All tests to be considered as type tests.
Clause numbers refer to this section unless stated otherwise.
No separate cold bend test on inner sheath, but compliance to be checked after cold bend test on complete cable.
GENERAL DATA FOR TYPE YMvK mb WITH CIRCULAR CONDUCTORS
1 |
2 |
3 |
4 |
5 |
6 |
Number and nominal |
Class of |
Insulation |
Thickness of |
Mean overall diam. |
|
cross-sect, area |
conductor HD 383 |
thickness Specified Value |
sheath Specified |
|
|
mm2 |
|
|
|||
|
|
mm |
Value |
Lower Limit |
Upper(*)limit |
|
|
|
mm |
mm |
mm |
1 x 1.5 |
1 |
0.7 |
1.4 |
5.4 |
7.0 |
1 x 2.5 |
1 |
0.7 |
1.4 |
5.7 |
7.3 |
1 x 4 |
1 |
0.7 |
1.4 |
6.2 |
7.8 |
1 x 6 |
1 |
0.7 |
1.4 |
6.7 |
8.8 |
1 x 10 |
1 |
0.7 |
1.4 |
7.0 |
9.5 |
1 x 10 |
2 |
0.7 |
1.4 |
7.5 |
10.0 |
1 x 16 |
2 |
0.7 |
1.4 |
9.1 |
11.5 |
1 x 25 |
2 |
0.9 |
1.4 |
10.0 |
13.0 |
1 x 35 |
2 |
0.9 |
1.4 |
11.5 |
14.5 |
1 x 50 |
2 |
1.0 |
1.4 |
12.5 |
16.0 |
1 x 70 |
2 |
1.1 |
1.4 |
14.5 |
18.0 |
1 x 95 |
2 |
1.1 |
1.5 |
16.5 |
20.5 |
1 x 120 |
2 |
1.2 |
1.5 |
18.0 |
22.0 |
1 x 150 |
2 |
1.4 |
1.6 |
20.0 |
24.0 |
1 x 185 |
2 |
1.6 |
1.6 |
22.0 |
26.5 |
1 x 240 |
2 |
1.7 |
1.7 |
25.0 |
29.5 |
1 x 300 |
2 |
1.8 |
1.8 |
28.0 |
33.0 |
1 x 400 |
2 |
2.0 |
1.9 |
32.0 |
37.0 |
1 x 500 |
2 |
2.2 |
2.0 |
36.0 |
41.0 |
1 x 630 |
2 |
2.4 |
2.2 |
39.0 |
45.0 |
1 x 800 |
2 |
2.6 |
2.3 |
44.0 |
50.0 |
1 x 1000 |
2 |
2.8 |
2.4 |
50.0 |
56.0 |
{*) See footnote at end of Table IIITABLE III (Continued)
1 |
2 |
3 |
4 |
5 |
6 |
Number and nominal cross-sect, area mm2 |
Class of conductor HD 383 |
Insulation thickness Specified Value mm |
Thickness of sheath Specified Value mm |
Mean overall diam. |
|
Lower Limit mm |
Upper! 11)limit mm |
||||
3 x 35 + |
2 |
0.9 |
1.8 |
24.5 |
29.0 |
1 x 25 |
2 |
0.9 |
|
|
|
3 x 50 + |
2 |
1.0 |
1.8 |
27.0 |
32.0 |
1 x 25 |
2 |
0.9 |
|
|
|
3 x 70 + |
2 |
1.1 |
1.9 |
31.0 |
37.5 |
1 x 35 |
2 |
0.9 |
|
|
|
3 x 95 + |
2 |
1.1 |
2.0 |
34.5 |
42.0 |
1 x 50 |
2 |
0.9 |
|
|
|
3 x120 + |
2 |
1.2 |
2.2 |
39.0 |
47.0 |
1 x 70 |
2 |
1.0 |
|
|
|
3 x 150 |
2 |
1.4 |
2.3 |
43.5 |
52.0 |
1 x 70 |
2 |
1.1 |
|
|
|
3 x185 + |
2 |
1.6 |
2.5 |
48.0 |
57.5 |
1 x 95 |
2 |
1.1 |
|
|
|
3 x 240 + |
2 |
1.7 |
2.6 |
54.0 |
65.0 |
1 x 120 |
2 |
1.1 |
|
|
|
4 x 35 + |
2 |
0.9 |
1.8 |
27.0 |
33.0 |
1 x 25 |
2 |
0.9 |
|
|
|
4 x 50 + |
2 |
1.0 |
1.9 |
30.5 |
36.5 |
1 x 25 |
2 |
0.9 |
|
|
|
4 x 70 + |
2 |
1.1 |
2.1 |
35.0 |
42.0 |
1 x 35 |
2 |
0.9 |
|
|
|
4 x 95 |
2 |
1.1 |
2.2 |
39.0 |
47.5 |
1 x 50 |
2 |
0.9 |
|
|
|
GENERAL DATA FOR TYPE YMvK mb WITH STRANDED-SHAPED CONDUCTORS
1 |
2 |
3 |
4 |
5 |
Number and nominal |
Class of |
Insulation |
Thickness of |
Nominal mean |
cross-sectional area of |
conductor |
thickness |
sheath |
overall diameter |
conductors |
HD 383 |
Specified value |
Specified Value |
|
|
(1) |
|
|
|
mm2 |
|
mm |
mm |
mm |
3 x 35 |
2 |
0.9 |
1.8 |
22 |
3 x 50 |
2 |
1.0 |
1.8 |
24 |
3 x 70 |
2 |
1.1 |
1.9 |
28 |
3 x 95 |
2 |
1.1 |
2.0 |
32 |
3 x 120 |
2 |
1.2 |
2.1 |
34 |
3 x 150 |
2 |
1.4 |
2.3 |
39 |
3 x 185 |
2 |
1.6 |
2.4 |
43 |
3 x 240 |
2 |
1.7 |
2.6 |
48 |
4 x 35 |
2 |
0.9 |
1.8 |
25 |
4 x 50 |
2 |
1.0 |
1.9 |
27 |
4x 70 |
2 |
1.1 |
2.0 |
32 |
4 x 95 |
2 |
1.1 |
2.1 |
36 |
4 x 120 |
2 |
1.2 |
2.3 |
39 |
4 x 150 |
2 |
1.4 |
2.4 |
44 |
4 x 185 |
2 |
1.6 |
2.6 |
49 |
4 x 240 |
2 |
1.7 |
2.8 |
55 |
(1) For special purposes Class 1 aluminium conductors may be applied.TABLE V GENERAL DATA FOR TYPES VO-YMvKas mb and VG-YMvKas mb with circular conductors 1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
|
|
|
|
Minimal nominal thickness of the |
|
|
|
|
|
||
Number and nominal cross sectional area of conductors mm2111 |
Class of conductor HD 383 |
Insulation thickness Specified value mm |
Thickness of inner sheath Specified value mm |
wires of the armour/PE-conductors |
Thickness of oversheath Specified value mm |
Nominal mean overall diameter mm |
Nominal copper equivalent crosssectional area of the armour/PE conductor mm2 |
Maximum electrical |
Number and nominal |
||
VO-YMcK as mb circular wires mm |
VG-' as circular wires mm |
/MvK mb flat wires mm |
resistance of the armour/PE conductor at 20°C ohm/km |
crosssectional area of conductors mm2 |
|||||||
1 x 1.5 |
1 |
0.7 |
0.8 |
0.3 |
1.0 |
|
1.8 |
11 |
1.5 |
12.1 |
1 x 1.5 |
1 x 2.5 |
1 |
0.7 |
0.8 |
0.0 |
1.0 |
- |
1.8 |
11 |
2.5 |
7.41 |
1 x 2.5 |
1 x 4 |
1 |
0.7 |
0.8 |
0.3 |
1.0 |
- |
1.8 |
12 |
4 |
4.61 |
1 x 4 |
1 x 6 |
1 |
0.7 |
0.8 |
0.3 |
1.0 |
- |
1.8 |
12 |
6 |
3.08 |
1 x 6 |
1 x 10 |
1 |
0.7 |
0.8 |
0.3 |
1.0 |
- |
1.8 |
13 |
10 |
1.83 |
1 x 10 |
1 x 10 |
2 |
0.7 |
0.8 |
0.3 |
1.0 |
|
1.8 |
14 |
10 |
1.83 |
1 x 10 |
1 x 16 |
2 |
0.7 |
0.8 |
0.3 |
1.0 |
- |
1.8 |
15 |
16 |
1.15 |
1 x 16 |
1 x 25 |
2 |
0.9 |
0.8 |
0.3 |
1.0 |
- |
1.8 |
16 |
16 |
1.15 |
1 x 25 |
1 x 35 |
2 |
0.9 |
0.8 |
0.3 |
1.0 |
|
1.8 |
18 |
16 |
1.15 |
1 x 35 |
1 x 50 |
2 |
1.0 |
0.8 |
- |
1.0 |
•* |
1.8 |
19 |
25 |
0.727 |
1 x 50 |
1 x 70 |
2 |
1.1 |
0.8 |
- |
1.0 |
1.4 |
1.8 |
22 |
35 |
0.524 |
1 x 70 |
1 x 95 |
2 |
1.1 |
0.8 |
- |
1.0 |
1.4 |
1.8 |
24 |
50 |
0.387 |
1 x 95 |
1 x 120 |
2 |
1.2 |
0.8 |
- |
(2) |
(2) |
1.8 |
27 |
60 |
0.306 |
1 x 120 |
1 x 150 |
2 |
1.4 |
0.8 |
|
(2) |
(2) |
1.8 |
29 |
75 |
0.248 |
1 x 150 |
1 x 185 |
2 |
1.6 |
0.9 |
- |
(2) |
(2) |
1.8 |
32 |
95 |
0.193 |
1 x 185 |
1 x 240 |
2 |
1.7 |
0.9 |
- |
(2) |
(2) |
1.9 |
35 |
120 |
0.153 |
1 x 240 |
1 x 300 |
2 |
1.8 |
1.0 |
|
(2) |
(2) |
1.9 |
38 |
150 |
0.124 |
1 x 300 |
1 x 400 |
2 |
2.0 |
1.0 |
- |
(2) |
(21 |
2.1 |
42 |
200 |
0.0940 |
1 x 400 |
1 x 500 |
2 |
2.2 |
1.1 |
- |
(2) |
(2) |
2.2 |
47 |
250 |
0.0732 |
1 x 500 |
1 x 630 |
2 |
2.4 |
1.1 |
- |
(2) |
(21 |
2.3 |
51 |
315 |
0.0566 |
1 x 630 |
1 x 800 |
2 |
2.6 |
1.2 |
- |
(2) |
(21 |
2.4 |
56 |
400 |
0.0470 |
1 x 800 |
1 x 1000 |
2 |
2.8 |
1.3 |
|
(2) |
(21 |
2.6 |
62 |
500 |
0.0366 |
1 x 1000 |