmms |
ING |
Operate delay time |
|
о |
TypRsCrv |
ENG |
Type of reset curve |
|
О |
RsDITmms |
ING |
Reset delay time |
|
О |
NOTE AVChr33 refers to the attribute AVCrv.setCharact = 33 etc. TmAChr33 refers to the attribute TmACrv.setCharact = 33 etc. |
LN: Volts per Hz Name: PVPH
For a description of this LN, see IEC 61850-5. One instance of PVPH shall be used per protection stage.
PVPH class |
||||
Data object name |
Common data class |
Explanation |
T |
MIDI C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
Str |
ACD |
Start |
|
M |
Op |
ACT |
Operate |
T |
M |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
О |
Settings |
||||
VHzCrv |
CURVE |
Operating curve type |
|
О |
VHzChr33 |
CSG |
Multiline curve characteristic definition |
|
С |
VHzSt |
CSD |
Active curve characteristic |
|
О |
StrVal |
ASG |
Volts per hertz start value |
|
О |
OpDITmms |
ING |
Operate delay time |
|
О |
TypRsCrv |
ENG |
Type of reset curve |
|
о |
RsDITmms |
ING |
Reset delay time |
|
О |
PVPH class |
||||
Data object name |
Common data class |
Explanation |
T |
N1/0/ c |
TmMult |
ASG |
Time dial multiplier |
|
О |
MinOpTmms |
ING |
Minimum operate time |
|
0 |
MaxOpTmms |
ING |
Maximum operate time |
|
о |
NOTE VHzChr33 refers to the attribute VHzCrv.setCharact = 33 etc. |
LN: Zero speed or underspeed Name: PZSU
For a description of this LN, see IEC 61850-5.
.. ■■ ■ ■ ' . . ". ■■■ PZSU class |
||||
Data object name |
Common data class |
Explanation |
T |
N1/0/ C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
Str |
ACD |
Start |
|
M |
Op |
ACT |
Operate |
T |
M |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
0 |
Settings |
||||
StrVal |
ASG |
Start value (speed) |
|
0 |
OpDITmms |
ING |
Operate delay time |
|
0 |
RsDITmms |
ING |
Reset delay time |
|
0 |
Logical nodes for power quality events LN Group: Q
Modelling remarks
This group of logical nodes refers to the modelling of power quality events detection and analysis functions. The models are based on the principles used for modelling protection functions. .
There is a one-to-one relationship between the power quality event logical nodes in IEC 61850-5 and the logical node class definitions in this standard.
LN: Frequency variation Name: QFVR
For a description of this LN, see IEC 61850-5.
QFVR class |
||||
Data object name |
Common data class |
Explanation |
T |
N1/0/ C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
VarStr |
SPS |
Start of the frequency variation event |
|
M |
UnHzStr |
SPS |
Start (underfrequency variation event in progress) |
|
о |
OvHzStr |
SPS |
Start (overfrequency variation event in progress) |
|
о |
VarEnd |
SPS |
Event finished but not reset |
T |
о |
QFVR class |
||||
Data object name |
Common data class |
Explanation |
T |
MIDI C |
Measured and metered values |
||||
HzVaTm |
MV |
Frequency variation duration of the last completed event |
|
0 |
HzVaMag |
MV |
Frequency variation magnitude of the last completed event |
|
0 |
EvtCnt |
HST |
Event counter histogram (HzVaTm, HzVaMag) |
|
0 |
Controls |
||||
OpCntRs |
INC |
Resettable counter operation |
|
о |
Settings |
||||
UnHzStrVal |
ASG |
Underfrequency set point |
|
0 |
OvHzStrVal |
ASG |
Overfrequency set point |
|
0 |
LN: Current transient Name: QITR
For a description of this LN, see IEC 61850-5.
QITR class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
VarStr |
SPS |
Start of the event |
|
M |
VarEnd |
SPS |
Event finished but not reset |
T |
0 |
Measured and metered values |
||||
ATrsTm |
MV |
Current transient duration |
|
0 |
MaxATrs |
MV |
Maximum current transient value |
|
0 |
EvtCnt |
HST |
Event counter histogram (ATrsTm, MaxATrs) |
|
о |
Controls |
||||
OpCntRs |
INC |
Resettable counter operation |
|
0 |
Settings |
||||
StrVal |
ASG |
Current transient start value |
|
0 |
LN: Current unbalance variation Name: QIUB
For a description of this LN, see IEC 61850-5.
QIUB class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
VarStr |
SPS |
Start of the event |
|
M |
VarEnd |
SPS |
Event finished but not reset |
T |
0 |
Measured and metered values |
||||
AVaTm |
MV |
Current unbalance variation duration |
|
0 |
MaxAVa |
MV |
Maximum unbalance deviation value |
|
0 |
EvtCnt |
HST |
Event counter histogram |
|
о |
QIUB class |
||||
Data object name |
Common data class |
Explanation |
T |
N1/0/ C |
Controls |
||||
OpCntRs |
INC |
Resettable counter operation |
|
О |
Settings |
||||
UnbDetMth |
ENG |
Unbalance detection method |
|
О |
StrVal |
ASG |
Current unbalance start value |
|
О |