N/A - Test not applicable
* - See reference in Column 7
Table 2 : Schedule of test*
1 |
2 |
3 |
4 |
|
Ref No |
Test |
Category |
Test method |
Requirement given in |
|
of test |
describe in: |
clause* |
|
1. |
Electrical tests |
|
|
|
1.1 |
Conductor resistance |
R |
HD 383 |
4.3.1 |
1.2 |
Armour resistance |
S |
HD 60S 3.1.2 |
4.3.5(g) 1 |
1.3 |
Voltage test (a) Oversheath - single core |
R |
HD 60S 3.2.3.1 |
2.4.2.1 |
1 |
(b) Complete cable |
R |
HD 605 3.2.1 |
2.4.2.2 |
1.4 |
Insulation resistance test:- (a) Insulated core |
T |
HD 605 3.3.1 |
2.4.3 |
|
(bl Complete Cable |
R |
HD 605 3.3.2 |
2.4.3 |
|
(c) Oversheath |
T |
HD 605 3.3.4 |
2.6 |
1.6 |
Spark test:- (a) Insulated core |
R |
HD 605 3.6.1 |
— |
|
(b) Oversheath |
R |
HD 605 3.6.1 |
■ |
2. |
Provisions covering constructional & dimensional characteristics |
|
|
|
2.1 |
Conductor material & construction |
S |
HD 383 |
4.3.1 and Part 1, 5.1 |
2.2 |
Insulation (al Application |
S |
Visual Examination |
Part 1. 5.2.2 |
|
(b) Thickness |
s |
HD 605 2.1.1 |
4.3.2 & Part 1. 5.2.3 |
2.3 |
Core identification |
s |
Visual Examination & Measurement |
2.1 and Part 1, 4 |
2.4 |
Laid up cores |
s |
Visual Examination |
4.3.3 |
2.5 |
Bedding (a) Taped bedding gap |
s |
HD 605 2.1.8 |
4.3.4.2 |
|
(b) Extruded bedding thickness |
s |
HD 605 2.1.2 |
2.2, 4.3.4 & Part 1, 6.4.3 |
2.6 |
Armour- la) Wire armour: |
|
|
|
|
(1) Diameter |
s |
HD 605 2.1.4.3 |
4.3.5(a) |
|
(2) Mass of zinc coating |
T |
HD 605 2.5.1.1D |
4.3.5(b) |
|
(galvanised wire only) (3) Wrapping test |
T |
HD 605 2.3.2 |
4.3.5(c) |
|
(galvanised wire only) (4) Tensile test |
T |
HD 605 2.3.1.1 |
4.3.5(d) |
|
(aluminium wire only) |
|
|
|
|
(b) aluminium strip armour: |
|
|
|
|
(1) Dimensions of individual |
s |
HD 605 2.1.4.3 |
4.3.5(e) |
|
strips (2) Tensile test |
T |
HD 605 2.3.1.1 |
4.3.5(f) |
2.7 |
Oversheath thickness |
s |
HD 605 2.1.2 |
4.3.6 and Part 1, 5.7.3 |
2.8 |
Cable markings |
R |
Visual examination & measurement |
2.3 & Part 1, 3 |
Clause numbers refer to this section unless stated otherwise.Table 2 : (concluded)
1 |
2 |
3 |
4 |
6 |
Ref No |
TEST |
Category |
Test method |
Requirement given |
|
|
of test |
described in: |
in clause5 |
3. |
Mechanical properties |
|
|
|
3.1 |
Insulation |
T |
Table 1 |
4.3.2 |
3.2 |
Extruded bedding |
T |
Table 1 |
4.3.4 |
3.3 |
Oversheath |
T |
ТаЫе 1 |
4.3.6 |
3.4 |
Compatibility test |
T |
HD 806, 2.4.12.2 |
2.6 |
4. |
Tests related to fire conditions |
|
|
|
4.1 |
Insulation - oxygen index |
T& s |
HD 406.3 (App. 8) |
2.4.4.4 |
4.2 |
Bedding - oxygen index |
T& s |
HD 406.3 (Арр. B) |
24.4.4 |
4.3 |
Oversheath - oxygen index |
T& s |
HD 406.3 (Арр. B) |
24.4.4 |
4.4 |
Complete cable:- |
|
|
|
|
(a) single cable |
s |
HD 406.1 |
HD 406.1 |
|
(b) bunched cables |
T |
HD 606, 4.1.1 |
2.4.4 |
Table 3: Single core 600/1000 V cables with circular stranded copper or aluminium conductors
1 |
2 |
3 |
4 |
5 |
6 |
Nominal crosssectional area of conductor* |
Thickness of insulation |
Armoured cables |
|||
Thickness of extruded bedding |
Nominal armour wire diameter |
Thickness of oversheath |
Approximate overall diameter |
||
mm2 |
mm |
mm |
mm |
mm |
mm I |
50 |
1.4 |
0.8 |
1.25 |
1.5 |
19.1 |
70 |
1.4 |
0.8 |
1.25 |
1.6 |
21.1 |
95 |
1.6 |
0.8 |
1.25 |
1.6 |
23.4 |
120 |
1.6 |
1.0 |
1.6 |
1.7 |
26.3 |
150 |
1.8 |
1.0 |
1.6 |
1.7 |
28.3 |
185 |
2.0 |
1.0 |
1.6 |
1.8 |
30.8 |
240 |
2.2 |
1.0 |
1.6 |
1.9 |
34.1 |
300 |
2.4 |
1.0 |
1.6 |
1.9 |
37.0 |
400 |
2.6 |
1.2 |
2.0 |
2.1 |
42.0 |
500 |
2.8 |
1.2 |
2.0 |
2.1 |
45.6 |
630 |
2.8 |
1.2 |
2.0 |
2.2 |
49.7 |
800 |
2.8 |
1.4 |
2.5 |
2.4 |
55.8 |
1000 |
3.0 |
1.4 |
2.5 |
2.5 |
61.0 |
* Circular or circular compacted stranded conductors (class 2) |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
|||
Nominal cross- |
Thickness of |
Armoured cables |
|||||||||
sectional area of |
insulation |
|
|
|
|
|
|
|
|||
conductor* |
|
Thickness of |
Nominal |
Armour strip |
Thickness of |
Approximate overall diameter |
|||||
|
|
extruded |
armour wire |
|
|
oversheath |
|
|
|||
|
|
bedding |
diameter |
Nominal |
Nominal |
|
Wire- |
Strip-armoured |
|||
|
|
|
|
thickness |
width |
|
armoured |
|
|||
mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
mm I |
|||
50 |
1.4 |
0.8 |
1.25 |
0.6 |
2.4 |
1.5 |
17.8 |
16.5 |
|||
70 |
1.4 |
0.8 |
1.25 |
0.6 |
2.4 |
1.6 |
19.6 |
18.3 |
|||
95 |
1.6 |
0.8 |
1.25 |
0.6 |
2.4 |
1.6 |
21.7 |
20.4 |
|||
120 |
1.6 |
1.0 |
1.6 |
0.6 |
2.4 |
1.7 |
24.3 |
22.3 |
|||
150 |
1.8 |
1.0 |
1.6 |
0.6 |
2.4 |
1.7 |
26.1 |
24.1 |
|||
185 |
2.0 |
1.0 |
1.6 |
1.0 |
3.6 |
1.8 |
28.3 |
27.1 |
|||
240 |
2.2 |
1.0 |
1.6 |
1.0 |
3.6 |
1.9 |
31.2 |
30.0 |
|||
300 |
2.4 |
1.0 |
1.6 |
1.0 |
3.6 |
1.9 |
33.7 |
32.5 |
|||
Circular sectoral conductors |
|||||||||||
380 (4 x 95) |
2.6 |
1.2 |
2.0 |
1.4 |
4.8 |
2.0 |
38.4 |
37.2 |
|||
480 |
2.8 |
1.2 |
2.0 |
1.4 |
4.8 |
2.1 |
41.7 |
40.5 |
|||
<4 X 120) |
|
|
|
|
|
|
|
|
|||
600 |
2.8 |
1.2 |
2.0 |
1.4 |
4.8 |
2.2 |
44.6 |
43.4 |
|||
(4 x 150) |
|
|
|
|
|
|
|
|
|||
740 |
2.8 |
1.4 |
2.5 |
1.4 |
4.8 |
2.3 |
49.5 |
47.3 I |
|||
(4 x 185) |
|
|
|
|
|
|
|
|
|||
960 |
3.0 |
1.4 |
2.6 |
1.8 |
6.4 |
2.5 |
54.9 |
53.5 I |
|||
(4 x 240) |
|
|
|
|
|
|
|
|
|||
1200 (4 x 300) |
3.0 |
1.6 |
2.5 |
1.8 |
6.4 |
2.6 |
59.7 |
68.3 I |
|||
|
|
|
•Circular solid conductors (class 1) |
|
|
|