1. LN: Phase angle measuring Name: PPAM

For a description of this LN, see IEC 61850-5. This function shall be used to model “out-of­step” protection of generators.



PPAM class

Data object name

Common data class

Explanation

T

М/О/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start


M

Op

ACT

Operate

T

M

Controls

OpCntRs

INC

Resettable operation counter


0

Settings

StrVal

ASG

Start value


о



  1. LN: Rotor protection Name: PRTR

For a description of this LN, see IEC 61850-5. Logical Node PRTR shall be used to represent a field short-circuit protection using the 6th harmonic (300 Hz). The protection is normally included in the excitation system.

PRTR class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start


M

Op

ACT

Operate (trips both field CB and generator CB)

T

M

Controls

OpCntRs

INC

Resettable operation counter


0

Settings

StrVal

ASG

Start value


0



  1. LN: Protection scheme Name: PSCH

This LN shall be used to model the logic scheme for line protection function co-ordination. The protection scheme allows the exchange of the “operate” outputs of different protection functions and conditions for line protection schemes. It includes data objects for teleprotection if applicable. In this case, all appropriate data objects shall be subscribed.

PSCH class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status Information

TxPrm

ACT

Permissive information to be transmitted to the other side (teleprotection permissive signal)

T

0

TxBIk

ACT

Blocking information to be transmitted to the other side (teleprotection blocking signal)

T

о

TxTr

ACT

Direct trip information to be transmitted to the other side

T

0

RxPrml

ACT

Activation information RxPrml received from the other side(s), for logging purposes (teleprotection permissive signal received)

T

0

PSCH class

Data object name

Common data class

Explanation

T

М/О/ C

RxBIkl

ACT

Activation information RxBIkl received from the other side(s), for logging purposes (teleprotection blocking signal received)

T

0

RxTrl

ACT

Activation information RxTrl received from the other side(s), for logging purposes (direct trip signal received)


0

Op

ACT

Operate

T

M

EchoWei

SPS

TxPrm is being sent as echo signal or in case of weak end infeed

T

0

EchoWeiOp

SPS

Additional indication that Op is the operate from the weak end infeed or echo function (typically with undervoltage control)

T

о

Controls

OpCntRs

INC

Resettable operation counter


о

Settings

RxSrd

ORG

Source for activation information RxPrm or RxBIk, must refer to data of type ACT


О

RxSrcTH

ORG

Source for activation information RxTr, must refer to data of type ACT


о

OpDITmms

ING

Operate delay time


О

CrdTmms

ING

Co-ordination timer for blocking scheme


О

DurTmms

ING

Minimum duration of TxPerm in case of operate of PSCH


0

UnBlkMod

ENG

Unblock function mode for scheme type


0

UnBlkTmms

ING

Unblocking time


О

WeiMod

ENG

Mode of weak end infeed function


о

WeiTmms

ING

Co-ordination time for weak end infeed function


0



  1. LN: Sensitive directional earthfault Name: PSDE

For a general description of directed earth fault protection, see IEC 61850-5. This LN is used for directional earthfault handling in compensated and isolated networks. The use of “operate” is optional and depends both on protection philosophy and on instrument transformer capabi­lities. For compensated networks, this function is often called wattmetric directional earthfault. The very high accuracy needed for fault current measurement in compensated networks may require phase angle compensation. This shall be realised by the related LN TCTR.

. PSDE class :

Data object name

Common data class

Explanation

T

М/О/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start


M

Op

ACT

Operate

T

о

Controls

OpCntRs

INC

Resettable operation counter


о

FltlndRs

SPC

Earthfault indication, resettable


О

Settings

Ang

ASG

Angle between voltage (Uo) and current (/0)


О

GndStr

ASG

Ground start value (3 Uo)


о

GndOp

ASG

Ground operate value (3 l0)


О

StrDITmms

ING

Start delay time


О

OpDITmms

ING

Operate delay time


О

DirMod

ENG

Directional mode


О



  1. LN: Transient earth fault Name: PTEF

For a description of this LN, see IEC 61850-5. This LN shall be used to detect (“start”) transient earth fault in compensated networks.

PTEF class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start (transient earth fault)


c

Op

ACT

Operate (transient earth fault)

T

c

Controls

OpCntRs

INC

Resettable operation counter


о

FltlndRs

SPC

Eartbfault indication, resettable


о

Settings

GndStr

ASG

Ground start value


О

DirMod

ENG

Directional mode


о

Condition C: at least one of the two status information (Str, Op) shall be used.



  1. LN: Thyristor protection Name: PTHF

Logical node PTHF shall be used to represent a thyristor (thyristor valve) protection. In a power plant, this protection will typically be included in the excitation system.

PTHF class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start


M

Op

ACT

Operate (trips both field CB and generator CB)

T

M

Controls

OpCntRs

INC

Resettable operation counter


0

Settings

StrVal

ASG

Start value


0



  1. LN: Time overcurrent Name: PTOC

For a description of this LN, see IEC 61850-5 (LN PTOC). This LN shall also be used to model the directional time overcurrent (PDOC/IEEE device function number 67, from IEEE C37.2:1996). The Definite Time overcurrent (also PTOC/IEEE device function number 51, from IEEE C37.2:1996) shall be modelled by use of PTOC and selecting the related curve.

PTOC class

Data object name

Common data class

Explanation

T

N1/0/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start


M



PTOC class

Data object name

Common data class

Explanation

T

М/О/ c

Op

ACT

Operate

T

M

Controls

OpCntRs

INC

Resettable operation counter


о

Settings

TmACrv,

CURVE

Operating curve type


0

TmAChr33

CSG

Multiline curve characteristic definition


c

TmASt

CSD

Active curve characteristic


о

StrVal

ASG

Start value


о

TmMult

ASG

Time dial multiplier


О

MinOpTmms

ING

Minimum operate time


о

MaxOpTmms

ING

Maximum operate time


о

OpDITmms

ING

Operate delay time


о

TypRsCrv

ENG

Type of reset curve


О

RsDITmms

ING

Reset delay time


О

DirMod

ENG

Directional mode


О

NOTE TmAChr33 refers to the attribute TmACrv.setCharact = 33 etc.



  1. LN: Overfrequency Name: PTOF

For a description of this LN, see IEC 61850-5 (LN PFRQ). This LN shall be used to model the overfrequency part of PFRQ. One instance shall be used per stage.

PTOF class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start


M

Op

ACT

Operate

T

M

BlkV

SPS

Blocked because of voltage


о

Controls

OpCntRs

INC

Resettable operation counter


0

Settings

StrVal

ASG

Start value (frequency)


0

BlkVal

ASG

Voltage block value


0

OpDITmms

ING

Operate delay time


о

RsDITmms

ING

Reset delay time


О