LN: Generic security application Name: GSAL
This node shall be used to monitor security violations regarding authorisation, access control, service privileges and inactive associations.
GSAL class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
AuthFail |
SEC |
Authorisation failures |
|
M |
AcsCtIFail |
SEC |
Access control failures detected |
|
M |
SvcViol |
SEC |
Service privilege violations |
|
M |
Ina |
SEC |
Inactive associations |
|
M |
NumCntRs |
INS |
Number of counter resets |
|
о |
Controls |
||||
OpCntRs |
INC |
Resettable operation counter |
|
M |
NOTE An operation in the context of this logical node is a security violation. |
Logical nodes for interfacing and archiving LN Group: I
Modelling remarks
The Logical Nodes of group I shall be used at the border of the IEC 61850 modelled system with the exception of the process interface (e.g. to operator by IHMI, to external communication system by ITCI) or where the modelling level is changed (proxy).
LN: Archiving Name: 1ARC
For a description of this LN, see IEC 61850-5.
IARC class |
||||
Data object name |
Common data class |
Explanation |
T |
N1/0/ C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Status information |
||||
MemOv |
SPS |
Memory overflow |
|
M |
MemUsed |
INS |
Memory used in % |
|
о |
NumRcd |
INS |
Actual number of records |
|
о |
Settings |
||||
InTrgl |
ORG |
Reference to trigger |
|
о |
InLogl |
ORG |
Reference to data objects |
|
о |
MaxNumRcd |
ING |
Maximum number of records |
|
о |
RcdMod |
ENG |
Recorder operation mode (saturation, overwrite) |
|
о |
MemFull |
ING |
Memory full level |
|
о |
LN: Human machine interface Name: IHMI
For a description of this LN, see IEC 61850-5.
IHMI class |
||||
Data object name |
Common data class |
Explanation |
T |
N1/0/ C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment name plate |
|
0 |
Status information |
||||
EEHealth |
ENS |
External equipment health |
|
о |
LocKey |
SPS |
Local or remote key |
|
0 |
Loc |
SPS |
Local control behaviour |
|
0 |
Controls |
||||
LocSta |
SPC |
Switching authority at station level |
|
о |
LN: Safety alarm function Name: ISAF
For a description of this LN, see IEC 61850-5. Logical node ISAF shall be used to represent an alarm push-button or any other device that is used to provide an alarm in case of danger to persons or property.
ISAF class |
||||
Data object name |
Common data class |
Explanation |
T |
N1/0/ C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment name plate |
|
0 |
ISAF class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
Status information |
||||
EEHealth |
ENS |
External equipment health |
|
о |
Alm |
SPS |
Safety alarm (True=On, False=Off) |
|
M |
Con tro Is |
||||
OpCntRs |
INC |
Resettable operation counter |
|
0 |
AlmReset |
SPC |
Alarm signal reset |
|
о |
LN: Telecontrol interface Name: ITCI
For a description of this LN, see IEC 61850-5.
ITCI class |
||||
Data object name |
Common data class |
Explanation |
T |
MIDI C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment name plate |
|
О |
Status information |
||||
EEHealth |
ENS |
External equipment health |
|
о |
Loc |
SPS |
Local control behaviour |
|
О |
Alm1 |
SPS |
Alarm signal |
|
О |
Controls |
||||
LocSta |
SPC |
Switching authority at station level |
|
О |
LN: Telemonitoring interface Name: ITMI
For a description of this LN, see IEC 61850-5.
ITMI class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment name plate |
|
о |
Status information |
||||
EEHealth |
ENS |
External equipment health |
|
о |
LN: Teleprotection communication interfaces Name: ITPC
For a description of this LN, see IEC 61850-5. The LN ITPC comprises all information for communication channel setting and supervision. ITPC is not intended to generate direct process data objects. Thus, it does not contain the input and output data objects to be transmitted and it has no ‘operate’ data objects object.
ITPC class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ C |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
1TPC class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment nameplate |
|
0 |
Status information |
||||
EEHealth |
ENS |
External equipment health |
|
о |
GrdRxCmdRx |
SPS |
Alarm situation: Guard received together with the command, may indicate interference on the channel. Used in case of an analogue communication channel. |
|
0 |
LosSig |
SPS |
Alarm situation: No signal received, indicates a channel problem |
|
о |
TxCmdCntl |
INS |
For diagnostics: Transmitted commands counters (for each command) |
|
О |
RxCmdCntl |
INS |
For diagnostics: Received commands counters (for each command) |
|
о |
LosSyn |
SPS |
Alarm situation: Loss of synchronism. Indicates that there is no synchronization between the transmitter and the receiver, i.e., no communication is possible. Used in case of a digital communication channel. |
|
О |
Measured and metered values |
||||
Ber |
MV |
Bit error rate of the communication channel. Used in case of a digital communication channel |
|
О |
Fer |
MV |
Frame error rate of the communication channel. Used in case of a digital communication channel. May be vendor specific |
|
о |
CarLev |
MV |
Power of received signal in case of an analogue communication channel |
|
О |
Snr |
MV |
Signal to noise ratio (in dB), used in case of analogue communication |
|
О |
LoopTestTm |
MV |
Time measured at last loop test |
|
О |
Settings |
||||
NumTxCmd |
ING |
Number of used binary transmit commands |
|
о |
NumRxCmd |
ING |
Number of used binary receive commands |
- |
О |
TpcTxModl |
ENG |
Teleprotection application mode in transmit direction for each command (Unused, Blocking, Permissive, Direct, Unblocking, Status) |
|
о |
TpcRxModl |
ENG |
Teleprotection application mode in receive direction for each command (Unused, Blocking, Permissive, Direct, Unblocking, Status) |
|
о |
SecTmms |
ING |
Pickup security timer on loss of carrier guard signal: if a command is received within SecTmms after the guard has disappeared, this command is considered valid, used in case of an analogue communication channel. |
|
о |
BstRat |
ASG |
Level of increased power during the transmission of a command in dB. Used in case of an analogue communication channel |
|
О |
TxPwr |
ASG |
Transmit power (peak envelope power) in dBm. Used in case of an analogue communication channel |
|
о |
TxCtrHz |
ASG |
Transmit center frequency. Used in case of an analogue communication channel |
|
О |
RxCtrHz |
ASG |
Receive center frequency. Used in case of an analogue communication channel |
|
О |
TxBndWid |
ASG |
Transmit bandwidth. Used in case of an analogue communication channel |
|
О |
RxBndWid |
ASG |
Receive bandwidth. Used in case of an analogue communication channel |
|
О |
NOTE EEHealth is used to indicate the state of the communication channel, whereas PhyHealth is used to indicate the state of the (physical) communication device. If ITPC receives a GOOSE message with quality attribute “invalid" or “questionable" or no GOOSE message at all within Tmax, it will set PhyHealth to "Warning". Other actions are a local issue. |
Logical nodes for mechanical and non-electric primary equipment LN group К
Modelling remarks
This group of logical nodes represents various devices that can be supervised, controlled or operated but that are not primarily of electrical nature. This group includes devices like tanks,
valves, fans etc. Therefore, description and requirements are given in IEC 61850-5 with different level of detail.
LN: Fan Name: KFAN
Logical node KFAN shall be used to represent a fan. It can be seen as an extended nameplate that allows the temporary setting of data object.
KFAN class |
||||
Data object name |
Common data class |
Explanation |
T |
М/О/ c |
LNName |
|
The name shall be composed of the class name, the LN-Prefix and LN- Instance-ID according to IEC 61850-7-2, Clause 22. |
|
|
Data objects |
||||
Descriptions |
||||
EEName |
DPL |
External equipment nameplate |
|
о |
Status information |
||||
EEHealth |
ENS |
External equipment health |
|
о |
Loc |
SPS |
Local control behaviour |
|
О |
LocKey |
SPS |
Local or remote key |
|
О |
OpTmh |
INS |
Operation time |
|
О |
Measured and metered values |
||||
Spd |
MV |
Rotational speed of the fan |
|
о |
Controls |
||||
OpCtl |
SPC |
Operate fan |
|
с |
SpdSpt |
APC |
Speed set-point (in case of speed regulated motor) |
|
с |
LocSta |
SPC |
Switching authority at station level |
|
о |
Settings |
||||
MinOpTmm |
ING |
Minimum operation time in minutes |
|
О |
MaxOpTmm |
ING |
Maximum operation time in minutes |
|
о |
C: Condition: only one data object should be applied. |