APPENDIX

GUIDE TO USE

  1. Recommendation fgr.use

  1. Permissible applications

Halogen-free cables may be laid in rooms and areas where dark smoke and oorroeive кігтдас can give damage In the case of a fire.

  1. 2 Concentric conductor

The concentric conductor may be used as PE or PEN.

  1. RecofnnMndabon ftx tNoarxi trantoort aod handlion of cabl> drums

The distance between the outer cable layer of fdied-up dekvery drum and the heed of the flange shal be sufficiently high to avoid damages of the cable. It shaM be prevented that drum flanges come in touch with the cable of another drum.

For the transport of filled-up drums only suitable carriers shall be used.

Cable drums wHh flange diameters exceeding Im have to be transported with the drum-axis in horizontal position. The drums have to be protected against movement. Loading and unloading shad be made by suitable devices to avoid damages of the cables and of the cable drums.

Fdlod-up cable drums shall be rolled only on short distances over plain, solid ground in the (Erection indicated. The drums shall be rolled in the same direction as it was turned during the cable reeling in (he manufacturing plant»

Cable ends shall be attached to the drum during transport, storage and laying.

2-1 Cable end sealing

The cable ends have to be sealed water-proof during transport storage and laying.

r

Race

tdation for cable installations

The cables shall be installed in such a way that the spread of fire end its consequences are limited. The relevant specifications especially those for preventive fire protection shal be taken into account.

  1. Pullmo loads

For pulling In of cables by means of a pulkng-head at the conductors, the folowing maximum values for the pulling forces are allowed:

al For cables with copper conductors о ■ БО N/mma

ЬЗ For cables with aluminium conductors cr 30 N/mm*

With these puling forces it » guaranteed that the permitted ekxiQatkxi of 0.2% for the conductor will not be exceeded. The maximum puling force (И la calculated from the total of the CSA (SL The CSA of the screens and of the concentric conductors shall not be considered in this calculation.

P - Sa where PinN tn N/mm1

S In mm*

  1. Lowest temperature remitted for с»Ыв laving

The lowest allowed temperature of the cables during installation and mourning of accessories is:

-20 °С for cables with insulation and sheath of thermoplastic or cross-linked halogen-free polymeric compounds.

These temperatures are valid for the cable itself and not for the surrounding. In case cables do have a lower than the permrutd temperature they must be warmed up. Core has to bo taken that the temperature remains within the permitted range of temperature during the whole laying procedure.

  1. Bendina Radius

During instahauon the bending radius shall not fai below the following values:

15 times the cable diameter for single core cables

12 times the cable diameter for multicore cables

In case of single time bending - for example in front of a terminal - it is permitted to reduce the bonding radius by 50%, provided the work ts made by ski led personnel, e.g., the cable ie heated up to 30°C, and the cable is bem by means of a template.SECTION Et CABLES WITH COPPER OR ALUMINIUM CONDUCTORS AND WIRE ARMOUR

CONTENTS

Вам

  1. Scope

2ь Additional general requirements

  1. Identification of cores S-E-2

  2. Thickness of inner sheath 5-E-2

  3. Cable marking 5*Ь2

  4. Additional test requirements 5-E-4

  1. iNcrt applicable! 5-E-7

  2. Cables with metallic covering

    1. Coda designation &‘E-7

    2. Rated voltage 5-E-6

    3. Construction 5-E-8

    4. Tests 5-E-9

Tables: 1 21 6-E-10

Appendix: Guide to use 5 E 34

REFERENCES

References are made, in this Section E of Part 5 of HD 604, to other Parte of this HD and to other Harmon nation Documents and International Standards as foftows:

HD 383 Conductors of Insulated cables [Endorsing IEC 226 and 228A)

HD 405 Testa on electric cables under fire conditions

HD 605 Common test methods for insulating and sheathing materials of electric cables

HD 602 Test on gases evolved during the combustion of materials from cables : Determination of degree of oddity (corrotrvrtv) of gases by measuring pH and conductivity

HD 606 Electric cables : Additional test methods

IEC 183 Guide to the selection of high voltage cables

In aU cases reference to another HD or international Standard implies the latest edition of that document



SECTION E



  1. Зедов

This section specifies requirements for and dimensions of single core and mufti-core halogen'free cables with XLFE or HEPR insulation end halogen-free sheath having reduced fire propagation performance.

The cables considered are intended for им where the combination of ambient temperature and temperature rhe due to loading current results in a conductor temperature not exceeding 90°C. The maximum temperature for short<tfcuit condmon ie 250°С.

This section covers the following desses of cable:

Ш 2, 3 and 4 core cables having copper conductor and steel wire armour

tii) 2t 3 and 4 core cables having sold aluminium conductors and steal wks armour

tiiti Single core cables having stranded copper, solid or sectoral aluminium conductors and ahjminkint wire armour

(rvf Mu№*core аихійагу cables having stranded copper conductors, and steel wire armour

  1. Additional оикаі reouiremenp

Th* fo*owino 0*ner«l r*qui««mentt Sha* be read in conjunction with those given In parr 1.

  1. Identification of cores

The cores of all cables shall be Identified either by numbers or by colours In accordance with the following sequence:

iber of cores


Identification



R

One Two

Three

Four

Auxiliary cables

ed or black

Red, black

Red, yellow, blue

Red, yellow, blue, black 1, 2, 3, 4, 6« 6, 7, and upwards

The height of individual numbers shall be not less than 1.5mm and the Interval between adjacent numbers shal not exceed 70mm.

  1. Thickness of inner sheath

The minimum thickness of extruded inner covering shea not be less than the specified value for each type and size of cable shown in the tables by an amount mom than 20% + 0.2mm, Complince shall be chocked by the test given in sub-clause 2J.2 of KD 605.

  1. Cable marking

The method of cable marking shal comply with clause 3 of Part 1 and the following additional requirements:

-

2.3.1


al marking


T

Example of mariuna

ELECTRIC CABLE 600/1000 V 600/1000 VAUX HD 604-6-E XYZ

he external surface of all cablet shall be legibly marked with the following element* of mailing:-

Eterrent

II Elecvic Cable

21 Voltage designation

31 Standard number

4) Manufacturer** identification

Б) Number of cores, type and nominal area of conductor |i) Copper conductor cables; 4 x50

(Note: 4 к ЕЮ Shall indicate a 4-core cable with Mm’ copper conductor*J

(it) Aluminium conductor cables: 4 x 50 AL

(Note: 4 x 60 AL shall indicate a 4-core cable whh 50mm* aluminium conductors.) (Hi) Copper conductor cable* with reduced neutral: 3 x 50/26

INote: 3 x 60/25 shall indicate a 4-core cable with three 50mm1 copper phase conductors and one 25mm1 copper neutral conductor.)

The marking of the Elements 1-4 shall be by embossing or indenting on the о ver sheath.

For cables with tabulated approximate overall diameters above 15mm, Elements 1, 2 and 3 shall appear, in any sequence that neither confuses nor conf&cu, on two or more primary lines along the »1* of the cable, approximately equally spaced around the circumference of the cable. Elements 4 and 5 shall appear on at least one line, which may bo one o* the primary lines, or a secondary line or lines. They may appear in any sequence that neither confuses nor conflicts, and need not all be on th* same ina.

For cable* with tabulated approximate overall cfiameters of 15mm or smaller, the Element* shall be disposed a* for cabfe* above 15mm except that the marking for Elements 1, 2 and 3 shall appear on one or more primary lines.

The letters and figures shall consist of upright block characters. The characters shall have a minimum height of 3mm.

The distance between the end of one element of marking and the beginning of the next identical element of marking shall rot be greater than 550mm, for Elements 1, 2 and 3, and not greater than 1100mm for Elements 4 and 6ч

CompEance shall be checked by visual examination and measurement.

  1. Identification of year of manufacture

A means of Identifying the year of manufacture of the cable shall be provided throughout the length of the cable, either internally or by marking on the surface of the cable.

If the kfentificobon ** Internal the distance between the end of one mark and the beginning of the next mark shall not be greater than 550 mtn. As an alternative internal marking, an identification thread may be used.If the identification is by marking on the surface it shall comply with the requremant* given tor Element* 4 and 5 In sub-clausa 2,3.1 In respect of maximum distance between marks.

  1. Пи mark of an AoorovaJ Organisation

If Iha mark of an Approval Organisation h used rt shall be provided throughout the length of the cable.

If the mark kt applied to the cable tt shall be on the surface in the form of the aymboKs) specified by the Approval Organisation, and shall comply with the requirements given for Elements 4 and 5 in sub-da use 2.3.1 In respect of maximum distance between marks.

As an attomative to the mark of the Approval Organisation, an Identification thread may bo incorporated into the cable, as specified by the Approval Organisation.

  1. Optional такта

The use of optional marking is permitted. Where such marking Is made h shall be throughout the length of the cable, and may bo on the external surface of the cable, or by means of a tape or thread within the cable, or by a combinatkm of these methods, И the additional marking is applied to the surface of the cable h shall not render illegible the marking specified in sub-clauses 2.3.1 - 2,3,3,

The additional marking, however made, shal be repeated at interval* nut exceeding 1100mm.

2.4 Additional test requirements

  1. Stmolifto for thickrwa» measurement

Make the measurements of thickness of insulation, extruded inner sheath and oversheath listed in the schedule of test requirements (Table 3k on a sample taken from one end of each drum length of cable selected for the test, having discarded any portion which may have suffered damage.

If any of the thicknesses measured does not comply with sub-dau*ts 4 3,2, 4.3 4 and 4,3.8 of this Part, then two Further samples shall be checked for the non-com pliant item*. If both samples meet the specified requirements the cable is deemed to comply, but if either does not meet the requirements, the cable is deemed not to comply.

  1. VoRaoe test

When the voltage test is carried out on the complete cable in accordance with sub-clause 3,2,1 qf HO 605, using a test voltage of 3.5kV for a duration of 6 minutes, the insulation shall not break down.

  1. Abrasion test

When a sample of th* completed cable їв tested in accordance with sub-dausa 2.4.Б of HD 605, the overaheath she* be deemed to be satisfactory provided that, foOowkig the test, examination of the sample without magnification reveals no crack* or split* hi the internd or external surface*.

2 4 4 Testi relating to fire conditions

2.4.4.1 Tert for fame propagation of ski ole cable

The finished cable shall comply with HD 405, Part 1 for tests under fire conditions when tested in accordance with that standard.

2 4.4.2 Tert for flame propagation of bunched cable

The finished cable shal comply with HD 605 clause 4.1.4 for test under fire conditions when tested in accordance with that standard.

2.4.4.3 Teat for smoke emission

When a sample of the complete cable is tested In accordance with HD 605 sub- clause 4.2,5 the values for the smoke generated, measured as standard absorbance IAJ shall be as follows:

(i) &nole core cables

Not to exceed 10

M Multi-core cables

Not to exceed the values in the tabla below:

Number of test pieces

A.

4 3

2 1

0.7 0,8 LO 1.5



2.4.4.4 T«t tar eorrorive and acid ои «ni&ston

When samples of bedding, oversheath, insulation, binders and filers are tested in accordance with HD 602 the recommended requirements shall be met.

2.4,5 Approval tests

2,4.5 J Ranos of approval for cables

Type approval for the complete range of cabin specified for this type te obtained by carrying out the following type tests on a cable having a tabulated diameter not exceeding 15mm and also on a cable having a tabulated diameter between 26mm and 40mm;

(a) Abrasion tert Isee 2,4.3)

One test should be carried out on each cable selectedtb) Corrosive sod gas test Uee 2Л.4.4)

At tbit it a test on a cable component end therefore generally independent of too or number of cores, only one test H necessary

  1. Test for flame propagation of bunched cable (see 2.4.4.21

For compliance with the requirements of HD 605 clausa 4,1.4 two possible methods of installation are stated, Й, in spaced and in touching formations. One tut of mufti-core cable having a tabulated diameter not exceeding 16mm should therefore be selected and tested in touching formation and one having a tabulated cSameter between 26mm and 40mm (provided that at least two samples of cable ere used) and tested in spaced formation for compliance with the requirements Of HD 605 clausa 4,1,4*

The test shall be considered satisfactory if, after burning has ceased, or the flamts extinguished io accordance with sub-clause 4 J .4 of HD 60&:

(il Penetration to the conductor has been achieved on all the front row of cables

  1. The cables have been wiped clean and the charred portion hat not reached a height exceeding 2.5m above the bottom edge of the upper burner, measured at the front, rear and where applicable between the cable assembly. Inspection shall be made of the internal surfaces of closely packed cable fristalations to ensure that the damage does not exceed the kmhs specified.

  1. Test for smoke emission (see 2.4.4.3)

The loss of light transmittance during the 3m cube test is not pro-rata to the number of cables. Therefore, although a range of cables may have identical components, two tests are required, in accordance with the following table, to obtain approval for either the complete or a limited range.

Range of approval Number of samples on test [MU>red tsao 2.4.4.3 and HD 605 stA-ctause 4.2.5)

Complete 4 and 2

16mm' and below 4 and 3

Ібпіт" and above 2 and 1

Ie) Compatibility (see Table 1)

Test to be carried out on each size of cable selected.

If) Oxygen index test (see 2.4.5.21

Test to be carried out on components from each of the selected cables

.Limited approval for cables of lOmm* and below can be obtained by carrying out all the test» given in hl to <e) on a cable having a tabulated diameter not exceeding 16mm, Limited approval for cables of 16mm’ and above can be obtained by carrying out ail ths tests on a cable having a tabulated diameter between 26mm and 40mm. For limited range of approval, however two tests need to bo carrwd out for smoke emission (see (d) above!.

Each of the tests should be carried out on the same cable except the corrosive acid gas test need only bo carried out on one of the selected cables.

2 4.5.2 Oxvoen index tost

During type tests the absolute oxygen index of samples of insulation, bedding and overshoe th. taken from the complete cable, shall be determined using the teat method given in HD 405.3 (Appendix BL The values obtained Shall be used to enable a nominal value together with sunable tolerances for sample test to be agreed between manufacturer and purchaser.

For sample tests the value of oxygen index of the bedding and oversbeath shall ba determined using the test method given in HO 405.3 (Appendix 8). The values obtained shall fall within the agreed tolerance on the nominal value.

2Л.6 Compatibility UM

When tested in accordance with clause 2.4.12.2 of HD 605. but using a temperature of (100 ± 2PC. the material shai comply with the values given in Table 21,

  1. Inautation resistance teatItxi HEPR core!

When tested in accordance with clause 3.3.1 of HD 605. the values measured shall not be less than the minimum specified value of К - 3 67 MD. Km measured at (90±2)*C.

  1. Oversheath resistance test

The oversheath resistance measurement shall be made between the armour and the water. The test voltage shall not be less than 500V d.c and shall be applied for sufficient time to reach steady measurement, but in no case (or less then one minute, by the method given in sub-clause 3X4 of HD 605,

The oversheath resistance shaE not be less than the minimum specified value of 1 M ohm per km when corrected to 20 °С.

  1. СаЫеі without matail.c covering

Not applicable.

  1. Cables with metallic covarino

    1. Coda designation

(Under consideration by TC20!

4 2 Rated voltage

0,6/1 OV,

4,3 Construction

  1. Conductor

The conductors shall be of the material and type detailed in tables 4 to 13 and shall comply with the requirements of HD 383.

Class 1 for solid conductors

Сіам 2 for stranded conductors.

Circular sectoral conductors are formed from four 90“ segments without any insulation between them. These shall comply with the material requirements of HD 383 and the resistance requirements of Table 15,

  1. кізіЯатіоп

The insulation shall be either cross-linked polyethylene IXLPE) or hard ethyleno propylene rubber IHEPRI complying with the requirements given in tabla 1, and sub-clause 2.4.4,4,

The insulation thickness shall comply with the value specified in tables 4 to 13.

  1. Aaaemfatv of cores

The cores of cables having two, three or four cores shall be toidup with a right-hand or right-and-left-hand alternating direction of lay. for multi-core auxiliary cables the direction of lay shall alternate for each successive layer. Auxiliary cables having up to and including seven cores may bo laid-up with a right-hand or left-hand or with a right-and-left-hand alternating direction of lay. Where necessary, synthetic filers, which may bo applied integrally with the bedding, shall be used to form a compact end reasonably circular свЫе.

  1. Inner covering ibeddino)

The bedding shall consist of an extruded layer of synthetic material compatible with the Operating temperature of the cable and shall comply with the requirements tor type TB2 in table 2t and sub-clausa 2.4,4.4*