NOTE In addition to any specific clauses relating to dangerous substances contained in this standard, there may be other requirements applicable to the products falling within its scope (e.g. transposed European legislation and national laws, regulations and administrative provisions). In order to meet the provisions of the EU Construction Products Directive, these requirements need also to be complied with, when and where they apply. An informative database of European and national provisions on dangerous substances is available at the Construction web site on EUROPA (CREATE, accessed through http://europa.eu.int/comm/enterprise/construction/internal/hygiene.htm).

Construction product: Electrical automatic control and delay device

Intended use(s): Components for use in gas extinguishing systems installed in buildings as a

complete operating system.

Table ZA.1 — Relevant Clauses

Essential characteristics

Clauses in this European Standard

Mandated levels and/or classes

Notes

Response delay (response time)

4.8

None


Operational reliability

4, 5, 6*,

*) where relevant

Performance parameters under fire conditions

4.3, 4.4, 4.5, 4.6

Durability

9

-



ZA.2 Procedure for the attestation of conformity of e.c.d.s

E.c.d.s for the intended use listed shall follow the system of attestation of conformity shown in Table ZA.2Table ZA.2 — Attestation of conformity system

Product

Intended use

Level(s) or class(es)

Attestation of nonform’ly PA/efAfn

Electrical automatic control and delay device

Fire safety


1

System 1: See CPD annex lll.2.(i), without audit testing of samples



The product certification body will certify the initial type testing of all relevant characteristics given in Table ZA.1 according to the provisions of 10.2 and for the initial inspection of the factory and of the factory production control, and for the continuous surveillance, assessment and approval of the factory production control, all characteristics shall be of interest to the approved body. The manufacturer shall operate a factory production control system in accordance with the provisions of 10.3.

ZA.3 CE marking

The CE marking symbol in the format specified in the Ell Directive 93/68/EEC shall be shown on the component together with the marking as specified in clause 7. In addition, the CE marking symbol shall appear on the packaging and/or on the accompanying commercial documents, together with the following information:

  • identification number of the certification body, and

  • the last two digits of the year in which the marking was affixed, and

  • the appropriate number of the ЕС-certificate of conformity, and

  • the number of this standard (EN 12094-1), and

  • the type of component (i.e. electrical automatic control device or electrical automatic control and delay device), and

  • the environmental class, and

  • the number of flooding zones,

  • per flooding zone: the type of flooding zone (e.g. CO2-high-pressure, CO2-low-pressure, inert gas, Halocarbon gas) and provided options,

  • the response delay activated condition (i.e. < 3 s),

  • the response delay triggering of outputs (i.e. < 1 s).

Figure ZA.1 gives an example of the information to be given on the commercial documents

.



0123

Any Co Ltd, P.O. Box 21, B1050
02

0123-CPD-001

EN 12094-1

Electrical automatic control and delay device

Environmental class A

6 flooding zones

Flooding zones 1 to 4:

CO2-low-pressure

Provided options:

  • Delay of extinguishing signal

  • Monitoring of status of components

  • Control of flooding time from 0 s to 300 s

  • Initiation of secondary flooding

  • Triggering of equipment outside the system

  • Control of extended discharge

Release of extinguishing media for selected flooding zones

Flooding zones 5 and 6:

CO2-high-pressure

Provided options:

  • Delay of extinguishing signal

Response delay activated condition maximum 3 s

Response delay triggering of outputs maximum 1 s

Figure ZA.1 — Example CE marking information

In addition to any specific information relating to dangerous substances shown above, the component should also be accompanied, when and where required and in the appropriate form, by documentation listing any other legislation on dangerous substances for which compliance is claimed, together with any information required by that legislation.

NOTE European legislation without national derogations need not be mentioned.

ZA.4 EC certificate and declaration of conformity

The manufacturer or his agent established in the EEA, shall prepare and retain a declaration of conformity, which authorises the affixing of the CE marking. This declaration shall include:

  • name and address of the manufacturer, or his authorised representative established in the EEA, and the place of production,

  • description of the component (type, identification, use), and a copy of the information accompanying the CE marking,

  • provisions to which the component conforms (i.e. annex ZA of this EN),

  • particular conditions applicable to the use of the component [if necessary],

  • name and address (or identification number) of the certification body,

  • name of, and position held by, the person empowered to sign the declaration on behalf of the manufacturer or of his authorised representative.

For characteristics where certification is required (system 1), the declaration shall contain a certificate of conformity with, in addition to the information above, the following information:

  • the name and address of the certification body,

  • the certificate number,

  • conditions and period of validity of the certificate, where applicable,

  • name of, and position held by, the person empowered to sign the certificate.

The declaration and certificate shall be presented in the language(s) of the Member State of use of the component.Bibliography

EN 45002, General criteria for the assessment of testing laboratories.

EN 45011, General requirements for bodies operating product certification systems (ISO/IEC Guide 65:1996).

EN ISO 9001:2000, Quality management systems - Requirements (ISO 9001:2000).

EN ISO/IEC 17025, General requirements for the competence of testing and calibration laboratories.

EU Directive 93/68/EEC, COUNCIL DIRECTIVE 93/68/EEC of 22 July 1993 amending Directives 87/404/EEC (simple pressure vessels), 88/378/EEC (safety of toys), 89/106/EEC (construction products), 89/336/EEC (electromagnetic compatibility), 89/392/EEC (machinery), 89/686/EEC (personal protective equipment), 90/384/EEC (non-automatic weighing instruments), 90/385/EEC (active implantable medicinal devices), 90/396/EEC (appliances burning gaseous fuels), 91/263/EEC (telecommunications terminal equipment), 92/42/EEC (new hot-water boilers fired with liquid or gaseous fuels) and 73/23/EEC (electrical equipment designed for use within certain voltage limits).

1 under preparation