unprotected conductor wires, conductor bars, and slip-ring assemblies shall be equipped with insulators with a minimum creepage distance of 60 mm;
enclosed conductor wires, insulated multipole conductor bars and insulated individual conductor bars shall have a minimum creepage distance of 30 mm.
The manufacturer's recommendations shall be followed regarding special measures to prevent a gradual reduction in the insulation values due to unfavourable ambient conditions (for example deposits of conductive dust, chemical attack).
7 Conductor system sectioning
Where conductor wires or conductor bars are arranged so that they can be divided into isolated sections, suitable design measures shall be employed to prevent the energization of adjacent sections by the current collectors themselves.
8 Construction and installation of conductor wire, conductor bar systems and slip-ring assemblies
Conductor wires, conductor bars and slip-ring assemblies in power circuits shall be grouped separately from those in control circuits.
Conductor wires, conductor bars and slip-ring assemblies shall be capable of withstanding, without damage, the mechanical forces and thermal effects of short-circuit currents.
Removable covers for conductor wire and conductor bar systems laid underground or underfloor shall be so designed that they cannot be opened by one person without the aid of a tool.
Where conductor bars are installed in a common metal enclosure, the individual sections of the enclosure shall be bonded together and connected to a protective bonding conductor at several points depending upon their length. Metal covers of conductor bars laid underground or underfloor shall also be bonded together and connected to a protective bonding conductor.
NOTE For the protective bonding together of covers or cover plates of metal enclosures or underfloor ducts, the metal hinges are considered sufficient to ensure continuity.
Underground and underfloor conductor bar ducts shall have drainage facilities.
Wiring practices
Connections and routing
General requirements
All connections, especially those of the protective bonding circuit, shall be secured against accidental loosening.
The means of connection shall be suitable for the cross-sectional areas and nature of the conductors being terminated.
The connection of two or more conductors to one terminal is permitted only in those cases where the terminal is designed for that purpose. However, only one protective conductor shall be connected to one terminal connecting point.
Soldered connections shall only be permitted where terminals are provided that are suitable for soldering.
Terminals on terminal blocks shall be plainly marked or labelled to correspond with markings on the diagrams.
Where an incorrect electrical connection (for example, arising from replacement of devices) can be a source of risk and it is not practicable to reduce the possibility of incorrect connection by design measures, the conductors and/or terminations shall be identified in accordance with 13.2.1.
The installation of flexible conduits and cables shall be such that liquids shall drain away from the fittings.
Means of retaining conductor strands shall be provided when terminating conductors at devices or terminals that are not equipped with this facility. Solder shall not be used for that purpose.
Shielded conductors shall be so terminated as to prevent fraying of strands and to permit easy disconnection.
Identification tags shall be legible, permanent, and appropriate for the physical environment.
Terminal blocks shall be mounted and wired so that the internal and external wiring does not cross over the terminals (see IEC 60947-7-1).
Conductor and cable runs
Conductors and cables shall be run from terminal to terminal without splices or joints. Connections using plug/socket combinations with suitable protection against accidental disconnection are not considered to be joints for the purpose of this Subclause.
Exception: Where it is impracticable to provide terminals in a junction box (for example on mobile machines, on machines having long flexible cables; cable connections exceeding a length which is not practical to be supplied by the cable manufacturer on one cable drum; repair of cable due to mechanical stresses during installation and operation), splices or joints may be used.
Where it is necessary to connect and disconnect cables and cable assemblies, a sufficient extra length shall be provided for that purpose.
The terminations of cables shall be adequately supported to prevent mechanical stresses at the terminations of the conductors.
Wherever practicable, the protective conductor shall be placed close to the associated live conductors in order to decrease the impedance of the loop.
Conductors of different circuits
Conductors of different circuits may be laid side by side, may occupy the same duct (for example conduit, cable trunking system), or may be in the same multiconductor cable provided that the arrangement does not impair the proper functioning of the respective circuits. Where those circuits operate at different voltages, the conductors shall be separated by suitable barriers or shall be insulated for the highest voltage to which any conductor within the same duct can be subjected, for example line to line voltage for unearthed systems and phase to earth voltage for earthed systems.
Connection between pick-up and pick-up converter of an inductive power supply system
The cable between the pick-up and the pick-up converter as specified by the manufacturer of the inductive power supply shall be:
as short as practicable;
adequately protected against mechanical damage.
NOTE The output of the pick-up can be a current source, therefore damage to the cable can result in a high voltage hazard.
Identification of conductors
General requirements
Each conductor shall be identifiable at each termination in accordance with the technical documentation (see Clause 17).
It is recommended (for example to facilitate maintenance) that conductors be identified by number, alphanumeric, colour (either solid or with one or more stripes), or a combination of colour and numbers or alphanumeric. When numbers are used, they shall be Arabic; letters shall be Roman (either upper or lower case).
NOTE Annex В can be used for agreement between supplier and user regarding a preferred method of identification.
Identification of the protective conductor
The protective conductor shall be readily distinguishable by shape, location, marking, or colour. When identification is by colour alone, the bicolour combination GREEN-AND-YELLOW shall be used throughout the length of the conductor. This colour identification is strictly reserved for the protective conductor.
For insulated conductors, the bicolour combination GREEN-AND-YELLOW shall be such that on any 15 mm length, one of the colours covers at least 30 % and not more than 70 % of the surface of the conductor, the other colour covering the remainder of the surface.
Where the protective conductor can be easily identified by its shape, position, or construction (for example a braided conductor, uninsulated stranded conductor), or where the insulated conductor is not readily accessible, colour coding throughout its length is not necessary but the ends or accessible locations shall be clearly identified by the graphical symbol IEC 60417-5019 (DB:2002-10) or by the bicolour combination GREEN-AND-YELLOW.
Identification of the neutral conductor
Where a circuit includes a neutral conductor that is identified by colour alone, the colour used for this conductor shall be BLUE. In order to avoid confusion with other colours, it is recommended that an unsaturated blue be used, called here “light blue” (see 3.2.2 of IEC 60446). Where the selected colour is the sole identification of the neutral conductor, that colour shall not be used for identifying any other conductor where confusion is possible.
Where identification by colour is used, bare conductors used as neutral conductors shall be either coloured by a stripe, 15 mm to 100 mm wide in each compartment or unit and at each accessible location, or coloured throughout their length.
Identification by colour
Where colour-coding is used for identification of conductors (other than the protective conductor (see 13.2.2) and the neutral conductor (see 13.2.3)), the following colours may be used:
BLACK, BROWN, RED, ORANGE, YELLOW, GREEN, BLUE (including LIGHT BLUE), VIOLET, GREY, WHITE, PINK, TURQUOISE.
NOTE This list of colours is derived from IEC 60757.
It is recommended that, where colour is used for identification, the colour be used throughout the length of the conductor either by the colour of the insulation or by colour markers at regular intervals and at the ends or accessible location.
For safety reasons, the colour GREEN or the colour YELLOW should not be used where there is a possibility of confusion with the bicolour combination GREEN-AND-YELLOW (see 13.2.2).
Colour identification using combinations of those colours listed above may be used provided there can be no confusion and that GREEN or YELLOW is not used except in the bicolour combination GREEN-AND-YELLOW.
Where colour-coding is used for identification of conductors, it is recommended that they be colour-coded as follows:
a
BLACK:
RED:
.c. and d.c. power circuits;a.c. control circuits;
BLUE: d.c. control circuits;
ORANGE: excepted circuits in accordance with 5.3.5.
Exceptions: to the above are permitted where:
insulation is used that is not available in the colours recommended; or
multiconductor cable is used, but not the bicolour combination GREEN-AND-YELLOW.
Wiring inside enclosures
Conductors inside enclosures shall be supported where necessary to keep them in place. Non- metallic ducts shall be permitted only when they are made with a flame-retardant insulating material (see the IEC 60332 series).
It is recommended that electrical equipment mounted inside enclosures be designed and constructed in such a way as to permit modification of the wiring from the front of the enclosure (see also 11.2.1). Where that is not practicable and control devices are connected from the rear of the enclosure, access doors or swingout panels shall be provided.
Connections to devices mounted on doors or to other movable parts shall be made using flexible conductors in accordance with 12.2 and 12.6 to allow for the frequent movement of the part. The conductors shall be anchored to the fixed part and to the movable part independently of the electrical connection (see also 8.2.3 and 11.2.1).
Conductors and cables that do not run in ducts shall be adequately supported.
Terminal blocks or plug/socket combinations shall be used for control wiring that extends beyond the enclosure. For plug/socket combinations, see also 13.4.5 and 13.4.6.
Power cables and cables of measuring circuits may be directly connected to the terminals of the devices for which the connections were intended.
Wiring outside enclosures
General requirements
The means of introduction of cables or ducts with their individual glands, bushings, etc., into an enclosure shall ensure that the degree of protection is not reduced (see 11.3).
External ducts
Conductors and their connections external to the electrical equipment enclosure(s) shall be enclosed in suitable ducts (i.e. conduit or cable trunking systems) as described in 13.5 except for suitably protected cables that may be installed without ducts and with or without the use of open cable trays or cable support means. Where devices such as position switches or proximity switches are supplied with a dedicated cable, their cable need not be enclosed in a duct when the cable is suitable for the purpose, sufficiently short, and so located or protected, that the risk of damage is minimized.
Fittings used with ducts or multiconductor cable shall be suitable for the physical environment.
Flexible conduit or flexible multiconductor cable shall be used where it is necessary to employ flexible connections to pendant push-button stations. The weight of the pendant stations shall be supported by means other than the flexible conduit or the flexible multiconductor cable, except where the conduit or cable is specifically designed for that purpose.
Connection to moving elements of the machine
Connections to frequently moving parts shall be made using conductors in accordance with 12.2 and 12.6. Flexible cable and flexible conduit shall be so installed as to avoid excessive flexing and straining, particularly at the fittings.
Cables subject to movement shall be supported in such a way that there is no mechanical strain on the connection points nor any sharp flexing. When this is achieved by the provision of a loop, it shall have sufficient length to provide for a bending radius of the cable of at least 10 times the diameter of the cable.
Flexible cables of machines shall be so installed or protected as to minimize the possibility of external damage due to factors that include the following cable use or potential abuse:
being run over by the machine itself;
being run over by vehicles or other machines;
coming into contact with the machine structure during movements;
running in and out of cable baskets, or on or off cable drums;
acceleration forces and wind forces on festoon systems or suspended cables;
excessive rubbing by cable collector;
exposure to excessive radiated heat.
The cable sheath shall be resistant to the normal wear that can be expected from movement and to the effects of environmental contaminants (for example oil, water, coolants, dust).
Where cables subject to movement are close to moving parts, precautions shall be taken to maintain a space of at least 25 mm between the moving parts and the cables. Where that distance is not practicable, fixed barriers shall be provided between the cables and the moving parts.
The cable handling system shall be so designed that lateral cable angles do not exceed 5°, avoiding torsion in the cable when:
being wound on and off cable drums; and
approaching and leaving cable guidance devices.
Measures shall be taken to ensure that at least two turns of flexible cables always remain on a drum.
Devices serving to guide and carry a flexible cable shall be so designed that the inner bending radius at all points where the cable is bent is not less than the values given in Table 8, unless otherwise agreed with the cable manufacturer, taking into account the permissible tension and the expected fatigue life.
Table 8 - Minimum permitted bending radii for the forced guiding of flexible cables
Application |
Cable diameter or thickness of flat cable (d) mm |
||
d< 8 |
8 < d< 20 |
d > 20 |
|
Cable drums |
6 d |
6 d |
8 d |
Guide rollers |
6 d |
8 d |
8 d |
Festoon systems |
6 d |
6 d |
8 d |
All others |
6 d |
6 d |
8 d |
The straight section between two bends shall be at least 20 times the diameter of the cable.
Where flexible conduit is adjacent to moving parts, the construction and supporting means shall prevent damage to the flexible conduit under all conditions of operation.
Flexible conduit shall not be used for connections subject to rapid or frequent movements except when specifically designed for that purpose.
Interconnection of devices on the machine
Where several machine-mounted switching devices (for example position sensors, pushbuttons) are connected in series or in parallel, it is recommended that the connections between those devices be made through terminals forming intermediate test points. Such terminals shall be conveniently placed, adequately protected, and shown on the relevant diagrams.
Plug/socket combinations
Where plug/socket combinations are provided, they shall fulfil one or more of the following requirements as applicable:
Exception: The following requirements do not apply to components or devices inside an enclosure, terminated by fixed plug/socket combinations (no flexible cable), or components connected to a bus system by a plug/socket combination.
When installed correctly in accordance with f), plug/socket combinations shall be of such a type as to prevent unintentional contact with live parts at any time, including during insertion or removal of the connectors. The degree of protection shall be at least IPXXB. PELV circuits are excepted from this requirement.
Have a first make last break protective bonding contact (earthing contact) (see also 6.3, 8.2.4) if used in TN- or TT-systems.
Plug/socket combinations intended to be connected or disconnected during load conditions shall have sufficient load-breaking capacity. Where the plug/socket combination is rated at 30 A, or greater, it shall be interlocked with a switching device so that the connection and disconnection is possible only when the switching device is in the OFF position.
Plug/socket combinations that are rated at more than 16 A shall have a retaining means to prevent unintended or accidental disconnection.
Where an unintended or accidental disconnection of plug/socket combinations can cause a hazardous situation, they shall have a retaining means.
The installation of plug/socket combinations shall fulfil the following requirements as applicable:
The component which remains live after disconnection shall have a degree of protection of at least IP2X or IPXXB, taking into account the required clearance and creepage distances. PELV circuits are excepted from this requirement.
Metallic housings of plug/socket combinations shall be connected to the protective bonding circuit. PELV circuits are excepted from this requirement.
Plug/socket combinations intended to carry power loads but not to be disconnected during load conditions shall have a retaining means to prevent unintended or accidental disconnection and shall be clearly marked that they are not intended to be disconnected under load.
Where more than one plug/socket combination is provided in the same electrical equipment, the associated combinations shall be clearly identifiable. It is recommended that mechanical coding be used to prevent incorrect insertion.
Plug/socket combinations used in control circuits shall fulfil the applicable requirements of IEC 61984. Exception: see item k).
Plug/socket combinations intended for household and similar general purposes shall not be used for control circuits. In plug/socket combinations in accordance with IEC 60309-1, only those contacts shall be used for control circuits which are intended for those purposes.
Exception: The requirements of item k) do not apply to control functions using high frequency signals on the power supply.
Dismantling for shipment
Where it is necessary that wiring be disconnected for shipment, terminals or plug/socket combinations shall be provided at the sectional points. Such terminals shall be suitably enclosed and plug/socket combinations shall be protected from the physical environment during transportation and storage.
Additional conductors
Consideration should be given to providing additional conductors for maintenance or repair. When spare conductors are provided, they shall be connected to spare terminals or isolated in such a manner as to prevent contact with live parts.
Ducts, connection boxes and other boxes
General requirements
Ducts shall provide a degree of protection suitable for the application (see IEC 60529).
All sharp edges, flash, burrs, rough surfaces, or threads with which the insulation of the conductors can come in contact shall be removed from ducts and fittings. Where necessary, additional protection consisting of a flame-retardant, oil-resistant insulating material shall be provided to protect conductor insulation.
Drain holes of 6 mm diameter are permitted in cable trunking systems, connection boxes, and other boxes used for wiring purposes that can be subject to accumulations of oil or moisture.
In order to prevent confusion of conduits with oil, air, or water piping, it is recommended that the conduits be either physically separated or suitably identified.
Ducts and cable trays shall be rigidly supported and positioned at a sufficient distance from moving parts and in such a manner so as to minimize the possibility of damage or wear. In areas where human passage is required, the ducts and cable trays shall be mounted at least 2 m above the working surface.
Ducts shall be provided only for mechanical protection (see 8.2.3 for requirements for connection to the protective bonding circuit).
Cable trays that are partially covered should not be considered to be ducts or cable trunking systems (see 13.5.6), and the cables used shall be of a type suitable for installation with or without the use of open cable trays or cable support means.
Percentage fill of ducts
Consideration of the percentage fill of ducts should be based on the straightness and length of the duct and the flexibility of the conductors. It is recommended that the dimensions and arrangement of the ducts be such as to facilitate the insertion of the conductors and cables.