Data object name

Semantics

ErrTerm

Control loop termination error value; the function cannot be fulfilled because of external reasons; the value gives difference between set point and actual value.

EvtCnt

Event counter - counts the number of times that a power quality event detected by the logical node occurred

EvTmms

Evaluation time in ms (time window) determines the lowest frequency

ExcITmms

Exclusion time in ms that consecutive triggers from the same source are ignored

FACntRs

Fault arc counter, resettable

FADet

TRUE = alarm that fault arc has been detected

FailMod

Circuit breaker failure detection mode.



Detection mode

Value


Current

1

Breaker status

2

Both current and breaker status

3

Other

4




FailTmms

The time delay in ms until the breaker failure function will issue the trip to an alternate device

FanA

Motor drive current of a fan in A

FanCtIGen FanCtl

FanCtIGen - Control of all fans FanCtl - Control of a single fan



Fan control

Value


Inactive

1

Stage 1

2

Stage 2

3

Stage 3

4

More stages may be added with numbers greater than 4

FanFlw

Air flow in fan

FanOvCur

Fan overcurrent trip

FctBIk

Dynamically blocking of function described by the LN

FctBlkRef

Blocking reference shows if a signal that blocks the function has been received.

Fer

Frame error rate .on this channel; count of erroneous (or missed, in case of redundancy) messages for each'1 000 messages forwarded to the application

FilAlm

Filter alarm, can be indicated by too high or too low differential pressure

FilTyp

Filter type: Low pass | High pass | Bandpass | Bandstop (notch) | Deadband

FishCnt

Fish counter reading

FixCol

Size of the external Fixcoil. The ANCR can take into account this value for the calculation of the necessary compensation. The size is given in Amperes and represents the current through the coil in case of a solid earth fault.

FldAmpRtg

Rated field current [A]

FldAmpRtgO

No-load field current for rated stator voltage [A]

FldRis

Field resistance [ohm]

FldRisTmp

Reference temperature for field resistance [usually in °С]

FloodAlm

Flood alarm

FloodLev

Flood alarm level

FltDiskm

The distance to a fault in km

FltlndRs

Earthfault indication, resettable



Data object name

Semantics

FltLoop





Fault loop

Value


Phase A to ground

1

Phase В to ground

2

Phase C to ground

3

Phase A to phase В

4

Phase В to phase C

5

Phase C to phase A

6

Others

7




FltNum

Fault number (number allocation is local issue)

FltZ

Fault impedance

Flush

Filter flushing in progress

FlushCnt

Filter flushing counter (resettable)

Flw

Flow rate of water or other liquid [usually in m3/s]

FuFail

TRUE = indicates that the TVTR fuse has opened/failed

GasFlwTr

Insulation liquid (for example oil) flow trip because of gas (maybe used for Buchholz trip)

GasInsAlm

Gas in insulation liquid (for example oil) alarm because of an abnormal condition (FALSE = normal, TRUE = alert, may be used for Buchholz trip)

GasInsTr

Gas in insulation liquid trip because of a dangerous condition (maybe used for Buchholz trip)

GenTrk

Common service tracking for all services for which no specific tracking data exists. The supported trackable services by GenTrk are a local issue.

GnCtl

Generator control

GndDIMod

Operate time delay for single-phase ground mode. TRUE = on, FALSE = off

GndDITmms

Operate time delay for single-phase ground faults in ms

GndOp

Ground operate value (3 /0)

GndStr

When the ground measurements exceed this value (or drop below, in the case of a dropout function), the operation of the related function is initiated. .

GnSpd

Generator speed

GnSt

Generator state



Generator state

Value


Stopped

1

Stopping

2

Started

3

Starting

4

Disabled

5




GoCBRef

Reference to the subscribed GOOSE control block

GocbTrk

Access service tracking for GOOSE control block

GrAlm

This data object summarises different alarms, assigned via configuration. TRUE = indicates a group alarm

Grind

This data object summarises different indications, assigned via configuration. TRUE indicates a group indication

GrnTag

Green tag information

GrRef

Reference to a higher-level logical device (LD). The Mod of this higher-level (referenced) LD influences the Beh of the LD and the Beh of all LNs in the LD where the GrRef is contained (see Beh of Table 10). See also the concept of “Logical device management hierarchy" described in lEC 61850-7-1.

GrdRxCmdRx

Alarm situation: Guard received together with the command, may indicate interference on the channel. Used in case of an analogue communication channel.

GriFItNum

Grid fault number is used for identification of disturbance records of a common fault (number allocation is local issue).

Data object name

Semantics

GrWrn

This data summarises different warnings, assigned via configuration. TRUE = indicates a group warning

H2ppm

Measurement of hydrogen (H2 in ppm). Combustible gas measurement in oil indicating the amount of deterioration of the insulation system.

H2Alm

H2 alarm for gas composition (FALSE = Normal, TRUE = alert)

H2Wrn

H2 warning for gas composition

H2O

Relative saturation of moisture in oil (in %). Note that this a measurement used in conjunction with H2OTmp.

H20Tmp

Temperature of oil at point of measurement of relative saturation of moisture in oil (usually in °С). Note that this is a measurement used in conjunction with H2O

HA

Phase-related sequence of harmonics or interharmonics current for А, В C, N, Net, Res

HaAmp

Non-phase-related sequence of harmonics or interharmonics current

HaAmpTm

Non-phase-related current time product

HaCfAmp

Non-phase-related current crest factors (peak waveform value/sqrt(2)/fundamental)

HaCfVol

Non-phase-related voltage crest factors (peak waveform value/sqrt(2)/fundamental)

HaKFact

Non-phase-related К Factor

HaRmsAmp

Non-phase-related current RMS harmonic or interharmonic (un-normalized Thd)

HaRmsVol

Non-phase-related voltage RMS harmonic or interharmonic (un-normalized Thd)

HaRst

Number of the harmonic that is being monitored for restraint

HaTdFact

Non-phase-related transformer derating factor

HaTiFact

Non-phase-related voltage telephone influence factor, method 1, 2, 3, ...

HATm

Phase-related current time product

HaTsWatt

Non-phase-related total harmonic or interharmonic active power (no fundamental) signed sum

HaTuWatt

Non-phase-retated total harmonic or interharmonic active power (no fundamental) unsigned sum

HaVol

Non-phase-related sequence of harmonics or interharmonics voltage

HaVolAmp

Non-phase-related sequence of harmonics or interharmonics apparent power

HaVolAmpr

Non-phase-related sequence of harmonics or interharmonics reactive power

HaWatt

Non-phase-related sequence of harmonics or interharmonics active power

HCfA

Phase-related current crest factors (peak waveform value/sqrt(2)/fundamental)

HCfPhV

Phase to ground voltage crest factors (peak waveform value/sqrt(2)/fundamental)

HCfPPV

Phase to phase voltage crest factors (peak waveform value/sqrt(2)/fundamental)

Health

This information reflects the state of the logical node related HW and SW. More detailed information related to the source of the problem may be provided by specific data objects. For LLNO, this data object reflects the worst value of "health" of the logical nodes that are part of the logical device associated with LLNO.


Health state

Value


Ok (“green") - no problems, normal operation

1

Warning (“yellow") - minor problems, but in safe operation mode

2

Alarm (“red”) - severe problem, no operation possible

3

Health states 1 (“green”) and 3 ('‘red”) are unambiguous by definition. The detailed meaning of Health state 2 (“yellow") is a local issue depending from the dedicated function/device.

HeatAlm

TRUE = supervision has detected an abnormal state of the heater

HiBatVal

High battery alarm value

HiColPos

High position of a suppression coil

HiCtIV

Highest control voltage since last reset

HiDmdA

Highest current demand since last reset



Data object name

Semantics

HiLim

High limit reached (input signal equal to or above limit)

HiLimSpt

High limit setpoint

HiSet

High operate value, percentage of the nominal current

HiTapPos

Highest tap position since last reset

HiTrgLev

High (positive) trigger level

HiVRtg

Rated voltage (high voltage level)

HKf

Phase-related К factor for А, В, C

Horlnsol

Total horizontal insolation [usually in W/m2]

HorWdDir

Horizontal wind direction

HorWdSpd

Average horizontal wind speed [usually in m/s]

HPhV

Sequence of harmonics or interharmonics for phase to ground voltages AN, BN, CN, NG

HPPV

Sequence of harmonics or interharmonics for phase to phase voltage AB, ВС, CA

HPTmpAlm

Hot point temperature alarm (FALSE = normal, TRUE = high)

HPTmpCIc

Calculated winding hotspot temperature

HPTmpOp

Winding hotspot temperature operates (could be used to trip a XCBR via a LN PTRC)

HPTmpTr

TRUE = indicates that a trip has occurred due to winding hotspot temperature

HRmsA

Phase-related current RMS harmonic or interharmonics (un-normalized total harmonic distortion, Thd) for А, В, C, N

HRmsPhV

Phase to ground voltage RMS harmonic or interharmonic (un-normalized Thd) for AN, BN, CN, NG

HRmsPPV

Phase to phase voltage RMS harmonic or interharmonic (un-normalized Thd) for AB, ВС, CA

HTdf

Phase-related transformer derating factor for А, В, C

HTif

Phase-related voltage telephone influence factor, method 1, 2, 3, ...

HTsW

Phase-related total phase harmonic or interharmonic active power (no fundamental) signed sum for А, В, C

HTuW

Phase-related total phase harmonic or interharmonic active power (no fundamental) unsigned sum for А, В, C

HVA

Phase-related sequence of harmonics or interharmonics apparent power for А, В, C

HVAr

Phase-related sequence of harmonics or interharmonics reactive power for А, В, C

HVStr

When the third harmonic phase voltage measurement exceeds this value, the PHIZ protection control operation is initiated.

HW

Phase-related sequence of harmonics or interharmonics active power for А, В, C

HydPH

Acidity of water (0-14)

HyPres

Actual pressure of the energy transferring medium in %, where 100 % corresponds to rated value and 0 % to block value

HyTmp

Actual temperature of the energy transferring medium (usually in °С)

Hz

The frequency of a power system in Hz

HzICIc

Frequency f1 at side 1 of the breaker. The side is not standardized; Common use: f1 = reference voltage or running voltage.

Hz2Clc

Frequency f2 at side 2 of the breaker. D50

HzAdj

This data object allows to switch on/off the frequency matching function of an automatic synchronizer. TRUE = ON; FALSE = OFF

HzChr

Frequency adjustment characteristic: definition of the rate of change of the governor (speed controller). The value is 1/s.

Hzlnd

This data object indicates whether the frequency difference (between the to voltages to be synchronised) is within the set limits or not. FALSE = value within the limits; TRUE = value outside the limits.

HzChr

Frequency adjustment characteristic