TABLE УШ
(concluded I
1 |
2 |
3 |
4 |
6 |
|
7 |
В |
6 |
to |
|
ЛМПІМІ сгом ■ ЄСГЙ»ЄІ •гм of GOhdllClort |
Clew of CCKKhjCTQT HD ЗВЭ |
IntuktdM tfucfenen Specified vehie |
TftkekfWM inner rteetn Specified vekie |
Нопмпай (Mmeter of the wrei of the braided аегмл |
Nominal его to ttctkmtl HU of the copper braid |
Maximum •lectncai reaiaunce of the copper brrtet 20eC |
ThlchneM of Kheeth Speeded velue |
ТЫскпм* of overehMth Speeded vafcM |
McnwwH meen ovarell die meter |
|
mm* |
|
nW |
mm |
Heel mm |
copper mm |
mmT |
ohntfkm |
mm |
mm |
mm |
4 ж В + > x 10 |
СП СП |
ОЛ 07 |
0.0 |
0.3 |
0,25 |
6 |
3.06 |
4 |
2.0 |
22 Б |
4ж 10 + 1 x 16 |
Б Б |
0.7 0.7 |
0.Э |
0,3 |
0 26 |
10 |
1.33 |
A |
2.0 |
26,0 |
41 16 t 1 к 26 |
Б Б |
0.7 О. В |
0.6 |
0.3 |
0,3 |
16 |
1.1Б |
|
|
29.0 |
4 х 2В + 1 к ЗБ |
Б Б |
OB 0.9 |
0.3 |
0.3 |
0 3 |
16 |
1.16 |
|
2.0 |
34,6 |
4х ЗБ * 1 х ЕЮ |
Б Б |
0.0 VO |
1.0 |
0.4 |
0.4 |
16 |
1.15 |
• |
Г0 |
40.0 |
APPENDIX
GUIDE TO USE
Scope
This "Guide to use" is applicable to cables according to Sector D of Pan 4 of HD 604.
Object
The object of this ’Guide to use" is to provide recommendations for the cables specified in Section D at Part 4 of HD 604..
ReeommandatHMis for storage, transport and tenJinfl
3-і РеНудгу
When delivered on a drum, the core diameter of the drum shall not be less than:
• 14 times the outer diameter of the cable for unarmoured, braided and double screened cables.
■ 16 times the outer diameter of the cable for cables with behcallv applied armour/PE conductor.
The distance between the outer cable lever and the head of the drum flange shall be sufficiently high to avoid damages to the cable.
Short cable lengths may be coiled to rings and transported and stored horizontally. The bending radii shal not be less than the above mentioned values.
Cable end sealing
The cable ends shall be sealed water-proof during transport, storage and laying.
Transport
For the transport of filled up cable reels, only suitable carriers shell be used.
Cables stored at temperatures which fal below those recommended for installation, shall not be subject to any mechanical stress including shocks, impact bendrig and torsion.
It shal be prevented that drum flanges come in touch with the cable Of another drum.
For loading and unloading of cable drums, suitable String and hoisting equipment shall be used; never drop a drum on the ground or on a buffer.
See also relevant figures.
Filled up cable drums shall be rolled only short distances over plain solid ground in the direction indicated.
The cable end shall be tightened.
Lowest temperature for cable laying and installation
Sheath of PVC ie liable to cracking at low temperatures in case of blows to the cable or excessive bending. Care should therefore be taken during transport, laying and installation. The lowest temperature for cables during installation is 0°C under normal conditions of care.
This temperature is valid for the cable itself and not for the environment- If possible, the temperature of the cable shall bo raised co at least +10°C before laying, e.g. in a heated building, to facilitate handling and to reduce the nsk of damage.
Puling loads
It is assumed chat the cable route is well designed for the laying procedure with well established curves and a sufficient number of cable rollers. Special attention shall be paid to the required minimum bending radii late Sub-clause 3.6b The puking forces shall be permanently supervised during the pull- in procedure.
The pul к ng force shall be evenly divided over the main conductors.
The maximum pulling force IP} shall be calculated as follows:
P - S о where P is in N v is maximum tensile stress in conductor, v>2 50 N/nwi3 for copper conductor 30 N/rnm1 for aluminium conductors
S is total cross-sectional area in mm’ of the main conductors (ignoring screens, concentric conductors end auxiliary conductors).
In case of using a cable stocking, the total pulling force shall not exceed 1000N.
ЗЛ Bendina radius
During instaNation, the Internal bending radius of the cable shall not be smaller than 10Dr where 0 is the overall diameter of the cable. This value may be reduced to 8D In case of a careful, one single time bending of the cable end.
Bending nearby the temperature limits given in sub-clause 3 4 should be carried out extra carefully.
Armoured single core cables
Single core cables with armour/PE conductor made up partly of steel wires are for direct current only.
Current rating
For the calculation of the continuous current rating, see IEC 287«
STORAGE
Never lay
Keep the drum standing tipright, using wedges in the heels of the flanges
Drues say only be piled flange on flange. Lower layer to be secured over full drum width.
then flat
TRANSPORT
Roll the drum in the direction withwich it turned during cable reeling
Drums nay be lifted either by crane or fork-lift truck
DE-REELING
De-reel in this way
Never de-reel in this way
FE-WXHPINE
Recommended
Not recommended
SECTION E: CABLES WITH COPPER OR ALUMINIUM CONDUCTORS.
AND WIRE QH STRIP ARMOUR
CONTENTS
Pace
1, Scope 4-E-2
Additional general requirements
Identification of cores 4'E-2
Thickness of inner sheath 4-E’2
Cable marking 4-E’2
Additional test requirements 4-E-4
(Not applicable) 4-E6
Cables with metallic covering
Cod* designation 4-E-8
Rated voltage 4-Е-6
Construction 4-Е-6
Tests 4-E8
Tables: 1 -26 4-E-9
Appendix: Guide to use 4-E-37
■ d 4 л . f •■Лили^лл
REFERENCES
References ere made, in this Section E of Pari 4 of HD 604, to other Pans of cNs HD and to other Harmonisation Documents and International Standards as t clows:
HD 383 Conductor* of insulated cables lEndcrging I EC 228 and 22BA)
HD 405 Tests on electric cables under fire conditions
HD 505 Common test methods for insulating and sheathing materials of electric cables
HD 605 Becuic cables : Additional test methods
ІЄС 287 Calculation of th* continuous current ratine of cables 1100% load factor)
In all cases reference to another HD or International Standard implies the latest edition of that document.
SECTION E
1. Scope
This section specifies requirements for end dimensions of single core and multi-core XLPE or HEPR insulated and PVC sheathed cables having reduced fire propagation performance.
The cables considered are intended for use where the combination of ambient temperature and temperature rise due to loading current results in a conductor temperature not exceeding 90° C. The maximum temperature tgr short-circuit conditions is 250 °С.
This section covers the following classes of саЫе:
Пі 2j 3 and 4 core cables having copper conductor and steel wire armour
Ik) 3 and 4 core cables having solid aluminium conductors and aluminium wire or strip armour
(hi) Single core cables having copper conductor and aluminium wire armour
(rvj Single core cables having solid sectoral or stranded aluminium conductors and aluminium wire or strip armour.
tv| Multicore auxiliary cables having 2 up to 4B cores with copper conductors and steel wire armour
2 Additional gen*ml requirements
The folowing general requirements shall be read in conjunction with those given in Pan t
1 Identification of cores
The cores of all cables shall be identified either by numbers or by colours in accordance with the following sequence:
Number of cores Identification
R
One
Two
Three Four
ed or blackRed, black
Red. yellow, Ыие
Red. yellow, Ыие, Ыаск
Auxiliary cables 1, 2, 3, 4, 5, 6r 7 and upwards
The height of individual numbers shall be not less than 1.5mm and the interval between adjacent numbers shell not exceed 70mm.
ThictaiM» of inner sheath
Th* minimum thickness of extruded inner covering shaN not be less than ths specified value for each type and size of cable shown in the tables by an amount mor* than 15% + 0.1 mm. Compliance shall be checked by the test given in clause 2J.2 of HD 60S.
Cable marking
Th* method of cable marking shall comply with clause 3 of Part 1 and the following additional requirements:-External marking
The external surface of al cables shall be legibly marked with the following element* at marking:^
E
Elements
xample of marking11 Electric cable 2| Voltage designation
Э) Standard number
4} Manufacturer's
►dentrhcatior
ELECTRIC CABLE 600/1000 V 600/1 000 AUX HD 604-4-E
XYZ
SI Number of cores, type and nominal area of conductor
10 Copper conductor cables: 1 x40Q
(Note: 1x400 shall indicate я single-core cable with 400mm1 copper conductor) lid Aluminium conductor cables: 1x400AL
(Note: 1x400 AL shal indicate a single-core cable with 400mm* aluminium conductor)
(Ш) Copper conductor cables with reduced neutral: 3 x Б0/25
(Note: 3 x 60/25 shall indicate a 4-е ore cable with three 50mm1 copper phase conductors and one 25m«nT copper neutral conductor).
The marking of the Elements 1-4 shall be by embossing or indenting on the о ver shea th.
For cables with tabulated approximate overaR diameters above 15mm, Elements 1, 2 and 3 shall appear, in any sequence that neither confuses nor eonfkets, on two or more primary lines along the axis of the cable, approximately equally spaced around the circumference of the cable. Elements 4 and 5 Shall appear on at least one line, which may be one of the primary Enas, or a secondary hne or lines. They may appear in any sequence that neither confuses nor conflicts, and need not ail be on the same fate
For cables with tabulated approximate overall diameters of 15mm or smiler, the Elements shall be disposed as for cables above 15mm except that the marking for Elements 1, 2 and 3 shaN appear on one or more primary lines
The letters and figures shall consist of upright block characters. The characters shall have a minimum height of 3mm,
The distance between the end of one element of marking and the beginning of the next identical element of marking snail not be greater than 550mm, for Elements 1,2 and 3, and not greater than 1100mm for Elements 4 and 5.
Compliance shall be checked by visual examination and measurement
ktemXicabon <rf уваг of manufacture
A means of identifying the year of manufacture of the cable shall be provided throughout the length of the cable, either internally or by marking on (he surface of the CaWe
If the identification is internal the distance between the end of the mark and the beginning of the next mark shall not be greater than 550mm. As an alternative internal marking, an identification thread may be used.H the identification is by marking on ths surface it shall comply with the requirements given for Elements 4 and 6 in sub-dause 2.3.1 in respect of maximum distance between marks.
Ths mark of an Approval Organisation
If the mark of an Approval Organisation is used it shal be provided throughout the length of the cable,
H the mark is applied to the саЫе h shall be on the surface in the form of the symbols) specified by the Approval Organisation, and shall comply with the requirements given for Elements 4 and 5 in tub-clausa 2.3.1 in respect of maximum distance between marks.
As an alternative to the mark of the Approval Organisation, an identification thread may be Incorporated into the caWe, as specified by the Approval Organisation,
2-3Л Optional mefkino
The use of optional marking is permitted. Where such marking is made 4 shall be throughout the length of the cable, and may be on the external surface of the cable, or by means of a tape or thread wrth*n the cable, or by a combination of these methods- 11 the additional marking is applied to the surface of the cable it shall not render illegible the marking specified in sub-clause 2,3,1 * 2 3 3.
The additional marking, however made, shall be repeated at intervals not exceeding 1100mm,
Additional tost reputremant*
Sampkno for thickness measurement
Make the measurements of thickness of insulation, extruded inner sheath and oversheath listed in the schedule of test requirements {Table 31 on a sample taken from one end of each drum length of cable selected for the test having discarded any portion which may have suffered damage.
If any of the thicknesses measured does not comely with sub-clause 4 3.2, 4,3,4 and 436 of this part then two further samples shall be chocked for the non-compliant items. If both samples meet the specified requirements the cable is deemed to comply, but if either does not meet the requirements, the cable is deemed not to comply
Vottaae tests
Test on ovsrshwtf of single core catXtf
When the oversheath is tested, at an applied voltage gf 3kV sc rm* oi SkV de for one minute, in accordance with sub-clause 3.2.3.1 of HD 606 the oversheath Sha I not break down-
Test on complete cable
When the voltage test is earned out in accordance with sub-clause 3.2,1 of HD 606, using a test voltage of 3,5kV a.c. for a duration of 5 minutes, the insulation shall not break down.
4.3 tosuiailon resistance іиі (on HEPR core)
When tested »n accordance with sub^lsuse 3-3.1 of HD 605 the values measured shell not be less than the minimum specified value of К ■ 3-67 MOkm measured at 90°C.
Qversheaih resistance test
The over sheath resistance measurement shall be made between the armour and the water. The test voltage shall nut be less than 500V de and shal be applied for sufficient time to reach steady measurement, but in no case tor less than 1 minute, by the method given in sub* clause 3*3.4 of HO 605.
The Oversheath resistance shall not be less than the minimum specified value of 1 M ohm per km when corrected to 20°C.
Compatibility test
When tested in accordance with sub-clausa 2,4.12.2 erf HD 605, but using a temperature of 4100* 2PC, the material shall comply with the values given in table 26.
2*4*6 Approval tests related to f<e condition*
Range of approval for single core cables
Type approval for the complete range of single-core cable a specified for chi» type or limited range of sites is obtained by carrying out the tests given in HD 405*1 and sub-clause 4.1,1 of HD 605 on one cable size*
The cable size selected for test for the range for which approval is sought she! be that which has the greatest re сю of sectional area in mm* of non-meta lie material to that of al (he metallic components* Tests carried out in cables having aluminium conductors will also cover cables having copper conductors but not vica versa. Tests carried out on aluminium strip armour will also gain approval for wire armour and vice versa.