01 Circular or compacted circular stranded conductor [class 2)
TABLE 5
Single core 600/1000 V cables with solid aluminium conductor
1 |
2 |
3 |
4 |
s |
6 |
Nominal cross- |
Thickness of |
Thickness of |
Nominal |
Thickness of |
Approximate |
section^ area |
insUatkon |
extruded |
aluminium armour |
oversheath |
overall |
of conductor |
|
bedding |
wire diameter |
|
diameter |
Circular solid conductor (ctm 11 |
|||||
mm’ |
mm |
mm |
mm |
mm |
mm |
50 |
1-0 |
0.8 |
0.9 |
1.5 |
16-2 |
70 |
1J |
0.8 |
125 |
1*5 |
18.7 |
95 |
VI |
0.8 |
1.25 |
1.6 |
20-6 |
120 |
1.2 |
0-8 |
1.25 |
1.6 |
22.1 |
1Б0 |
1,4 |
1.0 |
1.6 |
1.7 |
25.2 |
185 |
1Л |
1.0 |
1.6 |
1.8 |
27-4 |
240 |
1*7 |
ro |
16 |
1.8 |
29.9 |
300 |
1-8 |
1.0 |
1.6 |
1.9 |
32.4 |
Circular sectoral conductors |
|||||
mm’ |
mm |
mm |
mm |
mm |
mm |
380 14 x 951 |
2.0 |
1.2 |
2.0 |
2.0 |
37.1 |
480 (4 x 120) |
2.2 |
E2 |
2.0 |
2.1 |
40.4 |
600 14 x 150) |
2Д |
1,2 |
2,0 |
2.2 |
43.8 |
740 (4 x 1851 |
2 6 |
1.4 |
2.5 |
2.3 |
49.1 |
960 <4 x 240) |
2.8 |
1.4 |
2 6 |
2-6 |
54.4 |
1200 |
3.0 |
1.6 |
2.5 |
2.6 |
597 |
44 x 300) |
|
|
|
|
TABLE 6
Two core 600/1000 V cables with stranded copper conductors
1 |
2 |
3 |
4 |
5 |
6 |
Nominal cross* |
Thickness of |
Thickness of |
Nominal steel |
Thickness of |
Approximate |
sectional area |
insulation |
extruded |
armour wire |
Qversheaih |
overall |
of conductor |
|
bedding |
diameter |
|
diameter |
mm* |
mm |
mm |
mm |
ГТИП |
mm |
1.5*’» |
0.7 |
0*8 |
0*9 |
1.3 |
12*5 |
2*6*’» |
07 |
0*8 |
0,9 |
1*4 |
13.6 |
4rtl |
0.7 |
0*8 |
0-9 |
1.4 |
14*7 |
0ПІ |
0.7 |
0*8 |
0.9 |
1.4 |
15.9 |
10”» |
0*7 |
0*8 |
0.9 |
1.5 |
18.0 |
Iff1* |
0.7 |
0,8 |
1.26 |
1.5 |
20*0 |
25*'1 |
09 |
0*8 |
1.2Б |
16 |
24.1 |
25q* |
0.9 |
0.8 |
1*25 |
1.6 |
204 |
35n* |
0.9 |
1.0 |
1*8 |
1.7 |
27*9 |
35е* |
0.9 |
KO |
1*6 |
1.7 |
23*4 |
БО"» |
1,0 |
1*0 |
1.6 |
1*8 |
25 8 |
70 |
1.1 |
1-0 |
1,6 |
1*9 |
29 0 |
95 |
1.1 |
1.2 |
2.0 |
2*0 |
33.1 |
120 |
1,2 |
1.2 |
2,0 |
2.1 |
36*1 |
150 |
1,4 |
1*2 |
2.0 |
2*2 |
39*3 |
185 |
1.6 |
1.4 |
2.5 |
2.4 |
44*7 |
240 |
1.7 |
1.4 |
2,5 |
2.5 |
49,0 |
300 |
1.8 |
1*6 |
2,5 |
2*6 |
53 5 |
400 |
2.0 |
1*6 |
2*5 |
2*8 |
59.0 |
111 Circular or compacted circular stranded conductors (class 2|
10 Shaped stranded conductor (class 21
'* Cables having conductors of nominal cross-sectional area 50mm* and above have shaped stranded conductors (class 21
TABLE 7
Two сото 600/1000 V cablet with solid aluminium conductors
1 |
2 |
3 |
4 |
5 |
6 |
Nominal cross- |
Thickness of |
Thickness of |
Nominal steal |
Thickness of |
Approximate |
sectional area |
insulation |
extruded |
armour wire |
oversheath |
overall |
of conductor |
|
bedding |
diameter |
|
diameter |
mm1 |
mm |
mm |
mm |
mm |
mm |
16’11 |
0*7 |
0.8 |
1.25 |
1.6 |
19,2 |
25"* |
0,9 |
0.8 |
1.25 |
1.6 |
22.4 |
25» |
0.9 |
0.8 |
1.25 |
1.6 |
18.7 |
Э611' |
0.9 |
1.0 |
V6 |
1.7 |
25.7 |
35а |
0,9 |
vo |
V6 |
1.7 |
2V4 |
5ОЛ |
1.0 |
VO |
V6 |
1.8 |
23,5 |
70 |
VI |
VO |
ve |
1.9 |
26.3 |
95 |
1,1 |
V2 |
2.0 |
2.0 |
30.0 |
411 Solid circular conductor (class 1)
ш Solid sector shew! conductor (class 1)
w Cables having conductors of nominal cross-sectional area 50mm1 and above have shaped solid conductors (class IITABLE-6
Three core 600/1000 V cables whh stranded copper coo ductors
1 |
2 |
3 |
4 |
5 |
6 |
Nominal cross- |
Thickness of |
Thickness of |
Nominal steel |
Thickness of |
Approximate |
sectional area |
insulation |
extruded |
armour wire |
oversheath |
overall |
of conductor |
|
bedding |
diameter |
|
diameter |
mm* |
mm |
mm |
mm |
mm |
mm |
1.5m |
0Л |
0.8 |
0.9 |
E3 |
13.0 |
2Л"' |
0.7 |
0,8 |
0 9 |
E4 |
14.1 |
4m |
0.7 |
0.8 |
09 |
1.4 |
15.3 |
|
0.7 |
0 8 |
0.9 |
1.4 |
16.6 |
Itf" |
0.7 |
0.8 |
1.25 |
E5 |
19.5 |
Iff1’ |
0.7 |
0.8 |
E25 |
E6 |
21.2 |
25’11 |
0.9 |
1.0 |
E6 |
E7 |
28.7 |
25«* |
0.9 |
1.0 |
1.6 |
E7 |
23.6 |
35'” |
0.9 |
1.0 |
Efl |
E8 |
29.6 |
35а' |
0.9 |
1.0 |
Efl |
E8 |
259 |
БО™ |
E0 |
1,0 |
1.6 |
1.8 |
28.5 |
70 |
1.1 |
E0 |
1.6 |
1.9 |
32.2 |
95 |
E1 |
1,2 |
2.0 |
2.1 |
37.0 |
120 |
1,2 |
12 |
2.0 |
2.2 |
40 4 |
150 |
1.4 |
E4 |
2,5 |
2.3 |
45.5 |
186 |
E6 |
1.4 |
2.5 |
2.4 |
49.8 |
240 |
1.7 |
E4 |
2.5 |
2,6 |
55.1 |
300 |
1.8 |
E6 |
2.5 |
2.7 |
60.2 |
400 |
2.0 |
E6 |
2.5 |
2.9 |
66.6 |
ni Circular or compacted circular stranded conductors (class 2)
Shaped stranded conductor (class 2)
ai Cables having conductors of nominal cross-sectional area 50mm* and above have shaped stranded conductors (class 21
TABLE 9
Three core 600/1000 V cables with solid aluminium conductors