LN: Overvoltage Name: PTOV
For a description of this LN, see IEC 61850-5. For some applications such aS transformer starpoint or delta supervision, “operate” may not be used.
|
PTOV class |
||||
|
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
|
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
|
Data objects |
||||
|
Status information |
||||
|
Str |
ACD |
Start |
|
M |
|
Op |
ACT |
Operate |
T |
0 |
|
Controls |
||||
|
OpCntRs |
INC |
Resettable operation counter |
|
0 |
|
Settings |
||||
|
TmVCrv |
CURVE |
Operating curve type |
|
0 |
|
TmVChr33 |
CSG |
Multiline curve characteristic definition |
|
c |
|
TmVSt |
CSD |
Active curve characteristic |
|
о |
|
StrVal |
ASG |
Start value |
|
0 |
|
TmMult |
ASG |
Time dial multiplier |
|
о |
|
MinOpTmms |
ING |
Minimum operate time |
|
О |
|
MaxOpTmms |
ING |
Maximum operate time |
|
О |
|
OpDITmms |
ING |
Operate delay time |
|
О |
|
RsDITmms |
ING |
Reset delay time |
|
о |
|
NOTE TmVChr33 refers to the attribute TmVCrv.setCharact = 33 etc. |
||||
LN: Protection trip conditioning Name: PTRC
This LN shall be used to connect the “operate” outputs of one or more protection functions to a common “trip” to be transmitted to XCBR. In addition, or alternatively, any combination of “operate” outputs of the protection functions may be combined to a new “operate” of PTRC.
|
PTRC class |
||||
|
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
|
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
|
Data objects |
||||
|
Status information |
||||
|
Tr |
ACT |
Trip |
|
c |
|
Op |
ACT |
Operate (combination of subscribed Op from protection functions) |
|
c |
|
Str |
ACD |
Start (combination of subscribed Str from protection functions) |
|
о |
|
Controls |
||||
|
OpCntRs |
INC |
Resettable operation counter |
|
0 |
|
Settings |
||||
|
TrMod |
ENG |
Trip mode |
|
о |
|
TrPlsTmms |
ING |
Trip pulse time |
|
О |
Condition C: At least one of the two status informations (Tr, Op) shall be used.LN: Thermal overload Name: PTTR
For a description of this LN, see IEC 61850-5 (LNs PROL, PSOL). PTTR shall be used for all thermal overload functions. Depending on the algorithm, the LN describes either a temperature or a current (thermal model). Temperature data objects are also provided by other LNs. Examples are the hot spot temperature in LN YPTR or the isolation gas temperature in LN
SIMG.
|
PTTR class |
||||
|
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
|
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
|
Data objects |
||||
|
Status information |
||||
|
Str |
ACD |
Start |
|
0 |
|
op |
ACT |
Operate |
T |
M |
|
AlmThm |
SPS |
Thermal alarm |
|
о |
|
BlkThm |
SPS |
Block closing command for circuit breaker because of thermal condition |
|
о |
|
Measured and metered values |
||||
|
Amp |
MV |
Current for thermal load model |
|
о |
|
Tmp |
MV |
Temperature for thermal load |
|
о |
|
TmpRI |
MV |
Relation between temperature and maximum temperature |
|
О |
|
LodRsvAlm |
MV |
Load reserve to alarm |
|
О |
|
LodRsvTr |
MV |
Load reserve to trip |
|
О |
|
Controls |
||||
|
OpCntRs |
INC |
Resettable operation counter |
|
о |
|
Settings |
||||
|
TmTmpCrv |
CURVE |
Characteristic curve for temperature measurement |
|
О |
|
TmTmpChr33 |
CSG |
Multiline curve characteristic definition |
|
с |
|
TmACrv |
CURVE |
Characteristic curve for current measurement /Thermal model |
|
о |
|
TmAChr33 |
CSG |
Multiline curve characteristic definition |
|
с |
|
TmTmpSt |
CSD |
Active curve characteristic |
|
о |
|
TmASt |
CSD |
Active curve characteristic |
|
о |
|
TmpMax |
ASG |
Maximum allowed temperature |
|
о |
|
StrVal |
ASG |
Start value |
|
о |
|
OpDITmms |
ING |
Operate delay time |
|
о |
|
MinOpTmms |
ING |
Minimum operate time |
|
О |
|
MaxOpTmms |
ING |
Maximum operate time |
|
О |
|
RsDITmms |
ING |
Reset delay time |
|
О |
|
ConsTmsl |
ING |
Time constant of the thermal model |
|
о |
|
AlmVaJ |
ASG |
Alarm value |
|
о |
|
DropoutVal |
ASG |
Dropout value for blocking closing command |
|
О |
|
NOTE TmAChr33 refers to the attribute TmACrv.setCharact = 33 etc. TmTmpChr33 refers to the attribute TmTmpCrv.setCharact = 33 etc. |
||||
LN: Undercurrent Name: PTUC
For a description of this LN, see IEC 61850-5 (LN PUCP). This LN shall be used for the undercurrent part of PUCP. The underpower part of LN PUCP is covered by PDUP. Different instances shall be used for phase and ground.
|
PTUC class |
||||
|
Data object name |
Common data class |
Explanation |
T |
MIOI C |
|
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
|
Data objects |
||||
|
Status information |
||||
|
Str |
ACD |
Start |
|
M |
|
Op |
ACT |
Operate |
T |
M |
|
Controls |
||||
|
OpCntRs |
INC |
Resettable operation counter |
|
о |
|
Settings |
||||
|
TmACrv |
CURVE |
Operating curve type |
|
о |
|
TmAChr33 |
CSG |
Multiline curve characteristic definition |
|
с |
|
TmASt |
CSD |
Active curve characteristic |
|
о |
|
StrVal |
ASG |
Start value |
|
о |
|
OpDITmms |
ING |
Operate delay time |
|
о |
|
TmMult |
ASG |
Time dial multiplier |
|
о |
|
MinOpTmms |
ING |
Minimum operate time |
|
о |
|
MaxOpTmms |
ING |
Maximum operate time |
|
о |
|
TypRsCrv |
ENG |
Type of reset curve |
|
о |
|
RsDITmms |
ING |
Reset delay time |
|
о |
|
DirMod |
ENG |
Directional mode |
|
о |
|
NOTE TmAChr33 refers to the attribute TmACrv.setCharact = 33 etc. |
||||
LN: Underfrequency Name: PTUF
For a description of this LN, see IEC 61850-5 (LN PFRQ). This LN shall be used to model the underfrequency part of PFRQ. One instance shall be used per stage.
|
PTUF class |
||||
|
Data object name |
Common data class |
Explanation |
T |
Nl/O/C |
|
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
|
Data objects |
||||
|
Status information ' |
||||
|
Str |
ACD |
Start |
|
M |
|
Op |
ACT |
Operate |
T |
M |
|
BlkV |
SPS |
Blocked because of voltage |
|
о |
|
Controls |
||||
|
OpCntRs |
INC |
Resettable operation counter |
|
о |
|
Settings |
||||
|
StrVal |
ASG |
Start value (frequency) |
|
О |
|
BlkVal |
ASG |
Voltage block value |
|
О |
|
OpDITmms |
ING |
Operate delay time |
|
о |
|
RsDITmms |
ING |
Reset delay time |
|
о |
LN: Undervoltage Name: PTUV
|
For a description of this LN, see IEC 61850-5. With an appropriate low operating curve, PTUV works also as zero voltage relay.PTUV class |
||||
|
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
|
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
|
Data objects |
||||
|
Status information |
||||
|
Str |
ACD |
Start |
|
M |
|
Op |
ACT |
Operate |
T |
M |
|
Controls |
||||
|
OpCntRs |
INC |
Resettable operation counter |
|
о |
|
Settings |
||||
|
TmVCrv |
CURVE |
Operating curve type |
|
0 |
|
TmVChr33 |
CSG |
Multiline curve characteristic definition |
|
c |
|
TmVSt |
CSD |
Active curve characteristic |
|
о |
|
StrVal |
ASG |
Start value |
|
0 |
|
TmMult |
ASG |
Time dial multiplier |
|
0 |
|
MinOpTmms |
ING |
Minimum operate time |
|
о |
|
MaxOpTmms |
ING |
Maximum operate time |
|
о |
|
OpDITmms |
ING |
Operate delay time |
|
о |
|
RsDITmms |
ING |
Reset delay time |
|
о |
|
NOTE TmVChr33 refers to the attribute TmVCrv.setCharact = 33 etc. |
||||
LN: Underpower factor Name: PUPF