LN: Generic sensor Name: TGSN
Logical node TGSN shall be used to represent a generic sensor if there is no specific sensor available. It can also be used for modeling the health and name of an external equipment (sensor).
TGSN class |
||||
Data object name |
Common data class |
Explanation |
T |
N1/ O/C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment name plate |
|
0 |
Status information |
||||
EEHealth |
ENS |
External equipment health |
|
0 |
Measured and metered values |
||||
GenSv |
SAV |
Generic sampled value |
|
C |
Settings |
||||
SmpRte |
ING |
Sampling rate setting |
|
О |
Condition C: The data object is mandatory if the data object is transmitted over a communication link and therefore it is visible. |
LN: Humidity Name: THUM
Logical Node THUM shall be used to represent a measurement of humidity in the media that is monitored. The result is given in percent of maximum possible humidity.
THUM class |
||||
Data object name |
Common data class |
Explanation |
T |
М/ o/c |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment name plate |
|
0 |
Status information |
||||
EEHealth |
ENS |
External equipment health |
|
0 |
Measured and metered values |
||||
HumSv |
SAV |
Humidity [%] |
|
C |
Settings |
||||
SmpRte |
ING |
Sampling rate setting |
|
0 |
Condition C: The data object is mandatory if the data object is transmitted over a communication link and therefore it is visible.
LN: Media level Name: TLVL
Logical node TLVL shall be used to represent a measurement of the media level in the container where it is located. The level is expressed as a percentage of full container. For a measurement given as a distance from a base level, the HLVL logical node shall be used.
TLVL class |
||||
Data object name |
Common data class |
Explanation |
T |
Mi o/c |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment name plate |
|
о |
Status information |
||||
EEHealth |
ENS |
External equipment health |
|
0 |
Measured and metered values |
||||
LevPctSv |
SAV |
Level [%] |
|
c |
Settings |
||||
SmpRte |
ING |
Sampling rate setting |
|
о |
Condition C: The data object is mandatory if the data objects are transmitted over a communication link and therefore they are visible. |
LN: Magnetic field Name: TMGF
Logical node TMGF shall be used to represent a measurement of the magnetic field strength at the place where it is located.
TMGF class |
||||
Data object name |
Common data class |
Explanation |
T |
Mi ОІС |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment name plate |
|
0 |
Status information |
||||
EEHealth |
ENS |
External equipment health |
|
0 |
Measured and metered values |
||||
MagFIdSv |
SAV |
Magnetic field strength / flux density (T) |
|
c |
Settings |
||||
SmpRte |
ING |
Sampling rate setting |
|
0 |
Condition C: The data object is mandatory if the data object is transmitted over a communication link and therefore it is visible. |
LN: Movement sensor Name: TMVM
Logical node TMVM shall be used to represent a measurement of movement or speed. It is intended to provide a measurement of the speed, in m/s, with which two objects (one of which may be fixed) are moving in relation to each other.TMVM class |
||||
Data object name |
Common data class |
Explanation |
T |
Ml QIC |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment name plate |
|
О |
Status information |
||||
EEHealth |
ENS |
External equipment health |
|
О |
Measured and metered values |
||||
MvmRteSv |
SAV |
Movement rate [m/s] |
|
С |
Settings |
||||
SmpRte |
ING |
Sampling rate setting |
|
О |
Condition C: The data object is mandatory if the data object is transmitted over a communication link and therefore it is visible. |
LN: Position indicator Name: TPOS
Logical node TPOS shall be used to represent the position of a movable device, actuator or similar. The position is given as a percentage of the full movement of the device being monitored. Compare with TDST that returns the distance in m.
TPOS class |
||||
Data object name |
Common data class |
Explanation |
T |
М/ QIC |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment name plate |
|
О |
Status information |
||||
EEHealth |
ENS |
External equipment health |
|
О |
Measured and metered values |
||||
PosPctSv |
SAV |
Position given as percentage of full movement [%] |
|
С |
Settings |
||||
SmpRte |
ING |
Sampling rate setting |
|
О |
Condition C: The data object is mandatory if the data object is transmitted over a communication link and therefore it is visible. |
LN: Pressure sensor Name: TPRS
Logical node TPRS shall be used to represent the absolute pressure of a medium. The medium might be air, water, oil, steam or any other substance, the pressure of which needs to be supervised.
TPRS class |
||||
Data object name |
Common data class |
Explanation |
T |
Ml QIC |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
TPRS class |
||||
Data object name |
Common data class |
Explanation |
T |
М/ o/c |
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment name plate |
|
о |
Status information |
||||
EEHealth |
ENS |
External equipment health |
|
0 |
Measured and metered values |
||||
PresSv |
SAV |
Pressure of media [Pa] |
|
c |
Settings |
||||
SmpRte |
ING |
Sampling rate setting |
|
о |
Condition C: The data object is mandatory if the data object is transmitted over a communication link and therefore it is visible. |
LN: Rotation transmitter Name: TRTN
Logical node TRTN shall be used to represent the rotational speed of a rotating device. Different measurement principles may be used, the presented result is however the same.
TRTN class |
||||
Data object name |
Common data class |
Explanation |
T |
Ml QIC |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment name plate |
|
О |
Status information |
||||
EEHealth |
ENS |
External equipment health |
|
0 |
Measured and metered values |
||||
RotSpdSv |
SAV |
Rotational speed [1/s] |
|
C |
Settings |
||||
SmpRte |
ING |
Sampling rate setting |
|
0 |
Condition C: The data object is mandatory if the data object is transmitted over a communication link and therefore it is visible. |
LN: Sound pressure sensor Name: TSND
Logical node TSND shall be used to represent the sound pressure level at the location where the sensor is located.
TSND class |
||||
Data object name |
Common data class |
Explanation |
T |
М/ o/c |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment name plate |
|
0 |
Status information |
||||
EEHealth |
ENS ' |
External equipment health |
|
0 |
TSND class |
||||
Data object name |
Common data class |
Explanation |
T |
Ml QIC |
Measured and metered values |
||||
SndSv |
SAV |
Sound pressure level [dB] |
|
C |
Settings |
||||
SmpRte |
ING |
Sampling rate setting |
|
О |
Condition C: The data object is mandatory if the data object is transmitted over a communication link and therefore it is visible. |
LN: Temperature sensor Name: TTMP
Logical node TTMP shall be used to represent a single temperature measurement.
TTMP class |
||||
Data object name |
Common data class |
Explanation |
T |
Ml QIC |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment name plate |
|
О |
Status information |
||||
EEHealth |
ENS |
External equipment health |
|
О |
Measured and metered values |
||||
TmpSv |
SAV (Temperature [°С] |
|
С |
|
Settings |
||||
SmpRte |
ING |
Sampling rate setting |
|
О |
Condition C: The data object is mandatory if the data object is transmitted over a communication link and therefore it is visible. |