1. LN: Overvoltage Name: PTOV

For a description of this LN, see IEC 61850-5. For some applications such aS transformer star­point or delta supervision, “operate” may not be used.

PTOV class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start


M

Op

ACT

Operate

T

0

Controls

OpCntRs

INC

Resettable operation counter


0

Settings

TmVCrv

CURVE

Operating curve type


0

TmVChr33

CSG

Multiline curve characteristic definition


c

TmVSt

CSD

Active curve characteristic


о

StrVal

ASG

Start value


0

TmMult

ASG

Time dial multiplier


о

MinOpTmms

ING

Minimum operate time


О

MaxOpTmms

ING

Maximum operate time


О

OpDITmms

ING

Operate delay time


О

RsDITmms

ING

Reset delay time


о

NOTE TmVChr33 refers to the attribute TmVCrv.setCharact = 33 etc.



  1. LN: Protection trip conditioning Name: PTRC

This LN shall be used to connect the “operate” outputs of one or more protection functions to a common “trip” to be transmitted to XCBR. In addition, or alternatively, any combination of “operate” outputs of the protection functions may be combined to a new “operate” of PTRC.

PTRC class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Tr

ACT

Trip


c

Op

ACT

Operate (combination of subscribed Op from protection functions)


c

Str

ACD

Start (combination of subscribed Str from protection functions)


о

Controls

OpCntRs

INC

Resettable operation counter


0

Settings

TrMod

ENG

Trip mode


о

TrPlsTmms

ING

Trip pulse time


О

  1. Condition C: At least one of the two status informations (Tr, Op) shall be used.LN: Thermal overload Name: PTTR

For a description of this LN, see IEC 61850-5 (LNs PROL, PSOL). PTTR shall be used for all thermal overload functions. Depending on the algorithm, the LN describes either a temperature or a current (thermal model). Temperature data objects are also provided by other LNs. Examples are the hot spot temperature in LN YPTR or the isolation gas temperature in LN

SIMG.

PTTR class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start


0

op

ACT

Operate

T

M

AlmThm

SPS

Thermal alarm


о

BlkThm

SPS

Block closing command for circuit breaker because of thermal condition


о

Measured and metered values

Amp

MV

Current for thermal load model


о

Tmp

MV

Temperature for thermal load


о

TmpRI

MV

Relation between temperature and maximum temperature


О

LodRsvAlm

MV

Load reserve to alarm


О

LodRsvTr

MV

Load reserve to trip


О

Controls

OpCntRs

INC

Resettable operation counter


о

Settings

TmTmpCrv

CURVE

Characteristic curve for temperature measurement


О

TmTmpChr33

CSG

Multiline curve characteristic definition


с

TmACrv

CURVE

Characteristic curve for current measurement /Thermal model


о

TmAChr33

CSG

Multiline curve characteristic definition


с

TmTmpSt

CSD

Active curve characteristic


о

TmASt

CSD

Active curve characteristic


о

TmpMax

ASG

Maximum allowed temperature


о

StrVal

ASG

Start value


о

OpDITmms

ING

Operate delay time


о

MinOpTmms

ING

Minimum operate time


О

MaxOpTmms

ING

Maximum operate time


О

RsDITmms

ING

Reset delay time


О

ConsTmsl

ING

Time constant of the thermal model


о

AlmVaJ

ASG

Alarm value


о

DropoutVal

ASG

Dropout value for blocking closing command


О

NOTE TmAChr33 refers to the attribute TmACrv.setCharact = 33 etc. TmTmpChr33 refers to the attribute TmTmpCrv.setCharact = 33 etc.



  1. LN: Undercurrent Name: PTUC

For a description of this LN, see IEC 61850-5 (LN PUCP). This LN shall be used for the undercurrent part of PUCP. The underpower part of LN PUCP is covered by PDUP. Different instances shall be used for phase and ground.



PTUC class

Data object name

Common data class

Explanation

T

MIOI C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start


M

Op

ACT

Operate

T

M

Controls

OpCntRs

INC

Resettable operation counter


о

Settings

TmACrv

CURVE

Operating curve type


о

TmAChr33

CSG

Multiline curve characteristic definition


с

TmASt

CSD

Active curve characteristic


о

StrVal

ASG

Start value


о

OpDITmms

ING

Operate delay time


о

TmMult

ASG

Time dial multiplier


о

MinOpTmms

ING

Minimum operate time


о

MaxOpTmms

ING

Maximum operate time


о

TypRsCrv

ENG

Type of reset curve


о

RsDITmms

ING

Reset delay time


о

DirMod

ENG

Directional mode


о

NOTE TmAChr33 refers to the attribute TmACrv.setCharact = 33 etc.



  1. LN: Underfrequency Name: PTUF

For a description of this LN, see IEC 61850-5 (LN PFRQ). This LN shall be used to model the underfrequency part of PFRQ. One instance shall be used per stage.

PTUF class

Data object name

Common data class

Explanation

T

Nl/O/C

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information '

Str

ACD

Start


M

Op

ACT

Operate

T

M

BlkV

SPS

Blocked because of voltage


о

Controls

OpCntRs

INC

Resettable operation counter


о

Settings

StrVal

ASG

Start value (frequency)


О

BlkVal

ASG

Voltage block value


О

OpDITmms

ING

Operate delay time


о

RsDITmms

ING

Reset delay time


о



  1. LN: Undervoltage Name: PTUV

For a description of this LN, see IEC 61850-5. With an appropriate low operating curve, PTUV works also as zero voltage relay.PTUV class

Data object name

Common data class

Explanation

T

М/О/ c

LNName


The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22.



Data objects

Status information

Str

ACD

Start


M

Op

ACT

Operate

T

M

Controls

OpCntRs

INC

Resettable operation counter


о

Settings

TmVCrv

CURVE

Operating curve type


0

TmVChr33

CSG

Multiline curve characteristic definition


c

TmVSt

CSD

Active curve characteristic


о

StrVal

ASG

Start value


0

TmMult

ASG

Time dial multiplier


0

MinOpTmms

ING

Minimum operate time


о

MaxOpTmms

ING

Maximum operate time


о

OpDITmms

ING

Operate delay time


о

RsDITmms

ING

Reset delay time


о

NOTE TmVChr33 refers to the attribute TmVCrv.setCharact = 33 etc.



  1. LN: Underpower factor Name: PUPF