1. LN: Tap changer Name: YLTC

For a description of this LN, see IEC 61850-5.

YLTC class

Data object name

Common data class

Explanation

T

М/С/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Descriptions

EEName |DPL

External equipment name plate


0

Status information

EEHealth

ENS

External equipment health


°



YLTC class

Data object name

Common data class

Explanation

T

N1/0/ C

OpCnt

INS

Operation counter


о

EndPosR

SPS

End position raise reached


M

EndPosL

SPS

End position lower reached


M

OoStep

SPS

Out of step alarm: supervision of selector switch synchronism


о

LTCCycAlm

SPS

LTC switching cycle incomplete: tap change operation without diverter switch operation


о

BlkLoVisc

SPS

Blocked by low oil viscosity


о

Controls

TapPos

ISC

Change tap position to dedicated position


с

TapChg

BSC

Change tap position (stop, higher, lower)


с

Condition C: depending on the tap-change method, at least one of the two controls TapChg and TapPos shall be used.



  1. LN: Power shunt Name: YPSH

For a description of this LN, see IEC 61850-5. The LN class power shunt also includes the switch for closing and opening the shunt.

YPSH Class

Data object name

Common data class

Explanation

T

N1/0/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Descriptions

EEName

DPL (External equipment name plate


o

Status information

EEHealth

ENS

External equipment health


О

OpTmh

INS

Operation time


о

ShOpCap

ENS

Operating capability


м

MaxOpCap

INS

Power shunt operating capability when fully charged


О

Controls

Pos

DPC

Switch position


м

BlkOpn

SPC

Block opening


м

BlkCls

SPC

Block closing


м

ChaMotEna

SPC

Charger motor enabled


о



  1. LN: Power transformer Name: YPTR

For a description of this LN, see IEC 61850-5.

YPTR class

Data object name

Common data class

Explanation

T

N1/0/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Descriptions

EEName

DPL (External equipment name plate


o

Status information

EEHealth

ENS

External equipment health


О

OpTmh

INS

Operation time


о

OpNoLod

SPS

Operation at no load


о



YPTR class

Data object name

Common data class

Explanation

T

М/О/ C

OpOvA

SPS

Operation at overcurrent


о

OpOvV

SPS

Operation at overvoltage


о

OpUnV

SPS

Operation at undervoltage


о

Measured and metered values

LodFact

MV

Load factor (apparent power / rated power)


о

MaxPwr

MV

Calculated maximum permissible permanent power (overload) [W]


О

OvITm

MV

Calculated maximum permissible overload time with cooling unit [min]


о

OvITEmg

MV

Calculated maximum permissible overload time without cooling unit (emergency case) [min]


о

Settings

HiVRtg

ASG

Rated voltage (high voltage level)


О

LoVRtg

ASG

Rated voltage (low voltage level)


о

PwrRtg

ASG

Rated power


о

MaxPwrSpt

ASG

Maximum permissible permanent power (overload) [W]


О

OvITmSpt

ASG

Maximum permissible overload time with cooling unit [min]


О

OvITEmgSpt

ASG

Maximum permissible overload time without cooling unit (emergency case) [min]


О



  1. Logical nodes for further power system equipment LN Group: Z

    1. Modelling remarks

The logical nodes of group Z refer all to power system objects which are reusable in other power systems domains but not modelled in other LN groups of this standard.

  1. LN: Auxiliary network Name: ZAXN

For a description of this LN, see IEC 61850-5. Auxiliary networks belong to the power supply system of substations and other power systems installations.

ZAXN class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Descriptions

EEName

DPL

External equipment name plate


О

Status information

EEHealth

ENS

External equipment health


0

OpTmh

INS

Operation time


о

Measured and metered values

Vol

MV

Voltage of the auxiliary network


о

Amp

MV

Current of the auxiliary network


о



5.18.3 LN: Battery Name: ZBAT

For a description of this LN, see IEC 61850-5.

ZBAT class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



ZBAT class

Data object name

Common data class

Explanation

T

М/О/ c

Data objects

Descriptions

EEName

DPL

External equipment name plate


о

Status information

EEHealth

ENS

External equipment health


0

OpTmh

INS

Operation time


0

TestRsI

SPS

Battery test results


о

BatHi

SPS

Battery high (voltage or charge - overcharge)


О

BatLo

SPS

Battery low (voltage or charge)


о

Measured and metered values

Vol

MV

Battery voltage


м

VolChgRte

MV

Rate of battery voltage change


О

Amp

MV

Battery drain current


О

Controls

BatTest

SPC

Start battery test


О

Settings

LoBatVal

ASG

Low battery alarm value


о

HiBatVal

ASG

High battery alarm value


О



5.18.4 LN: Bushing Name: ZBSH

For a description of this LN, see IEC 61850-5.

ZBSH class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Descriptions

EEName |DPL

External equipment name plate

|o.

Status information

EEHealth

ENS

External equipment health


о

OpTmh

INS

Operation time


о

Measured and metered values

React

MV

Relative capacitance of bushing related to the data object RefReact


м

AbsReact

MV

Online capacitance, absolute value


О

LosFact

MV

Loss factor (tan delta)


О

Vol

MV

Voltage of bushing measuring tap


о

DisplA

MV

Displacement current: apparent current at measuring tap


0

LeakA

MV

Leakage current: active current at measuring tap


О

Settings

RefReact

ASG

Reference capacitance for bushing at commissioning


о

RefPF

ASG

Reference power factor for bushing at commissioning


О

RefV

ASG

Reference voltage for bushing at commissioning


О