Table 4: Single core 600/1000 V cables with circular solid aluminium conductors


Page 3-E-15 HD 604 S1:1994/A1:1997

Part 3 Section E






























Table 5: Two-core 600/1000V cables with copper conductors

1

2

3

4

6

6

7

Nominal

Thickness of

Armoured cables

cross-

insulation






sectional area


Thickness of

Nominal steel

Thickness of

Approximate overall diameter

of conductor


extruded

armour wire

oversheath





bedding

diameter


Extruded

Taped В






bedding

bedding I

mm*

mm

mm

mm

mm

mm

mm і

1.Б'

0.6

0.8

0.9

1.4

12.3


2.5'

0.7

0.8

0.9

1.4

13.6

4'

0.8

0.8

0.9

1.4

16.1

6'

0.8

0.8

0.9

1.5

16.5

10*

1.0

0.8

1.26

1.6

20.1

1Є'

1.0

0.8

1.26

1.6

21.9

21.9

25*

1.2

1.0

1.6

1.7

23.0

22.6

25'

1.2

1.0

1.6

1.7

26.7

26.3

35*

1.2

1.0

1.6

1.8

24.8

24.4

35'

1.2

1.0

1.6

1.8

29.2

28.8

50’

1.4

1.0

1.6

1.9

27.8

27.4

70

1.4

1.0

1.6

1.9

30.4

30.0

95

1.6

1.2

2.0

2.1

35.5

34.7

120

1.6

1.2

2.0

2.2

38.0

37.2

150

1.8

1.2

2.0

2.3

41.3

40.5

185

2.0

1.4

2.5

2.4

46.4

45.2

240

2.2

1.4

2.5

2.5

51.2

50.0

300

2.4

1.6

2.5

2.7

66.4

54.8

400

2.6

1.6

2.5

2.9

61.9

60.3

' Circular or circular compacted stranded conductors (class 2).




* Shaped stranded conductors (class 2).





Cables having conductors of nominal cross-sectional area 50mm2 and above have shaped stranded conductors

(class 2}







1

2

3

4

Б

6

7

8

9

10

Nominal cross-

Thickness of

Armoured cables

sectional area of conductor

insulation

Thickness of

Nominal

Armour strip

Thickness of

Approximate overall diameter



extruded bedding

aluminium armour wire

Nominal

Nominal width

oversheath

Wire-armoured

Strip-armoured




diameter

thickness



Extruded bedding

Taped bedding

(taped bedding)

mm’

mm

mm

mm

mm

mm

mm

mm

mm

mm

16’

1.0

0.8

1.26

0.6

2.4

1.6

20.6

20.6

19.3

26'

1.2

1.0

1.6

0.6

2.4

1.7

21.3

20.9

18.9

26"

1.2

1.0

1.6

0.6

2.4

1.7

26.0

24.6

22.6

36'

1.2

1.0

1.6

0.6

2.4

1.8

22.9

22.6

20.6

366

1.2

1.0

1.6

0.6

2.4

1.8

27.2

26.8

24.8

60»

1.4

1.0

1.6

0.6

2.4

1.8

26.6

26.1

23.1

70

1.4

1.0

1.6

1.0

3.6

1.9

27.7

27.3

26.1

96

1.6

1.2

2.0

1.0

3.6

2.1

32.4

31.6

29.6


Table 7 - Three core 600/1000 V cables with copper conductors

1

2

3

4

Б

6

7

Nominal

Thickness of

Armoured саЫеа

СГО8Є- sectional area

insulation

Thickness of

Nominal steel

Thickness of

Approximate overall diameter

of conductor


extruded bedding

armour wire diameter

oversheath

Extruded bedding

Taped 1

bedding J

mm*

mm

mm

mm

mm

mm

mm 1

1.6'

0.6

0.8

0.9

1.4

12.8


2.6'

0.7

0.8

0.9

1.4

14.1


4'

0.8

0.8

0.9

1.4

16.8

-

Є'

0.8

0.8

1.26

1.6

18.0

-

10'

1.0

0.8

1.25

1.6

21.2

-

16’

1.0

0.8

1.25

1.6

23.1

23.1

26’

1.2

1.0

1.6

1.7

25.0

24.6

26'

1.2

1.0

1.6

1.7

2B.2

27.8

36*

1.2

1.0

1.6

1.8

27.1

26.7

36'

1.2

1.0

1.6

1.8

30.8

30.4

50‘

1.4

1.0

1.6

1.9

ЗО. Б

30.1

70

1.4

1.2

2.0

2.0

35.0

34.2

96

1.6

1.2

2.0

2.1

39.3

38.6

120

1.6

1.2

2.0

2.2

42.2

41.4

160

1.8

1.4

2.5

2.4

47.6

46.3

185

2.0

1.4

2.5

2.6

61.9

60.7

240

2.2

1.6

2.6

2.6

67.8

66.2

300

2.4

1.6

2.6

2.8

63.2

61.6

400

2.6

1.6

2.5

3.0

69.6

68.0



' Circular or circular compacted stranded conductors (class 2)

* Shaped stranded conductors (class 2)

Cables having conductors of nominal cross-sectional are 60 mm2 and above have shaped stranded conductors (class

1


2


3


4


6


6


7


8


8


10 1

Nominal cross-

Thickness of

Armoured cables

sectional area of conductor

insulation

Thickness of

Nominal

Armour strip

Thickness of

Approximate overall diameter



extruded bedding

aluminium armour wire

Nominal

Nominal width

oversheath

Wire-armoured

Strip-armoured




diameter

thickness



Extruded bedding

Taped bedding

(taped bedding)

mm’

mm

mm

mm

mm

mm

mm

mm

mm

mm

16*

1.0

0.8

1.25

0.6

2.4

1.6

21.7

21.7

20.4

26'

1.2

1.0

1.6

0.6

2.4

1.7

23.9

23.6

21.6

26*

1.2

1.0

1.6

0.6

2.4

1.7

26.4

26.0

24.0

36'

1.2

1.0

1.6

0.6

2.4

1.8

26.8

26.4

23.4

36*

1.2

1.0

1.6

0.6

2.4

1.8

28.7

28.3

26.3

60*

1.4

1.0

1.6

1.0

3.6

1.8

28.8

28.6

27.3

70

1.4

1.2

2.0

1.0

3.6

2.0

33.0

32.2

30.2

95

1.6

1.2

2.0

1.4

4.8

2.1

37.1

36.3

36.1

120

1.6

1.2

2.0

1.4

4.8

2.2

38.7

38.8

37.7

160

1.8

1.4

2.5

1.4

4.8

2.4

44.7

43.6

41.3

186

2.0

1.4

2.6

1.4

4.8

2.6

48.7

47.6

46.3

240

2.2

1.6

2.6

1.8

6.4

2.6

64.2

62.6

61.2

300

2.4

1.6

2.6

1.8

6.4

2.8

69.2

67.6

66.2