Table 16 : Mass of zinc coating

1

2

Nominal diameter

Minimum mass of

of armour wire

zinc coating

mm

g/m2

0.9

112

1.25

150

1.6

172

2.0

180

2.5

195

3.15

206



Table 17 : Maximum resistance of conductor and armour for single-core cables having aluminium wire armour

1

2

3

4

5

6


Maximum resistance per kilometre of cable at 20°C




Aluminium wire armour

Nominal cross­sectional area of conductor

Copper conductor

Aluminium conductor

Cables with stranded copper or aluminium conductor

Cables with solid aluminium conductors




600/1000V

19OO/33OOV

600/1000V

mm9

Cl

n

Ci

Q

Q

50

0,387

0.641

0.82

0.73

0.90

70

0.268

0.443

0.73

0.65

0.79

95

0.193

0.320

0.64

0.45

0.71

120

0.153

0.253

0.45

0.42

0.49

150

0.124

0.206

0.40

0.39

0.45

185

0.0991

0.164

0.37

0.36

0.41

240

0.0754

0.125

0.33

0.33

0.37

300

0.0601

0.100

0.30

0.30

0.34

400

0.0470

0.0778

0.21

0.21

-

500

0.0366

0.0605

0.19

0.19

-

630

0.0283

0.0469

0.18

0.18

-

800

0.0221

0.0367

0.13

0.13

-

1000

0.0176

0.0291

0.12

0.12

Circular sectoral conductors

380


0.0800


-

0.24

480

0.0633

-

-

0.22

600

*■

0.0515

-

-

0.20

740

0.0410

-

-

0.15

960

-

0.0313

-

0.13

1200

-

0.0250

0.12



Table 18: Maximum resistance of conductor and armour for single-core cables having solid aluminium conductors and aluminium strip armour

1

2

3

Nominal cross-

Maximum resistance per kilometre of cable

sectional area of

at 20°C

conductor

Aluminium

Strip armour


conductor

600/1000V

mm2

Q

Q

50

0.641

1.8

70

0.443

1.6

95

0.320

1.4

120

0.253

1.2

150

0.206

1.1

185

0.164

0.57

240

0.125

0.51

300

0.100

0.46

Circular sectoral conductors

380

0.0800

0.29

480

0.0633

0.27

600

0.0515

0.24

740

0.0410

0.22

960

0.0313

0.15

1200

0.0250

0.14

Table 19 : Maximum resistance of conductor and armour for two core, three core and four core cables having solid aluminium conductors and aluminium strip armour

1

2

3

4

5

6


Maximum resistance per kilometre of cable at 20°C

Nominal cross­sectional area

Aluminium conductor

Strip armour

of conductor

Two-core

Three-core

Three-core

Four-core



600/1000V

600/1000V

1900/3300V

600/1000V

mm2

Q

n

D

Q

0

16

1.91

1.5

1.4

0.97

1.2

25

1.20

1.6

1.3

0.90

1.2

35

0.868

1.4

1.2

0.54

1.1

50

0.641

1.2

0.57

0.48

0.51

70

0.443

0.60

0.51

0.44

0.44

95

0.320

0.54

0.31

0.29

0.28

120

0.253

0.29

0.27

0.25

150

0.206


0.27

0.24

0.23

185

0.164


0.24

0.23

0.16

240

0.125

*

0.16

0.16

0.14

300

0.100


0.15

0.14

0.13

Table 20 : Maximum resistance of conductor and armour for two-core, three-core and four-core cables having wire armour

1

2

3

4

5

6

7

8

9

10

11

12

Nominal





Maximum resistance per kilometre of cable at 20

°С




cross-












sectional



Cables with stranded copper conductors and steel wire armour

Cables with solid aluminium conductors and aluminium

area of









wire

armour


conductor

Copper conductor

Aluminium conductor

Two-core

Three-core

Three-core

Four-core (equal)

Four-core (reduced

Two-core

Three-core

Three-core

Four-core








neutral)








600/1000V

600/1000V

19OO/33OOV

600/1000V

600/1000V

600/1000V

600/1000V

1900/3300V

600/1000V

mm2

Q

0

Й

Q

Q

Q

n

Q

Q

Q

Q

1.5*

12.1

-

10.2

9.5


8.8


-

-


-

2.5*

7.41

-

8.8

8.2

-

7.7

-

-

-

-

-

4

4.61

-

7.5

7.0

-

4.6


-

-

-

-

6

3.08

-

6.8

4.6

-

4.1

-

-


-

-

10

1.83


3.9

3.7

-

3.4

-

-

-

-

-

15

1.15

1.91

3.4

3.1

1.9

2.2

-

0.75

0.69

-

0.49

25

0.727

1.20

2.6

2.4

1.7

2.1

2.1

0.59

0.52

-

0.46

35

0.524

0.868

2.4

2.1

1.7

1.9

1.9

0.55

0.47


0.41

50

0.387

0.641

2.1

1.9

1.3

1.3

1.7

0.49

0.41

0.27

0.29

70

0.268

0.443

1.9

1.4

1.2

1.2

1.2

0.43

0.29

0.25

0.25

95

0.193

0.320

1.3

1.2

1.1

0.98

1.0

0.29

0.25

0.23

0.22

120

0.153

0.253

1.2

1.1

0.74

0.71

0.73

-

0.24

0.17

0.16

150

0.124

0.206

1.1

0.74

0.69

0.65

0.67

-

0.17

0.16

0.15

185

0.0991

0.164

0.78

0.68

0.64

0.59

0.60

-

0.15

0.15

0.13

240

0.0754

0.125

0.69

0.60

0.58

0.52

0.54


0.14

0.13

0.12

300

0.0601

0.100

0.63

0.54

0.53

0.47

0.49


0.13

0.12

0.11








(150mm2)





300

0.0601

0.100

-


-

-

0.47

(185mm2)

-

-

-

400

0.0470

-

0,56

0.49

0.48

0.34