ДСТУ HD 604 S1:2012/Зміна №1:2012 сторінка 24 з 46
-
(concluded)
-
Schedule of Tests
-
1
-
2
-
3
-
4
-
Ref No
-
Test
-
Category of test
-
Test method described in:
-
Requirement given in clause*
-
3
-
Mechanical properties
-
3.1
-
Insulation
-
T
-
Table 1
-
4.3.2 and Table 1
-
3.2
-
Extruded bedding
-
T
-
Table 2
-
4.3.4 and Table 2
-
3.3
-
Oversheath
-
T
-
Table 2
-
4.3.6 and Table 2
-
4
-
Compatibility test
-
T
-
HD 605 2.4.12.2
-
Table 30 and 2.4.5
-
5
-
Tests related to fire conditions
-
5.1
-
Bedding - oxygen index
-
T&S
-
HD4O5.3 (Annex B)
-
2.4.6.4
-
5.2
-
Oversheath - oxygen index
-
T&S
-
HD4O5.3 (Annex B)
-
2.4.6.4
-
5.3
-
Complete cable:- (a) single cable
-
s
-
HD405.1
-
HD 405.1
-
(b) bunched cables
-
T
-
HD605, 4.1.1
-
2.4.6
-
-
Clause numbers refer to this section unless stated otherwise.
-
Single core 600/1000V cables with stranded copper or aluminium conductors
-
1
-
2
-
3
-
4
-
5
-
6
-
Armoured cables
-
Nominal crosssectional area
-
Thickness of insulation
-
Thickness
-
Nominal
-
Thickness of
-
Approximate
-
of conductor*
-
of extruded
-
armour wire
-
oversheath
-
overall
-
bedding
-
diameter
-
diameter
-
mm2
-
mm
-
mm
-
mm
-
mm
-
mm
-
50
-
1.0
-
0.8
-
0.9
-
1.5
-
17.5
-
70
-
1.1
-
0.8
-
1.25
-
1.5
-
20.2
-
95
-
1.1
-
0.8
-
1.25
-
1.6
-
22.3
-
120
-
1.2
-
0.8
-
1.25
-
1.6
-
24.2
-
150
-
1.4
-
1.0
-
1.6
-
1.7
-
27.4
-
185
-
1.6
-
1.0
-
1.6
-
1.8
-
30.0
-
240
-
1.7
-
1.0
-
1.6
-
1.8
-
32.8
-
300
-
1.8
-
1.0
-
1.6
-
1.9
-
35.6
-
400
-
2.0
-
1.2
-
2.0
-
2.0
-
40.5
-
500
-
2.2
-
1.2
-
2.0
-
2.1
-
44.2
-
630
-
2.4
-
1.2
-
2.0
-
2.2
-
48.8
-
800
-
2.6
-
1.4
-
2.5
-
2.4
-
55.4
-
1000
-
2.8
-
1.4
-
2.5
-
2.5
-
60.6
-
* Circular or circular compacted stranded conductors (class 2)
-
-
TABLE 5
-
Single core 600/1000V cables with solid aluminium conductors
1 -
-
2
-
3
-
4
-
5
-
6
-
7
-
8
-
9
-
Armoured cables
-
Nominal area
-
Thickness of
-
Thickness of
-
Nominal
-
Armour strip
-
Thickness of
-
Approximate overall diameter
-
of conductor
-
insulation
-
extruded
-
armour wire
-
bedding
-
diameter
-
Nominal
-
Nominal
-
oversheath
-
Wire-armoured
-
Strip-armoured
-
thickness
-
width
-
Circular solid conductors (Class 1)
-
mm1
-
mm
-
mm
-
mm
-
mm
-
mm
-
mm
-
mm
-
mm
-
50
-
1.0
-
0.8
-
0.9
-
0.6
-
2.4
-
1.5
-
16.3
-
15.7
-
70
-
1.1
-
0.8
-
1.25
-
0.6
-
2.4
-
1.5
-
18.7
-
17.4
-
95
-
1.1
-
0.8
-
1.25
-
0.6
-
2.4
-
1.6
-
20.6
-
19.3
-
120
-
1.2
-
0.8
-
1.25
-
0.6
-
2.4
-
1.6
-
22.1
-
20.8
-
150
-
1.4
-
1.0
-
1.6
-
0.6
-
2.4
-
1.7
-
25.2
-
23.2
-
185
-
1.6
-
1.0
-
1.6
-
0.6
-
2.4
-
1.8
-
27.4
-
25.4
-
240
-
1.7
-
1.0
-
1.6
-
1.0
-
3.6
-
1.8
-
29.9
-
28.7
-
300
-
1.8
-
1.0
-
1.6
-
1.0
-
3.6
-
1.9
-
32.4
-
31.2
-
Circular sectoral conductors
-
380
-
2.0
-
1.2
-
2.0
-
1.4
-
4.8
-
2.0
-
37.1
-
35.9
-
(4 x 95)
-
480
-
2.2
-
1.2
-
2.0
-
1.4
-
4.8
-
2.1
-
40.4
-
39.2
-
(4 x 120)
-
600
-
2.4
-
1.2
-
2.0
-
1.4
-
4.8
-
2.2
-
43.8
-
42.6
-
(4 x 150)
-
740
-
2.6
-
1.4
-
2.5
-
1.4
-
4.8
-
2.3
-
49.1
-
46.9
-
(4 x 185)
-
960
-
2.8
-
1.4
-
2.5
-
1.8
-
6.4
-
2.5
-
54.4
-
53.0
-
(4 x 240) 1200
-
(4 x 300)
-
3.0
-
1.6
-
2.5
-
1.8
-
6.4
-
2.6
-
59.7
-
58.3
-
-
-
Page 4-Е-17 HD 604 S1:1994/A1:1997
-
Part 4 Section E
-
-
Page 4-Е-18
-
HD 604 S1:1994/A1:1997
-
Part 4 Section E
Побачили розбіжність з офіційним текстом?
Дивіться також
Сборник ГОСТ ЕСКД
Збірник із 154 стандартів