Data object name |
Semantics |
MaxVTrs |
Maximum voltage transient value |
MaxWa |
Maximum unbalance deviation value |
MaxW |
Maximum active power in a defined evaluation interval (period) |
MaxWPhs |
Maximum magnitude of active power of the 3 phases. Max(Wa, Wb, Wc) |
MaxWrmStr |
Permissible number of warm starts, in most cases cold starts - 1 |
MaxZPhs |
Maximum magnitude of impedance of the 3 phases. Max(Za, Zb, Zc) |
MbrAlm |
Leakage supervision alarm of tank conservator membrane |
MechHealth |
Supervision has detected an abnormal condition of the mechanical chain, derived for example from travel curve or operating times. The values are the same as for the health. |
MemClr |
TRUE = clear memory |
MemFull |
This data object is the percentage at which to indicate memory is full. |
MemOv |
TRUE = memory overflow has occurred |
MemRs |
TRUE = resetting the memory in the recorder |
MemUsed |
Percentage of storage memory in use |
MinAmps |
Minimum current in a defined evaluation interval (period) |
MinAPhs |
Minimum magnitude of current of the 3 phases. Min(la,lb,lc) |
MinFwdAng |
Minimum phase angle in forward direction |
MinHzTmms |
Minimum frequency adjustment pulse time: the value is used to define a minimum pulse length, limiting the calculated variable pulse time. In case of constant pulse length, this value may be used to define the pulse length. |
MinOpTmm |
Minimum operation time in minutes |
MinOpTmms |
The data object minimum operating time in ms for the LN is used for co-ordinating with older electromechanical relays |
MinPFPhs |
Minimum magnitude of power factor of the 3 phases. Min(PFa, PFb, PFc) |
MinPhVPhs |
Minimum magnitude of phase to reference voltage of the 3 phases. Mln(PhVa, PhVb, PhVc) |
MinPPV |
Minimum phase to phase voltage |
MinPPVPhs |
Minimum magnitude of phase to phase voltage of the 3 phases. Min(PPVa, PPVb, PPVc) |
MinRvAng |
Minimum phase angle in reverse direction |
MinVA |
Minimum apparent power in a defined evaluation interval (period). |
MinVAPhs |
Minimum magnitude of apparent power of the 3 phases. Min(VAra, VArb, VArc) |
MinVAr |
Minimum reactive power in a defined evaluation interval (period) |
MinVArPhs |
Minimum magnitude of reactive power of the 3 phases. Min(VAra, VArb, VArc) |
MinVolts |
Minimum voltage in a defined evaluation interval (period) |
MinVSyn |
Minimum voltage for live synchronisation |
MinVTmms |
Minimum voltage adjustment pulse time: the value is used to define a minimum pulse length, limiting the calculated variable pulse time. In case of constant pulse length, this value may be used to define the pulse length. |
MinW |
Minimum real power in a defined evaluation interval (period) |
MinWPhs |
Minimum magnitude of active power of the 3 phases. Min(Wa, Wb, Wc) |
MinZPhs |
Minimum magnitude of impedance of the 3 phases. Min(Za, Zb, Zc) |
Data object name |
Semantics |
MltCmd |
Multiple command generation (TRUE = multiple command). Used to distinguish between single command and multiple command modes of an automatic synchroniser. With this data object it can be selected whether the synchroniser should only give one command within a synchronising attempt, or it should always give a command if all conditions are fulfilled. TRUE = multiple commands allowed; FALSE = single command only. |
Mod |
Controllable data to change the behaviour of the LN by the operator (see Annex A) |
MltLev |
Select mode of authority for local control (True - control from multiple levels is allowed, False (default) - no other control level allowed) |
MotA |
Motor current (usually displayed in A) |
MotAlm |
TRUE = motor operating time exceeded |
MotStrNum |
Alarm level for motor run time in s |
MotAlmTms |
Alarm level for number of motor starts |
MotDrvA |
Motor drive current |
MotDrvBIk |
Motor drive overcurrent blocking t |
MotOp |
TRUE = motor is running |
MotStr |
І-Motor startup threshold. This value identifies a motor starting condition. |
MotStrAlm |
TRUE = motor starts limit exceeded |
MotStrTms |
Time interval for acquisition of motor starts |
MotTm |
Motor operating time of the last charging operation (usually displayed in s) |
MstAlm |
Moisture alarm (FALSE = normal, TRUE = high moisture) |
MstWrn |
Moisture warning (moisture has reached the warning level) |
MsvcbTrk |
Access service tracking for multicast sampled values control block |
Mvm |
Valve is moving |
N2ppm |
Measurement of N2 in ppm |
NamPIt |
This is the name plate of the logical node |
NeutAlm |
TRUE = neutral alarm is present |
NgEna |
Monitoring of negative sequence current is enabled (TRUE) in order to detect an unbalanced fault condition during power swing in the system. |
NOxEms |
NOx emissions |
NomA |
Normalising demand current used in IEEE 519 TDD calculation |
NQS |
Average partial discharge current |
NumCntRs |
Number of times a counter is reset |
NumCyc |
Number of cycles of the basic frequency |
NumPwrUp |
The number of power up operations of the physical device since the last reset |
NumRcd |
Actual number of records |
NumSublntv |
The number of sub-intervals a calculation period interval duration contains |
O2CmbuGas |
Oxygen in combustion gases |
O2ppm |
Measurement of O2 in ppm |
ОЗАіг |
Ozone in air |
Ofs |
Offset, for analogue values, the offset from zero of the analogue value |
OilFil |
TRUE = oil filtration is operational/running |
OilMotA |
Oil circulation motor drive current |
OilTmpIn |
Oil temperature cooler in |
OilTmpOut |
Oil temperature cooler out |
OilTmpSet |
Set point for oil temperature |
OoStep |
Out of step alarm: supervision of selector switch synchronism |
Data object name |
Semantics |
|||
Op |
Operate (common data classes ACT) indicates the trip decision of a protection function (LN). The trip itself is issued by PTRC. |
|||
OpAlmTmh |
Alarm limit for operation time in hours |
|||
OpAlmNum |
Alarm limit for number of operations |
|||
OpCIs |
Operation close switch. OpCIs shall be used if no control service is available between CSWI and XCBR and the GOOSE is used instead. |
|||
OpCnt |
This data object represents a count of operations that is not resettable. In general, this type of counter is included in the following LNs: XCBR, XSWI, and YLTC. The counter shall not be reset from remote but maybe from local. |
|||
OpCntAlm |
TRUE = number of operations has exceeded the alarm limit |
|||
OpCntRs |
This data object represents a resettable LN operations counter. The use of the CDC INC permits setting the counter to something other than "0". |
|||
qpCntWrn |
TRUE = number of operations has exceeded the warning limit |
|||
OpDITmms |
Time delay in milliseconds before operating once operate conditions have been met |
|||
OpCtl |
Command to operate a device (motor, pump, fan or similar) that will continue running until the command is negated |
|||
OpEx |
Trip of a breaker failure function to a circuit breaker other than the faulty one to switch off the “rid fault (“external trip”) |
|||
Opln |
Retrip of a breaker failure function after a trip of a protection function was not successful (“internal trip'') |
|||
OpModRect |
This data is used to define what mode a controllable rectifier shall operate in. |
|||
|
Operating mode of rectifier |
Value |
|
|
Current control mode |
1 |
|||
Voltage control mode |
2 |
|||
Active power control mode |
3 |
|||
|
|
|
||
OpModSyn |
This data object may be used to select the operating mode: |
|||
|
Operating mode for synchronizer |
Value |
|
|
Automatic synchronising mode |
1 |
|||
Automatic paralleling mode |
2 |
|||
Manual mode |
3 |
|||
Test mode |
4 |
|||
Description of the different values:
|
||||
OpnLim |
Open position limitation, temporary limitation of maximum opening of valve, actuator or other device |
|||
OpNoLod |
TRUE = provides indication that power system devices is operating with no load |
|||
OpnPos |
Open end position reached (valve cannot move further) |
|||
OpOpn |
Operation open switch. OpOpn shall be used if no control service is available between CSWI and XCBR and the GOOSE is used instead |
|||
OpOvA |
TRUE = device is operating under an overcurrent condition |
|||
OpOvExt |
TRUE = device operating in an over excited condition |
|||
OpOvV |
TRUE = device is operating under an overvoltage condition |
|||
OpSar |
TRUE = surge arrestor operation detected |
|||
OpSpdCIs |
Operation speed of main contact during close operation (usually displayed in m/s) |
|||
OpSpdOpn |
Operation speed of main contact during open operation (usually displayed in m/s) |
|||
OpTmAlm |
TRUE = Switch operating time exceeded |
|||
OpTmCIs |
Operation timing of main contact during close operation (usually displayed in ms). |
Data object name |
Semantics |
|||||||
OpTmh |
This data object indicates the operation time in hours of a physical device since start of the operation. Details are LN specific. |
|||||||
OpTmOpn |
Operation timing of main contact during open operation (usually displayed in ms) |
|||||||
OpTmWrn |
TRUE = operation time of a physical device exceeds the warning limit |
|||||||
OpUnExt |
TRUE = device operated in an under-excited condition |
|||||||
OpUnV |
TRUE = device operating in an under voltage condition |
|||||||
OpWrnTmh |
Warning limit for operation time in hours |
|||||||
OpWmNum |
Warning limit for number of operations |
|||||||
Out |
Analogue output of the function |
|||||||
OutOv |
This data object indicates that a buffer overflow occurred for the output buffer and important annunciation's may be lost (TRUE) for the communication. A general interrogation is recommended or an integrity scan is started automatically. |
|||||||
OvHzStr |
Start (overfrequency variation event in progress) |
|||||||
OvHzStrVal |
Overfrequency set point |
|||||||
OvITm |
Calculated maximum permissible overload time with cooling unit [min] |
|||||||
OvITEmg |
Calculated maximum permissible overload time without cooling unit (emergency case) [min] |
|||||||
OvITmSpt |
Maximum permissible overload time with cooling unit [min] |
|||||||
OvITEmgSpt |
Maximum permissible overload time without cooling unit (emergency case) [min] |
|||||||
OvStkCls |
The movement of the main contact during a close operation, which is over the end position (usually displayed in mm) |
|||||||
OvStkOpn |
The movement of the main contact during an open operation, which is over the end position (usually displayed in mm) |
|||||||
PAct |
Proportional action |
|||||||
PaDschAlm |
TRUE = Partial discharge has reached pre-set alarm level |
|||||||
ParOp |
Transformers or suppression coils are operating in parallel. |
|||||||
ParColMod |
Mode of parallel operation of petersen coil (controllable) |
|||||||
|
Mode of parallel operation |
Value |
|
|||||
Master/slave |
1 |
|||||||
Master/slave with fixed slave position |
2 |
|||||||
Master/slave with variable slave position |
3 |
|||||||
Parallel operation without communication |
4 |
|||||||
|
|
|
||||||
ParMod |
Set current regulator mode during control (master, slave, independent) |
|||||||
ParTraMod |
Parallel transformer mode. Defined values are: |
|
||||||
|
Mode of parallel operation |
Value |
|
|||||
No mode predefined |
1 |
|||||||
Master |
2 |
|||||||
Follower . |
3 |
|||||||
Power factor |
4 |
|||||||
Negative reactance |
5 |
|||||||
Circulating current |
6 |
|||||||
Circulating reactive current (var balancing) |
7 |
|||||||
Circulating reactive current by equalizing calculated transformer power factor |
8 |
|||||||
|
|
|
||||||
PartSens |
Sensitivity to particulates |
PctRch |
Distance characteristic reach in percent of the line length; see curve in PctOfs |
PerTrgTms |
Periodic trigger time in s |
PF |
Phase to ground power factor for phases 1, 2, and 3, including angle |
PFRtg |
Rated power factor |
Distance characteristic offset in percent of the line length.
Semantics
Data object
name
PctOfs
Specification of the power factor sign according a certain standard. Two possible values:
PFSign |
Value |
Active power (usually named IEC) |
1 |
Lead/Lag (usually named IEEE) |
2 |