LN: Overvoltage Name: PTOV
For a description of this LN, see IEC 61850-5. For some applications such aS transformer starpoint or delta supervision, “operate” may not be used.
PTOV class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
Str |
ACD |
Start |
|
M |
Op |
ACT |
Operate |
T |
0 |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
0 |
Settings |
||||
TmVCrv |
CURVE |
Operating curve type |
|
0 |
TmVChr33 |
CSG |
Multiline curve characteristic definition |
|
c |
TmVSt |
CSD |
Active curve characteristic |
|
о |
StrVal |
ASG |
Start value |
|
0 |
TmMult |
ASG |
Time dial multiplier |
|
о |
MinOpTmms |
ING |
Minimum operate time |
|
О |
MaxOpTmms |
ING |
Maximum operate time |
|
О |
OpDITmms |
ING |
Operate delay time |
|
О |
RsDITmms |
ING |
Reset delay time |
|
о |
NOTE TmVChr33 refers to the attribute TmVCrv.setCharact = 33 etc. |
LN: Protection trip conditioning Name: PTRC
This LN shall be used to connect the “operate” outputs of one or more protection functions to a common “trip” to be transmitted to XCBR. In addition, or alternatively, any combination of “operate” outputs of the protection functions may be combined to a new “operate” of PTRC.
PTRC class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
Tr |
ACT |
Trip |
|
c |
Op |
ACT |
Operate (combination of subscribed Op from protection functions) |
|
c |
Str |
ACD |
Start (combination of subscribed Str from protection functions) |
|
о |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
0 |
Settings |
||||
TrMod |
ENG |
Trip mode |
|
о |
TrPlsTmms |
ING |
Trip pulse time |
|
О |
Condition C: At least one of the two status informations (Tr, Op) shall be used.LN: Thermal overload Name: PTTR
For a description of this LN, see IEC 61850-5 (LNs PROL, PSOL). PTTR shall be used for all thermal overload functions. Depending on the algorithm, the LN describes either a temperature or a current (thermal model). Temperature data objects are also provided by other LNs. Examples are the hot spot temperature in LN YPTR or the isolation gas temperature in LN
SIMG.
PTTR class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
Str |
ACD |
Start |
|
0 |
op |
ACT |
Operate |
T |
M |
AlmThm |
SPS |
Thermal alarm |
|
о |
BlkThm |
SPS |
Block closing command for circuit breaker because of thermal condition |
|
о |
Measured and metered values |
||||
Amp |
MV |
Current for thermal load model |
|
о |
Tmp |
MV |
Temperature for thermal load |
|
о |
TmpRI |
MV |
Relation between temperature and maximum temperature |
|
О |
LodRsvAlm |
MV |
Load reserve to alarm |
|
О |
LodRsvTr |
MV |
Load reserve to trip |
|
О |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
о |
Settings |
||||
TmTmpCrv |
CURVE |
Characteristic curve for temperature measurement |
|
О |
TmTmpChr33 |
CSG |
Multiline curve characteristic definition |
|
с |
TmACrv |
CURVE |
Characteristic curve for current measurement /Thermal model |
|
о |
TmAChr33 |
CSG |
Multiline curve characteristic definition |
|
с |
TmTmpSt |
CSD |
Active curve characteristic |
|
о |
TmASt |
CSD |
Active curve characteristic |
|
о |
TmpMax |
ASG |
Maximum allowed temperature |
|
о |
StrVal |
ASG |
Start value |
|
о |
OpDITmms |
ING |
Operate delay time |
|
о |
MinOpTmms |
ING |
Minimum operate time |
|
О |
MaxOpTmms |
ING |
Maximum operate time |
|
О |
RsDITmms |
ING |
Reset delay time |
|
О |
ConsTmsl |
ING |
Time constant of the thermal model |
|
о |
AlmVaJ |
ASG |
Alarm value |
|
о |
DropoutVal |
ASG |
Dropout value for blocking closing command |
|
О |
NOTE TmAChr33 refers to the attribute TmACrv.setCharact = 33 etc. TmTmpChr33 refers to the attribute TmTmpCrv.setCharact = 33 etc. |
LN: Undercurrent Name: PTUC
For a description of this LN, see IEC 61850-5 (LN PUCP). This LN shall be used for the undercurrent part of PUCP. The underpower part of LN PUCP is covered by PDUP. Different instances shall be used for phase and ground.
PTUC class |
||||
Data object name |
Common data class |
Explanation |
T |
MIOI C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
Str |
ACD |
Start |
|
M |
Op |
ACT |
Operate |
T |
M |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
о |
Settings |
||||
TmACrv |
CURVE |
Operating curve type |
|
о |
TmAChr33 |
CSG |
Multiline curve characteristic definition |
|
с |
TmASt |
CSD |
Active curve characteristic |
|
о |
StrVal |
ASG |
Start value |
|
о |
OpDITmms |
ING |
Operate delay time |
|
о |
TmMult |
ASG |
Time dial multiplier |
|
о |
MinOpTmms |
ING |
Minimum operate time |
|
о |
MaxOpTmms |
ING |
Maximum operate time |
|
о |
TypRsCrv |
ENG |
Type of reset curve |
|
о |
RsDITmms |
ING |
Reset delay time |
|
о |
DirMod |
ENG |
Directional mode |
|
о |
NOTE TmAChr33 refers to the attribute TmACrv.setCharact = 33 etc. |
LN: Underfrequency Name: PTUF
For a description of this LN, see IEC 61850-5 (LN PFRQ). This LN shall be used to model the underfrequency part of PFRQ. One instance shall be used per stage.
PTUF class |
||||
Data object name |
Common data class |
Explanation |
T |
Nl/O/C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information ' |
||||
Str |
ACD |
Start |
|
M |
Op |
ACT |
Operate |
T |
M |
BlkV |
SPS |
Blocked because of voltage |
|
о |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
о |
Settings |
||||
StrVal |
ASG |
Start value (frequency) |
|
О |
BlkVal |
ASG |
Voltage block value |
|
О |
OpDITmms |
ING |
Operate delay time |
|
о |
RsDITmms |
ING |
Reset delay time |
|
о |
LN: Undervoltage Name: PTUV
For a description of this LN, see IEC 61850-5. With an appropriate low operating curve, PTUV works also as zero voltage relay.PTUV class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
Str |
ACD |
Start |
|
M |
Op |
ACT |
Operate |
T |
M |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
о |
Settings |
||||
TmVCrv |
CURVE |
Operating curve type |
|
0 |
TmVChr33 |
CSG |
Multiline curve characteristic definition |
|
c |
TmVSt |
CSD |
Active curve characteristic |
|
о |
StrVal |
ASG |
Start value |
|
0 |
TmMult |
ASG |
Time dial multiplier |
|
0 |
MinOpTmms |
ING |
Minimum operate time |
|
о |
MaxOpTmms |
ING |
Maximum operate time |
|
о |
OpDITmms |
ING |
Operate delay time |
|
о |
RsDITmms |
ING |
Reset delay time |
|
о |
NOTE TmVChr33 refers to the attribute TmVCrv.setCharact = 33 etc. |
LN: Underpower factor Name: PUPF