1. LN: Voltage transient Name: QVTR

For a description of this LN, see IEC 61850-5.

QVTR class

Data object name

Common data class

Explanation

T

MIDI C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status Information

VarStr

SPS

Start of the event


M

VarEnd

SPS

Event finished but not reset

T

о

Measured and metered values

VTrsTm

MV

Voltage transient duration


о

MaxVTrs

MV

Maximum voltage transient value


о

EvtCnt

HST

Event counter histogram


о

Controls

OpCntRs

INC

Resettable counter operation


о

Settings

StrVal

ASG

Voltage transient start value


О



  1. LN: Voltage unbalance variation Name: QVUB

For a description of this LN, see IEC 61850-5.

QVUB class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

VarStr

SPS

Start of the event


M

VarEnd

SPS

Event finished but not reset

T

о

Measured and metered values

WaTm

MV

Voltage unbalance variation duration


о

MaxWa

MV

Maximum unbalance deviation value


о

EvtCnt

HST

Event counter histogram


О

Controls

OpCntRs

INC

Resettable counter operation


о

Settings

UnbDetMth

ENG

Unbalance detection method


м

StrVal

ASG

Voltage unbalance start value .


м

  1. LN: Voltage variation Name: QVVR

For a description of this LN, see IEC 61850-5. This LN refers to one phase only.

QVVR class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

VarStr

SPS

Start (voltage variation event in progress)


M

DipStr

SPS

Start (voltage dip event in progress)


о

SwIStr

SPS

Start (voltage swell event in progress)


о

IntrStr

SPS

Start (voltage interruption event in progress)


о

VarEnd

SPS

Event finished but not reset

T

О

Measured and metered values

Wa

MV

Voltage variation magnitude of the last completed event


о

EvtCnt

HST

Event counter histogram


о

WaTm

MV

Voltage variation duration of the last completed event


о

Controls

OpCntRs

INC

Resettable counter operation


о

Settings






DipStrVal

ASG

Voltage dip set point


О

SwIStrVal .

ASG

Voltage swell set point


о

IntrStrVal

ASG

Voltage Interruption set point


о

IntrDetMth

ENG

Interruption detection method


о



  1. Logical nodes for protection related functions LN Group: R

    1. Modelling remarks

Table 8 gives the relation between IEC 61850-5 and this standard for protection related LNs.

Table 8 - Relation between IEC 61850-5 and IEC 61850-7-4 for protection related LN

Functionality

IEEE reference

Defined in IEC 61850-5 by LN

Modelled in IEC 61850-7-4 by LN

Comments

Carrier or pilot line wire protection

85

RCPW

PSCH

PSCH is used for line protection schemes instead of RCPW

Directional element



RDIR

Directional element for modelling directed protection with Pxyz nodes

Disturbance recording (acquisition)


RDRE

RDRE

RADR

RBDR

Basic functionality Analogue channel Binary channel



  1. LN: Disturbance recorder channel analogue Name: RADR

In addition to the channel number, all attributes needed for the COMTRADE file (IEEE C37.111:1999) are provided either by data objects from the TVTR or TCTR or by attributes of the measured value (samples subscribed from TVTR or TCTR) itself or by data objects from pseudo channels (calculated values, derived values of power quality devices). The "circuit component” and “phase identification” is provided by the instance identification of the LN RADR. Channels "1” to “n" are created by "1” to “n” instances.

RADR class

Data object name

Common data class

Explanation

T

М/О/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

ChTrg

SPS

Channel triggered


M

Measured and metered values

Access via COMTRADE only


Analogue input channel


M

Controls

OpCntRs

INC

Resettable operation counter


о

Settings

ChNuml

ING

Channel number


c

TrgMod

ENG

Trigger mode (internal trigger, external or both)


0

LevMod

ENG

Level trigger mode


о

HiTrgLev

ASG

High (positive) trigger level '


о

LoTrgLev

ASG

Low (negative) trigger level


о

PreTmms

ING

Pre-trigger time


о

PstTmms

ING

Post-trigger time


о

SrcRef

ORG

Reference to the IEC 61850 source data object


о

Condition C: multiple instances of ChNum are only allowed in case of compound data types (e.g. WYE). The order of these shall be the same as in the referenced data object.



  1. LN: Disturbance recorder channel binary Name: RBDR

In addition to the channel number, all attributes needed for the COMTRADE file (IEEE C37.111:1999) are provided by attributes of the binary input (subscribed from another LN). The “circuit component” and “phase identification” is provided by the instance identification of the LN RBDR. Channels “1” to "n” are created by “1” to “n" instances.

RBDR class

Data object name

Common data class

Explanation

T

М/О/ C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

ChTrg

SPS

Channel triggered


M

Access via

COMTRADE only


Binary input channel


M

Controls

OpCntRs

INC

Resettable operation counter


0

Settings

ChNuml

ING

Channel number


о

TrgMod

ENG

Trigger mode (internal trigger, external or both)


о



RBDR class

Data object name

Common data class

Explanation

T

MIDI C

LevMod

ENG

Level trigger mode


0

PreTmms

ING

Pre-trigger time


о

PstTmms

ING

Post-trigger time


о

SrcRef

ORG

Reference to the IEC 61850 source data object


о

Condition C: multiple instances of ChNum are only allowed in case of compound data types (e.g. double indication). The order of these shall be the same as in the referenced data object.



  1. LN: Breaker failure Name: RBRF

For a description of this LN, see IEC 61850-5.

RBRF class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start, timer running


0

OpEx

ACT

Breaker failure trip ("external trip")

T

c

Opln

ACT

Operate, retrip ("internal trip”)

T

c

Controls

OpCntRs

INC

Resettable operation counter


0

Settings

FailMod

ENG

Breaker failure detection mode


о

FailTmms

ING

Breaker failure time delay for bus bar trip


о

SPITrTmms

ING

Single pole retrip time delay


о

TPTrTmms

ING

Three pole retrip time delay


о

DetValA

ASG

Current detector value


о

ReTrMod

ENG

Retrip mode


о

Condition C: At least one of either data objects shall be used depending on the applied tripping schema.



  1. LN: Directional element Name: RDIR

This LN shall be used to represent all directional data objects in a dedicated LN used for directional relay settings. The protection function itself is modelled by the dedicated protection LN. LN RDIR may be used with functions 21, 32 or 67 according to IEEE device function number designation.

RDIR class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Dir

ACD

Direction


M

Settings

ChrAng

ASG

Characteristic angle


о

MinFwdAng

ASG

Minimum phase angle in forward direction


о