Ref. No. |
Test |
Unit |
Compound XLPE |
Compoun d PVC/ST |
Test method described in Publication |
1.3 |
Properties after ageing in air oven of PVC/ST sheath |
|
|
|
HD 505.1.2, sub-clause 8.1 and HD 505.1.1, sub-clause 9.2 |
1.3.1 |
Ageing conditions - temperature - duration of treatment |
°С h |
■ |
100 + 2 10 x 24 |
|
1.3.2 |
Values to be obtained for the tensile strength: - median, min. - variation 3), max. |
N/mm! % |
■ |
12.5 ±25 |
|
1.3.3 |
Values to be obtained for the elongation at break - median, min - variation 31, max |
% % |
• |
150 ±25 |
|
2 |
Hot set test of XLPE insulation |
|
|
|
HD 505.2.1, Clause 9 |
2.1 |
Test conditions:
|
°С min. N/mm2 |
200 ±3 15 0.20 |
■ |
|
2.2 |
Values to be obtained:
|
% % |
100 15 |
|
|
3 |
Loss of mass test of PVC/ST sheath |
|
|
|
HD 505.3.2, sub-clause 8.2 |
3.1 |
Ageing conditions - temperature - duration of treatment |
°С h |
|
100±2 7 x 24 |
|
3.2 |
Values to be obtained for the loss of mass, max. |
mg/cm2 |
|
1.5 |
|
(3)
Variation:
Table I (continued) - Requirements for the non*electrical test for cross-linked polyethylene
insulation and polyvinyl chloride sheath
1 |
2 |
3 |
4 |
5 |
6 |
Ref. No |
Test |
Unit |
Compound |
Compound |
Test method |
|
|
|
XLPE |
PVC/ST |
described in Publication |
4 |
Test for non-contamination Ml |
|
|
|
|
4.1 |
Ageing conditions - temperature |
°С |
100 ± 2 |
’ 100 ± 2 |
HD 505.1.2, sub- |
|
- duration of treatment |
h |
7 x 24 |
7 x 24 |
clause 8.1.4 |
4.2 |
Mechanical properties after |
|
As in ref. nos. |
As in ref. nos. |
|
|
ageing Values to be obtained |
|
1.2.2 & 1.2.3 |
1.3.2 & 1.3.3 |
|
Б |
Heat shock test |
|
|
|
HD 505.3.1, sub- |
5.1 |
Test conditions: - temperature |
°С |
|
150 ± 3 |
clause 9.2 |
|
- duration of treatment |
h |
- |
1 |
|
5.2 |
Result to be obtained |
|
|
Absence of cracks |
|
6 |
Pressure test at high temperature |
|
|
|
HD 505.3.1, sub- |
5.1 |
Test conditions: - force exerted by the blade |
|
|
See HD 50Б.3.1, sub-clause 8.2.4 |
clause 8.2 |
|
- duration of heating under load |
h |
|
See HD 5ОБ.3.1, sub-clause 8.2.5 |
|
|
- temperature |
°С |
|
90 ± 2 |
|
6.2 |
Result to be obtained: - median of the depth of |
% |
* |
50 |
|
|
penetration, max. |
|
|
|
|
7 |
Bend test at low temperature |
|
|
|
HD 505.1.4, sub- |
7.1 |
Test conditions: - temperature |
°С |
- |
-25 ± 2 |
clause 8.2 |
|
- period of application of low |
|
- |
See HD 505.1.4, |
|
|
temperature |
|
* |
sub-clause 8.2.3 Absence of cracks |
|
7.2 |
Result to be obtained |
|
|
|
HD 505.1.4, sub- |
8 |
Elongation test at low temperature |
|
|
|
clause 8.4 |
8.1 |
Test conditions - temperature |
°С |
|
-25 ± 2 |
|
|
- period of application of low |
|
- |
See HD 505.1.4, |
|
|
temperature |
|
|
sub-clause 8.4.4 |
|
|
|
|
|
& 8.4.5 |
|
8.2 |
Result to be obtained: - elongation without break, min. |
% |
- |
20 |
|
if required in Clause(s) 3 and/or 4.Table II-A. (concluded) - Schedule of tests for unarmourad and armoured cables
in accordance with sub-clauses 3 and 4.1
1 |
2 |
3 |
4 |
5 |
Ref. No |
Test |
Category of test {1) |
Test method described in |
Requirement given in sub-clause 2) |
2.8 |
Sheath or oversheath a) Application |
|
Visual examination |
Part 1; 5.7 |
|
b) Thickness |
|
HD 605 2.1.2 |
2.3 & 3.3.6 or 4.1.3.9 |
2.9 |
Overall diameter, if required, and ovality |
|
HD 605 2.1.3.1 & 2.1.3.2 |
2.4.3 & 3.3.7 or 4.1.3.10 |
2.10 |
Cable markings |
|
Visual examination & measurement |
Part 1; 3 |
3 |
Mechanical properties of insulation including the contamination test |
|
Table I |
Table I |
4 |
Mechanical properties of inner sheath |
|
|
|
4.1 |
Tensile test before and after ageing |
|
HD 505.1.1; 9.2 & 505.1.2; 8.1 |
Table I |
Б |
Mechanical and physical properties of sheath and oversheath including the contamination test for sheath of unarmoured cables. |
|
Table 1 |
Table I |
6 |
Bend test on complete cable |
|
HD 605 2.4.1.1 |
2.4.2 |
7 |
Test related to fire conditions Reduced flame propagation |
|
HD 405.3 |
2.4.4 |
All tests to be considered as type tests.
Clause numbers refer to this section unless stated otherwise.
Table ll-B - Schedule of tests for double screened cables
in accordance with sub-clause 4.2
1 |
2 |
3 |
4 |
5 |
Ref. No |
Test |
Category of test (1) |
Test method described in |
Requirement given in sub-clause (2) |
1 |
Electrical tests |
|
|
|
1.1 |
Conductor resistance |
|
HD 605 3.1.1 |
HD 383 |
1.2 |
Copper screen resistance |
|
HD 605 3.1.4.1 |
4.2.3.8.3 |
1.3 |
Screening efficiency |
|
IEC 96-1, sub-clause A.5.1 and А.Б.2 |
4.2.3.8.4 |
1.4 |
Voltage test on cores at 3500 V |
|
HD 606 3.2.2.2 |
2.4.1.2 |
1.5 |
Voltage test on complete cable at 3500 V |
|
HD 605 3.2.1 |
2.4.1.1 |
2 |
Provisions covering constructional and dimensional characteristics |
|
|
|
2.1 |
Conductor material and construction |
|
Visual examination and, for class 5 conductors, by measurement according to HD 605, 2.1.4.1 |
2.2 & 4.2.3.1 & Part 1; 5.1 |
2.2 |
Insulation; a) Application |
|
Visual examination |
Part 1: 5.2.2 |
|
b) Thickness |
|
HD 605 2.1.1 |
4.2.3.3 and Part 1: 5.2.3 |
2.3 |
Core identification |
|
Visual examination and measurement if applicable |
2.1 & 4.2.3.4 Part 1: 4 |
2.4 |
Assembly of cores |
|
Visual examination |
4.2.3.5 |
2.5 |
Inner covering |
|
Visual examination |
4.2.3.6 and Part 1, 5.4 |
2.6 |
Inner sheath a| Application |
|
Visual examination |
Part 1: 5.5 |
|
b) Thickness |
|
HD 605 2.1.2 |
2.3 & 4.2.3.7 |
2.7 |
Screens: a) Composition Ы Thickness of screen elements |
|
Visual examination HD 605 2.1.4 |
4.2.3.8.1 4.2.3.8.2 |
(1) All tests to be considered as type tests.
{2} Clause numbers refer to this section unless stated otherwise.
Table ll-B (concluded) - Schedule of tests for double screened cables
in accordance with sub-clause 4.2
1 |
2 |
3 |
4 |
5 |
Ref. No |
Test |
Category of test (1) |
Test method described in |
Requirement given in sub-clause (2) |
2.8 |
Sheath or oversheath a) Application |
|
Visual examination |
Part 1; 6.7 |
|
b) Thickness |
|
HD 606 2.1.2 |
2.3 & 4.2.3.10 |
2.9 |
Overall diameter - ovality |
|
HD 605 2.1.3.2 |
2.4.3 |
2.10 |
Cable markings |
|
Visual examination & measurement |
Part 1; 3 |
3 |
Mechanical properties of insulation including the contamination test for cables with inner sheath |
|
Table 1 |
Table I |
4 |
Mechanical and physical properties of all sheaths including the contamination test for the inner sheath. (3) |
|
Table 1 |
Table I |
Б |
Bend test on complete cable |
|
HD 60Б 2.4.1.1 |
2.4.2 |
6 |
Test related to fire conditions Reduced flame propagation |
|
HD 40Б.З |
2.4.4 |