RsDITmms
Time delay in ms before reset once reset conditions have been met
Data object
name
RisGndRch
Semantics
Resistive reach of the quadrilateral ground distance element shown as the difference between the left and right resistive blinders in the diagram below. See also AngLod in this table.
DirMod = forward
IEC 1106/03
T
RsStat
his data object resets device statistics of this LN
D RstA Restraint current ata object name |
Semantics |
||||||
RstMod |
Identifies the restraint mode for the differential LN. |
|
|||||
|
Restraint mode |
Value |
|
||||
None |
1 |
||||||
2nd harmonic |
2 |
||||||
5th harmonic |
3 |
||||||
2nd and 5th harmonic |
4 |
||||||
Waveform analysis |
5 |
||||||
2nd harmonic and waveform analysis |
6 |
||||||
Other |
7 |
||||||
5,n harmonic and waveform analysis |
8 |
||||||
2nd and 5tn harmonic and waveform analysis |
9 |
||||||
|
|
|
|||||
RV |
TRUE = raise voltage, FALSE = no action |
||||||
RxBIk |
Activation information RxBIkl received from the other side(s), for logging purposes (teleprotection blocking signal received) |
||||||
RxCnt |
Number of received messages |
||||||
RxPrm |
Activation information RxPrm 1 received from the other side(s), for logging purposes (Teleprotection permissive signal received) |
||||||
RxSrc |
Source for activation information RxPrm or RxBIk, must refer to data of type ACT |
||||||
RxSrcTr |
Source for activation information RxTr, must refer to data of type ACT |
||||||
RxTr |
Activation information RxTrl received from the other side(s), for logging purposes (direct trip signal received) |
||||||
RZer |
Zero-sequence line resistance |
||||||
SatCffSIO |
Saturation coefficient S1.0 |
||||||
SatCffS12 |
Saturation coefficient S1.2 |
||||||
SbsNdsCom |
Subscription needs commissioning |
||||||
SbsSim |
Subscription with simulation |
||||||
SbsSt |
Status of the subscription (True = active, False = not active) |
||||||
SrcRef |
Reference to the IEC 61850 source data object. If this source data object has several (analogue) attributes, all shall be registered in the COMTRADE file, and an appropriate number of ChNuml instances shall define the channel mapping to them with the number in the order of the attributes as defined in IEC 61850-7-3. |
||||||
SecTmms |
Pickup security timer on loss of carrier guard signal in ms |
||||||
SelCIs |
Selection “close switch” |
||||||
SelOpn |
Selection “open switch” |
||||||
SeqA |
The absolute measured values of positive, negative and zero sequence current |
||||||
SeqV |
The absolute measured values of positive, negative and zero sequence voltage |
||||||
SetA |
Current setting for a limit in motor start-up (for example counting operate condition or thermal stress). This setting is used in motor start-up protection. |
||||||
SetTms |
Time setting for a limit in motor start-up (for example counting operate condition or thermal stress). This setting is used in motor start-up protection. . |
||||||
SgcbTrk |
Access service tracking for setting group control block |
||||||
ShOpCap |
This is an enumeration representing the operating capabilities of the power shunt. |
||||||
|
Shunt operating capability |
Value |
|
||||
None |
1 |
||||||
Open |
2 |
||||||
Close |
3 |
||||||
Open and close |
4 |
||||||
|
|
|
|||||
Sim |
Simulated GOOSE values or simulated sampled measurand values will be used instead of original values since they are first received. |
Data object name |
Semantics |
|||||
SimSt |
Status showing that really Sim messages are received and accepted |
|||||
Sint |
Salinity. Saline content of water [g/l] |
|||||
SmokAlm |
Smoke alarm |
|||||
SmpRte |
Sampling rate setting |
|||||
SnwDen |
Density of snowfall (usually in g/cm3) |
|||||
Snd |
Sound pressure level |
|||||
Snr |
Signal to noise ratio (in dB), used in case of analogue communication |
|||||
SnwTmp |
Temperature of snowfall (usually in °С) |
|||||
SnwCvr |
Snow cover (usually in mm) |
|||||
SnwFII |
Snowfall (usually in mm) |
|||||
SnwEq |
Water equivalent of snowfall (usually in mm) |
|||||
SOxEms |
SOX emissions |
|||||
SPCSO |
Generic single point controllable status output. It can be multiple in one LN-instance. |
|||||
SpcTrk |
Control service tracking for controllable single point |
|||||
Spd |
Rotational speed usually in 1/s |
|||||
SpdCrit |
Synchronous machine critical speed of the generator [s'1] |
|||||
SpdRtg |
Synchronous machine rated speed [s'1] |
|||||
SpdSrfc |
Surface speed of water flow (in m/s) |
|||||
SpdSpt |
Rotational speed setpoint |
|||||
SPITrTmms |
Single pole delay time in ms before the breaker failure tries to retrip the failed breaker |
|||||
SptChg |
Setpoint change (raise, lower) |
|||||
SptDvAlm |
Deviation alarm |
|||||
SptDir |
Setpoint direction |
|||||
SptDn |
Setpoint going up (lowering) |
|||||
SptEndSt |
Setpoint end status |
|
||||
|
Setpoint end status |
Value |
|
|||
Ended normally |
1 |
|||||
Ended with overshoot |
2 |
|||||
Cancelled: measurement was deviating |
3 |
|||||
Cancelled: loss of communication with dispatch centre |
4 |
|||||
Cancelled: loss of communication with local area network |
5 |
|||||
Cancelled: loss of communication with the local interface |
6 |
|||||
Cancelled: timeout |
7 |
|||||
Cancelled: voluntarily |
8 |
|||||
Cancelled: noisy environments |
9 |
|||||
Cancelled: material failure |
10 |
|||||
Cancelled: new set-point request |
1t |
|||||
Cancelled: improper environment (blockage) |
12 |
|||||
Cancelled: stability time was reached |
13 |
|||||
Cancelled: immobilisation time was reached |
14 |
|||||
Cancelled: equipment was in the wrong mode |
15 |
|||||
Unknown causes |
16 |
|||||
|
|
|
||||
SptMem |
Setpoint in memory |
|||||
SptUp |
Setpoint going up (raising) |
|||||
|
Data object name |
Semantics |
||||
SptVal |
Setpoint value |
||||
SptVol |
Voltage setpoint |
||||
SrcRef |
Reference to the IEC 61850 source data object |
||||
StatLeakX |
Stator leakage reactance [per unit] |
||||
StatRisTmp |
Reference temperature for stator resistance [usually °С] |
||||
StatRis |
Stator resistance [ohm] |
||||
StCIcTun |
Result of tuning: |
|
|||
|
StCIcTun |
Value |
|
||
Not tuned |
1 |
||||
Tuned - |
2 |
||||
Tuned but not compensated |
3 |
||||
Umax |
4 , |
||||
Umax nC (Umax- but not compensated) |
5 |
||||
Umax_not compensated due to U continous limitation |
6 |
||||
|
|
|
|||
StepNg |
Step size when turning from positive to negative direction |
||||
StepPs |
Step size when turning from negative to positive direction |
||||
Stk |
Stroke of the last operation defined as distance between start and end position of the main contact or at the place of travel measurement (usually displayed in mm) |
||||
StoRte |
Storage rate (often called sampling rate) of the disturbance recorder in samples per millisecond (ms) |
||||
Str |
Start (common data classes ACD) indicates the detection of a fault or an unacceptable condition. Str may contain phase and directional information. |
||||
StrCIc |
Start calculation sequence to estimate the parameters of a network. In compensated networks, this can be done either by variating the suppression coil (Petersen coil) or with an current injection in the neutral point of the system. |
||||
StrCrv |
Start level curve |
||||
StrDITmms |
Start delay time |
||||
Strlnh |
Status information restart inhibited. After a limit is reached (for example maximum number of starts or permissible temperature), restart inhibit is activated. |
||||
StrlnhTmm |
Time setting for restart inhibition. Once the Strlnh is activated, the motor should not be allowed to start until this time has elapsed. |
||||
StrPOW |
TRUE = start CPOW (for example by select) - Request by CSWI or RREC |
||||
StrVal |
Level of the supervised value, which starts a dedicated action of the related function |
||||
StrWeekDay |
Day of the start of the local week for statistical calculation |
|
|||
|
StrWeekDay |
Value |
|
||
Monday (default) |
1 |
||||
Tuesday |
2 |
||||
Wednesday |
3 |
||||
Thursday |
4 |
||||
Friday |
5 |
||||
Saturday , |
6 |
||||
Sunday |
7 |
||||
|
|
|
|||
Stuck |
Valve is blocked (cannot move from present position). Device is blocked through external influence (can not operate or move). |
||||
SumSwARs |
Sum of switched amperes, resettable. This data object indicates the sum or integration of all switched currents since the last reset of the counter, for example after maintenance of the contacts, the nozzle and other aging parts. |
||||
SupVArh |
Reactive energy supply (default supply direction: energy flow towards busbar) |
||||
SupWh |
Real energy supply (default supply direction: energy flow towards busbar) |
Data object name |
Semantics |
SvcViol |
Service violation: the data object that the client wanted to access exists in the access view for the association with that client, but the requested service is not allowed. |
SwArcDet |
TRUE = alarm that switch arc has been detected |
SwgReact |
Value of the power swing reactance band, see figure under SwgVal |
SwgRis |
Value of the power swing resistance band, see figure under SwgVal |
SwgTmms |
Power swing detection time in ms |
SwgVal |
Value of the power swing band. |
T
SwOpCap
his is an enumeration representing the physical capabilities of the switch to operate. It includes additional blocking due to some local problems.
Switch operating capability |
Value |
None |
1 |
Open |
2 |
Close |
3 |
Open and close |
4 |
SwTyp |
|
|
|
|
|
|
Switch type |
Value |
|
|
|
Load break switch |
1 |
|
|
|
Disconnector |
2 |
|
|
|
Earthing switch |
3 |
|
|
|
High speed earthing switch |
4 |
|
|
|
|
|
|
SynPrg |
Synchrocheck / Synchronizing in progress. Start/ Stop Synchrocheck/Synchronizing |
|||
TnkTyp |
Type of tank (pressure only, level only, both pressure and level) |
|||
TapBIkL |
Tap position of load tap changer where automatic lower commands blocked |
|||
TapBlkR |
Tap position of load tap changer where automatic raise commands blocked |
|||
TapChg |
This data object represents the control of a process to raise or lower a single step or tap |
|||
TapOpR |
Change tap position raise (shall be used if no control service is available and the GOOSE is used instead) |
|||
TapOpL |
Change tap position lower (shall be used if no control service is available and the GOOSE is used instead) |
|||
TapOpStop |
Change tap position stop (shall be used if no control service is available and the GOOSE is used instead) |
|||
TapPos |
Represents the discrete adjustment of a transformer such as used in a load tap changer to a specified tap position |
|||
TddA |
Current total demand distortion (according to IEEE 519, phase-related) |
|||
TddAmp |
Current total demand distortion (according to IEEE 519, non-phase-related) |
|||
TddEvnA |
Current total demand distortion (according to IEEE 519, even components, phase-related) |
|||
TddEvnAmp |
Current total demand distortion (according to IEEE 519, even components, non-phase-related) |