All tests to be considered as type tests.
Clause numbers refer to this section unless stated otherwise.
No separate cold bend test on inner sheath, but compliance to be checked after cold bend test on complete cable.
The oil, ozone and water absorption test shall not be carried out on the innersheath.TABLE IV
GENERAL DATA FOR TYPE YMz.Kmbzh WITH STRANDED-SHAPED CONDUCTORS
1 |
2 |
3 |
4 |
5 |
|||||
Number and nominal crosssectional area of conductors mm2 |
Class of conductor HD 383 (’) |
Insulation thickness Specified value mm |
Thickness of sheath Specified value mm |
Nominal mean overall diameter mm |
|||||
3 |
X |
35 |
2 |
0.9 |
1.8 |
22 |
|||
3 |
X |
50 |
2 |
1.0 |
1.8 |
24 |
|||
3 |
X |
70 |
2 |
1.1 |
1.9 |
28 |
|||
3 |
X |
95 |
2 |
1.1 |
2.0 |
32 |
|||
3 |
X |
120 |
2 |
1.2 |
2.1 |
34 |
|||
3 |
X |
150 |
2 |
1.4 |
2.3 |
39 |
|||
3 |
X |
185 |
2 |
1.6 |
2.4 |
43 |
|||
3 |
X |
240 |
2 |
1.7 |
2.6 |
48 |
|||
4 |
X |
35 |
2 |
0.9 |
1.8 |
25 |
|||
4 |
X |
50 |
2 |
1.0 |
1.9 |
27 |
|||
4 |
X |
70 |
2 |
1.1 |
2.0 |
32 |
|||
4 |
X |
95 |
2 |
1.1 |
2.1 |
36 |
|||
4 |
X |
120 |
2 |
1.2 |
2.3 |
39 |
|||
4 |
X |
150 |
2 |
1.4 |
2.4 |
44 |
|||
4 |
X |
185 |
2 |
1.6 |
2.6 |
49 |
|||
4 |
X |
240 |
2 |
1.7 |
2.8 |
55 |
For special purposes Class 1 aluminium conductors may be applied.TABLE V GENERAL DATA FOR TYPES Z.O-YMz.Kasmbzh AND Z.G-YMz.Kasmbzh WITH CIRCULAR CONDUCTORS 1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
Number and |
Class of |
Insulation |
Thickness of |
Minimal nominal thickness of the |
Thickness of |
Nominal |
Nominal |
Maximum |
Number and |
||
nominal cross sectional area |
conductor HD 383 |
thickness Specified |
inner sheath Specified |
wires of the arm |
our/PE-conductors |
oversheath Specified |
mean overall |
copper equivalent |
electrical resistance of |
nominal crosssectional area |
|
of conductors mm*" |
|
value mm |
value mm |
Z,0-YMz,K asmbzh circular wires mm |
Z.G-Y asm circular wires mm |
Mz,K bzh flat wires mm |
value mm |
diameter mm |
cross-sectional area of the armour/PE conductor mm2 |
the armour/PE conductor at 20°C ohm/km |
of conductors mm’ |
1 x 1.6 |
1 |
0.7 |
0.8 |
0.3 |
1.0 |
- |
1.8 |
11 |
1.6 |
12.1 |
1 x 1.6 |
1 X 2.5 |
1 |
0.7 |
0.8 |
0.3 |
1.0 |
|
1.8 |
11 |
2.6 |
7.41 |
1 x 2.5 |
1 x 4 |
1 |
0.7 |
0.8 |
0.3 |
1.0 |
- |
1.8 |
12 |
4 |
4.61 |
1 x 4 |
1 x 6 |
1 |
0.7 |
0.8 |
0.3 |
1.0 |
- |
1.8 |
12 |
6 |
3.08 |
1 x 6 |
1 x 10 |
1 |
0.7 |
0.8 |
0.3 |
1.0 |
|
1.8 |
13 |
10 |
1.83 |
1 x 10 |
1 x 10 |
2 |
0.7 |
0.8 |
0.3 |
1.0 |
- |
1.8 |
14 |
10 |
1.83 |
1 x 10 |
1 x 16 |
2 |
0.7 |
0.8 |
0.3 |
1.0 |
- |
1.8 |
16 |
16 |
1.15 |
1 x 16 |
1 x 25 |
2 |
0.9 |
0.8 |
0.3 |
1.0 |
|
1.8 |
16 |
16 |
1.15 |
1 x 25 |
1 x 35 |
2 |
0.9 |
0.8 |
0.3 |
1.0 |
- |
1.8 |
18 |
16 |
1.15 |
1 x 35 |
1 x 60 |
2 |
1.0 |
0.8 |
• |
1.0 |
- |
1.8 |
19 |
25 |
0.727 |
1 x 50 |
1 x 70 |
2 |
1.1 |
0.8 |
- |
1.0 |
1.4 |
1.8 |
22 |
35 |
0.524 |
1 x 70 |
1 x 95 |
2 |
1.1 |
0.8 |
- |
1.0 |
1.4 |
1.8 |
24 |
60 |
0.387 |
1 x 95 |
1 x 120 |
2 |
1.2 |
0.8 |
* |
(21 |
(2) |
1.8 |
27 |
60 |
0.306 |
1 x 120 |
1 x 150 |
2 |
1.4 |
0.8 |
- |
(2) |
(2) |
1.8 |
29 |
75 |
0.248 |
1 x 160 |
1 x 185 |
2 |
1.6 |
0.9 |
|
(2) |
(2) |
1.8 |
32 |
95 |
0.193 |
1 x 185 |
1 x 240 |
2 |
1.7 |
0.9 |
- |
(2) |
(21 |
1.9 |
35 |
120 |
0.153 |
1 x 240 |
1 x 300 |
2 |
1.8 |
1.0 |
* |
(2) |
(21 |
1.9 |
38 |
150 |
0.124 |
1 x 300 |
1 x 400 |
2 |
2.0 |
1.0 |
- |
(2) |
(2) |
2.1 |
42 |
200 |
0.0940 |
1 x 400 |
1 x 600 |
2 |
2.2 |
1.1 |
- |
(2) |
(2) |
2.2 |
47 |
260 |
0.0732 |
1 x 500 |
1 x 630 |
2 |
2.4 |
1.1 |
- |
(2) |
(2) |
2.3 |
61 |
315 |
0.0566 |
1 x 630 |
1 x 800 |
2 |
2.6 |
1.2 |
•» |
<2> |
(2) |
2.4 |
66 |
400 |
0.0470 |
1 x 800 |
1 x 1000 |
2 |
2.8 |
1.3 |
■ |
(2) |
(2) |
2.6 |
62 |
500 |
0.0366 |
1 x 1000 |
111 Single core cables with an armour/PE conductor made up partly of steel wires are for direct current only.
121 The shape and dimensions of armour wires for conductor sizes of 120mm2 and above are left to the choice of the manufacturer
Page 5-C-26
HD 604 S1:1994/A1:1997
Part 5 Section C
TABLE VI GENERAL DATA FOR TYPE Z.G-YMz,Kasmbzh і і I I I I I I і і 1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
Number and |
Class of |
Insulation |
Thickness |
Minimal nominal |
Thickness of |
Nominal mean |
Nominal |
Maximum |
Number |
|
nominal |
conductor |
thickness |
of inner |
thickness of the |
oversheath |
overall |
copper |
electrical |
and |
|
cross |
HD 383 |
Specified |
sheath |
wires of the armour/ |
Specified |
diameter |
equivalent |
resistance of |
nominal |
|
sectional |
|
Value |
Specified |
PE conductor |
value |
|
cross- |
the armour/ |
cross- |
|
area of |
|
|
Value |
|
|
|
|
sectional |
PE conductor |
sectional |
conductor |
|
|
|
|
|
|
|
area of the |
at 20eC |
area of |
|
|
|
|
|
|
|
|
armour/ PE |
|
conductors |
|
|
|
|
|
|
|
|
conductor |
|
|
|
|
|
|
flat |
conductor |
|
|
|
|
|
|
|
|
|
wires |
wires |
|
|
|
|
|
mm’ |
|
mm |
mm |
mm |
mm |
mm |
mm |
mm’ |
ohm/km |
mm2 |
3 x 35 |
2 |
0.9 |
0.8 |
0.8 |
1.0 |
1.8 |
25 |
16 |
1.15 |
3x 35 |
3 x 50 |
2 |
1.0 |
0.8 |
0.8 |
1.0 |
1.8 |
27 |
25 |
0.727 |
3 x 50 |
3x 70 |
2 |
1.1 |
0.9 |
0.8 |
1.0 |
2.0 |
31 |
35 |
0.524 |
3 x 70 |
3 x 95 |
2 |
1.1 |
1.0 |
0.8 |
1.0 |
2.1 |
35 |
50 |
0.387 |
3 x 95 |
3 x 120 |
2 |
1.2 |
1.0 |
0.8 |
1.0 |
2.2 |
38 |
60 |
0.306 |
3 x 120 |
3 x 150 |
2 |
1.4 |
1.1 |
0.8 |
1.0 |
2.4 |
42 |
75 |
0.248 |
3 x 150 |
3 x 185 |
2 |
1.6 |
1.1 |
0.8 |
1.0 |
2.5 |
46 |
96 |
0.193 |
3 x 185 |
3 x 240 |
2 |
1.7 |
1.2 |
1.4 |
1.6 |
2.7 |
52 |
120 |
0.153 |
3 x 240 |
4x 35 |
2 |
0.9 |
0.8 |
0.8 |
1.0 |
1.8 |
27 |
16 |
1.15 |
4x 35 |
4 x 60 |
2 |
1.0 |
0.9 |
0.8 |
1.0 |
1.9 |
30 |
25 |
0.727 |
4x 50 |
4 x 70 |
2 |
1.1 |
1.0 |
0.8 |
1.0 |
2.1 |
35 |
35 |
0.524 |
4x 70 |
4x 95 |
2 |
1.1 |
1.0 |
0.8 |
1.0 |
2.2 |
39 |
50 |
0.387 |
4x 95 |
4 x 120 |
2 |
1.2 |
1.1 |
0.8 |
1.0 |
2.4 |
43 |
60 |
0.306 |
4x 120 |
4 x 150 |
2 |
1.4 |
1.1 |
0.8 |
1.0 |
2.5 |
47 |
75 |
0.248 |
4 x 150 |
4 x 185 |
2 |
1.6 |
1.2 |
1.4 |
1.6 |
2.7 |
53 |
95 |
0.193 |
4 x 185 |
4 x 240 |
2 |
1.7 |
1.3 |
1.4 |
1.6 |
2.9 |
59 |
120 |
0.153 |
4 x 240 |