15 times the cable diameter for single core саЫеэ

12 times the cable diameter for multicore cables

5.4.2 In case of single time bending * for example in front of a terminal - it is permitted to reduct the bending radius by 50%, provided the work 4 made by skilled personnel t o the cable it heated up to 3O°C and the саЫе is bent by means of a template.

Б.Б Clbl, (тоигтьгю) installation

5.5.1 The following approximate values for the distance between brackets apply when cablee are mounted on walls or ceikngs Ixir^onta'fy:

20 times the cable diameter

These distances are also valid between points of support in case of laying on cable racks or inside cable trays. In any case a distance of 80 cm should not be exceeded.

  1. For vertical cable laying on walls higher distances between the brackets are permitted depending on the type of cable and type of brackets. Distances of 1,5m however should not be exceeded.

  2. Single core cables may be laid atone or system wise in bundles (trefoil formation}. A system of bundled cables may be treated as a muhtcore cable. Ir> case of separate laying of single core cables, brackets made of plastic or brackets consisting of non magnetic metals have to be used. Steel brackets may be used if the magnetic circuit is not dosed.

  3. Cables and bundles of cables are to be tightened m such a way that damages in form of pressure marks caused by heat expansion are avoided.

6. Voltage lest on cable olsnis aftet installation

It is recommended to test new cable plants after installation by a d.c* voltage between 5.6kV and 8kV tex at least 15 minutes but not more than 30 minutes



APPENDIX В

Cu f rent-carry И g Capacity

1

3

3

4

No

Тігпи


TabUJ Quenlftv

1


general




This wcnpn appbee to th» current-cerrying capacity under both «landed end devilling previa tons provided that the cable e n three-pluiee operation wirh Three cerkductori loaded or one siigle-ccre саЫе in DO operation


2


Basic proyworis


МММ M * U Ы •

Tempera їм ret

Bonding Fr Ефіопе у Operating oondftignir

Maximum permeable operating temperature Motin'tuf» ehofl-circuit tempwature Concentric eerKiictve bonded it both ends Рсі'АСГ ггифіеііиу

The tofr. listed rofixJ cweni-carrying сараснее зги h^eed on standard provi«»fine such as

- optMftiing ntoiie laying conditions

»neironn|«MuF cwtoifioria

For deviating operating сопЛЪопа the current currytog cepacetes in the fable ere io be multiplied by appropriate conversion factors, which slub be based on the Mme cokulaiHxt method and operecog condHtone atf uted lor iho cunertvcarrving capacity gtveti m thia clnuee. *

30*C

2БО*С

венг

See Appendix 0. Table Bl 1

3




3.1


Cables !ff a»r




Ao lad current-caaryng capacity IR imck* at andiiNJ prou udon*

See

Appendix B.

Table Bl

3.1.1

3J.2

3.1.3

Operating mode

Laying ccndj*i>nt

Є nvfrcm mantel СНХКЯТ«ОЛ&

CoriciriLMMit eporetion lofld factor

Froe in rnr

Ono mufti-COftf cable bid vingty.

Tlvee einfdo-core cables laid tteough-euT ifa enbie length m dose tret of formol bon With Ofiqi lyibrtl only.

Protect «in здоігчі direct thvmH retitotton due to тек eiCi

Ambient lempcrature, air

L0

30*C



Той agreed between purchaser and manufacturer



APPENDIX В
Current-Carrying Capacity
(continued)

1

2

3

4

No

Terms

Require rnacts

ТаЫЫ Quantify

3.2


Current carrying capacity tftdtf deviating provisions


3.2.1

Operating mode

-

-

3.2 2

Laying coMiton*

Grouping of catoes on trays and leddots


3.2.3

Enviontne^ial concMjona

Ambci'it laniptfratLtfO, as

1O*-ftO*C

4


Snort густш




Оіалд a «.hon-circuit cable* Sto loaded thermally and mechanically asweC Therefore the nominal cross-seci ionol ora* S,. m* ««№ type end necessary the hang of cable* ora to bo Mtectgd carefully еисЪ lh*( ths csNee are noi overloaded. Ilie provienme are valid lor a

short-оивді duration up to Б s.


4d

Rafael short- circuit Ci#rent arwm^ii

The rated v+xwt circuit currant for a short CrciJil durational 1» f* wlciOoted by mutt inlying the rated ahcrl-tme current denary with llw ги?*П'Піі cross-sectional urea of the conductor.

See Appahdot, Table В 2

4.2

P«rnw»ibl* short-circuit current (thermal!

F«r short etcuit durations horn Is tha pernwsble short-circuit current t* to be calcubiH by cbvding the rated short- cvguit current with the square root of the short circuit duration (in ah


4.3

Permissible abort-circuit Cltfrent (dynamic)

З'луїіг'сша eablts Ehazbe salaiy fixed Ю withstand the si facts of peek short treuft ыигегЧ*. for гінііксот® саЫеа special meeeurtnt <irc not rsc*ivad up to 4 Ofc A Ірпок vekiciL




,M To be agreed between purchaser and manufacturerTable 81 : Rated Current •carrying capacity» cablet in air

1

2

3

4

*

6

Insulating Material

XLP6

Permissible operating temperature

90°C

Designation

N2XH

N2XCK

Arrangement

Hi





Number of loaded conductors

1

3

3

3

3

Cross-sectional area


Rated Current in A


In mm*






1.5

33

26

25

27

2 5

43

32

34

33

36

4

57

42

44

43

47

6

72

53

56

54

59

10

99

74

77

75

81

16

131

98

102

100

109

25

177

133

138

136

146

35

217

162

170

165

179

50

265

197

207

201

218

70

336

250

263

255

275

95

415

308

325

314

336

120

485

359

380

364

388

150

557

412

437

416

438

185

646

475

507

480

601

240

774

564

604

565

580

300

901

649

697

643

654

400

1060

761

811

737

733

500

1252

866

940

807

825

I1J Rated current for cables in DC-Systems with return conductor far awayTable B2 r PerrrussAle short-circuit temperature end rated short time current densities

1

2

3 1 4

5

6

>

a

9

Permissible shorts circuit temperature In eC

Conductor temperature ar the beginning of short-circuit in °С

90

80 70

60

50

40

30

20

Rated short-time Current density in A/mm* for a rated short-circuit duration of 1 з

250

143

149 1 154

159

165

170

176 I

1 Bl

SECTION И ; CABLES WITH COPPER CONDUCTORS WITH AND WITHOUT CONCENTRIC
COPPER CONDUCTORS AND WITH OPTIONAL ARMOURING

CONTENTS

Pane

  1. . Scope 54+2

  2. Additional general requirements

    1. Identification of cores 5-М-2

    2. Cable marking 5*H*2

  3. Cables with or without concentric conductor and optional armour

ЭЛ Rated voltage 54+2

3.2 Construction 5-H-3

  1. Teats S4+4

TaWes: і 6 54+5

REFERENCES

References are made, in this Section H of Part б of HD 604, to other Part* of this HD and to other Harmonisation Documents and International Standards at follows:

HD 363 Conductors of insulated cables (Endorsing IEC 228 and 228A)

HD 405 Teste on electric cables under fire conditions

HD 506 Common test methods for insulating and sheathing materials of electric cables

HD 602 Test on gases evolved during the combustion of materials from cables : Determination of degree of acidity (corrosivity) of gases by measuring pH and conductivity

HD 605 Electric cables t Additional test methods

HD 606 Measurement of smoke density of electric cables burning under defined conditions

In all cases reference to another HD of International Standard implies the latest edition of that document.SECTION H

This section specifies requirements fur and dimensions of single-core end multi-core halogen-free cables having reduced fire performance. The cables are insulated and sheathed either with • thermoplastic or crosslinked compound. The cables may be armoured, and an additional halogen-free outer sheath may also be epptied.

The maximum continuous conductor temperature shal not exceed 70QC for compounds НГГ2 and HMT2 or 9C9C for aM other compounds. The maximum permissible conductor temperature under short-circuit conditions is 160’C except for crosslinked compounds НІС and HMC where the corresponding temperature limit is 250°С,

  1. Additional general reouirements

The following general requirements shall ba read in conjunction with those given in Part 1 of HD604.

  1. Identification of cores

The cores of cables having one up to five conductors shall be identified by colours In accordance with the following schemer

Number of cores

Identification n

Cables with Cables without

green-yeiiow core

1 2

3 4

Б

green-yelow ■ *

green-yeNow, Ыаск. red. white green-yellow, black, red, white, blue

black

black, red

black, red, white

black, red. whher blue

rtl The identification of a core having a reduced c.s.a, shall be ’ green yellow for cables with green-yeHow core * blue for cables without green-yellow core



  1. Cable marking

The method of cable marking shew comply as far as applicable with clause 3 of Part 1 and ihe following requirements:

The external surface of all cables shall be legibly marked with the type designation.

The type designation is under consideration.

  1. . СаЫм without Of with concentric conductor aod optional armour

    1. Rated vcHtaog

0.6/1 kV

32 Construction

  1. Conductor

Only copper conductor* are permissible. The conductor* «hall comply with HD 383. CUss 1 for solid conductor* end Сіам 2 for stranded conductor*. Type of conductor end nominal c.e.a. of conductor are specified in Table 3. Ona conductor may have a reduced c.s.a. as specified in Table 4. Over the conductor a tape may be applied.

  1. Insulation

The insulation shall ba a halogen-free thermoplastic 1HIT1 or HIT21 or halogen-free crosslinked (НІС) compound and sh*N comply with the requirement* and tests specified ki ТаЫе 1A, The insulation wad thickness shai comply with the minimum value specified In Table 5; the mean is not repuirad.

Over the Insulation of multi-core cables, a halogen-free separating element may be applied; it shall be applied over the insulation of single core cables with concentric conductor. Insulation and sheath of single-core cables shall be separable.

  1. Assembly of cores

The cores of cables having two up to five cores shall be cabled. Over the laid up cores a halogen-free binder tap* may be applied.

  1. Inner covering

The core assembly of mufti-core cables may ba covered completely by a halogen-free inner covering which shall be easily removable. It may consist either:

  • of a taped bedding;

  • of an extruded bedding compound, or - of a combination of the two.

Halogen free fillers for the interstices may be applied.