• exposure conditions: the side(s) to be exposed e.g. ducts (inside/outside);

  • dimensions of the component: height, width;

  • boundary and support conditions: restraint, free movement, distance between supports;

  • variation of constructional details;

  • envisaged class(es): i.e. combinations of performance criteria and times.

  1. B> Taking into account the direct field of application of test results as specified in the relevant test method and/or the extended application results, the number of tests, standard temperature/time tests and other exposures, and the specimen to be tested shall be deduced.

  2. Standard fire tests shall be carried out and for each test the times shall be determined, in elapsed minutes, for which the test specimen continues to satisfy the different aspects of the performance criteria.

  3. If more than one test has to be carried out because of the envisaged field of application, the lowest result shall determine the classification for the entire field of application. As the classification is linked to the field of application, results of individual tests may lead to higher ranking for a limited field of application.

  4. Classification reports shall be prepared as shown in Annex A. A report may be issued for any combination of performance parameters and times that E)are covered by results of tests and/or by extended application results <51.

  1. General rules for deducing the number of fire resistance tests

No test shall be duplicated for aspects of repeatability and a single test, unless required otherwise by this European Standard, allows the classification of all components in the field of direct application.

If, however, a wider field of application is envisaged, all relevant aspects may not be covered by a single test and additional tests are then required. Also, the influence of different boundary conditions may require evaluation of additional test specimens.

Asymmetrical components may have a different performance depending on the side from which they are tested. In such cases the fire resistance classification shall be based on fire exposure from the side demonstrated as giving the lower fire resistance time. This requires that a test on each side is carried out, except where provided for in the direct field of application.

An asymmetrical component tested from one side only shall be classified for fire attack from that side only.

The number of tests required may further depend on:

  • required classifications;

  • combination of performance criteria envisaged;

  • need to apply more than one thermal attack.

E) deleted text

Products/elements are supplied in a wide variety of sizes, shapes and materials including finishes to satisfy the requirements of the market. It is impractical to test every variation of shape, size or material for each product.

The extent to which a tested product/element may or may not be changed under the field of direct application is given in rules or guidelines which limit the permitted variation away from the test specimen without further evaluation or calculation. The field of direct application clause in each specific test method relates to the common forms of construction for which experience of testing has provided the knowledge that such variations can be safely accepted.

15) The extent to which a tested product or element may be changed under the field of extended application is given in rules in the relevant extended application standards. <51

— Dimensions:

The test specimen shall normally be full size. When the specimen cannot be tested full size, the specimen size shall be in accordance with the specification of the relevant test method. For the application of test results for products/elements with dimensions other than those tested, see the field of direct application clause within E) the appropriate test standard and the field of extended application in the appropriate extended application standard <51.

— Variation of constructional details:

For the application of test results for constructional details other than those tested, see the field of direct application clause within Ei) the appropriate test standard and the field of extended application in the appropriate extended application standard <51.

Different variations of constructional details shall not be included in a single test specimen, unless it can be shown that they will not interfere with the performance of each other.

7.1.3 I5> Field of application

Field of application can be defined using test reports and other relevant data in accordance with the procedures specified in prEN 15725, which e.g. describes the role of extended application in the classification process.

7.2 Classification

  1. General

  2. and 7.2.3 indicate the relevant performance criteria and classes for each product/element.

  3. Ventilation ducts

  1. E) Test method and field of application rules <51

The test method for ducts shall be as given in EN 1366-1. The method is applicable to vertical and horizontal four sided ducts with fire exposure from the outside and/or inside, duct A and/or duct B, as a function of the required classification. I5> Extended application shall be carried out as described in the relevant extended application standard and in prEN 15725. <51

^deleted text^J The applicability of results to two or three sided ducts or larger cross section ducts is the subject of extended application.

  1. Tests to be carried out

The design of the test specimen and the number of tests to be carried out shall be derived from a comparison between the envisaged field of application of the classification and the field of application of test results as defined in this European Standard.

The test method provides information on the following:

  • test specimen/construction;

  • field of direct application of test results;

  • guidance on test specimen design.

Aspects influencing the number of tests to be carried out include, for example:

  • range of exposure conditions to be covered;

  • dimensional variations and orientation;

  • pressure conditions.

  1. Performance criteria

— Integrity

E> Integrity shall be assessed as the time at which:

  1. integrity failure for the duct occurs outside the furnace, using the criteria in 5.1.2;

  2. volume flow rate measured in duct A exceeds 15 m3/(m2 h) related to 20 °С and related to the internal surface area of the duct inside the furnace as specified in EN 1366-1.

Table 1 gives a summary of the appropriate integrity evaluation.

Table 1 — Integrity evaluation

Duct

Within furnace

Outside furnace

Duct A (Fire outside duct) (o->i)

Volume flow rate

Volume flow rate

Cotton pad

Openings

Flaming

Duct В (Fire inside duct) (i -* o)

Cotton pad Openings Flaming



  • Insulation

The performance level used to define insulation shall be the mean temperature rise on the unexposed face, limited to 140 °С above the initial mean temperature, with the maximum temperature rise at any point limited to 180 °С above the initial mean temperature.

  • Smoke leakage (if necessary)

Failure of this criterion shall occur if the flow rate in a duct, exposed to fire outside the duct, during the test exceeds 10 m3/(m2 x h) related to 20 °С.

7.2.2.4 Classes

The following classes are defined:

El 15 20 30 45 60 90 120 180 240

E 30 60

The classification shall indicate if the performance criteria are satisfied by fire from inside or fire from outside or both, and whether it applies to vertical or horizontal orientations or both. The additions “i -> o”, “o -» i“ or “i o” shall be used respectively together with “ve” and/or “ho” to indicate orientation (vertical and horizontal).

For example, a classification EI30 (ve ho і o) indicates a ventilation duct capable of satisfying 30 min integrity and insulation, from inside to outside and vice-versa in both vertical and horizontal applications.

The classification S shall be added, based on satisfaction of the ambient smoke leakage criterion. This shall be based on a pass/fail test for the leakage. For example, a classification EI30 (ve ho і <-> o) S indicates a duct with the same performance as above but additionally satisfying the leakage criterion (10 m3/(m2h).

Failure of the suspension devices does not constitute failure of the test specimen unless it leads to failure of either E or El.

7.2.3 Fire dampers

  1. E) Test method and field of application rules (51

The test method for dampers shall be as given in EN 1366-2. E) Extended application shall be carried out as described in the relevant extended application standard and in prEN 15725. (51

  1. Tests to be carried out

The design of the test specimen and the number of tests to be carried out shall be derived from a comparison between the envisaged field of application of the classification and the field of application of test results as E>defined in the test standard and in the relevant extended application standard^]. Full details of the number of tests are given in EN 1366-2:

The test method provides information on the following:

  • test specimen/construction;

  • field of direct application of test results;

  • guidance on test specimen design.

Aspects influencing the number of tests to be carried out include, for example:

  • installation of the damper;

  • symmetry of the damper;

  • direction of flow;

  • orientation of the installation.

  1. Performance criteria

— Integrity

Integrity shall be assessed during the test as the time at which leakage through the damper after 5 min from the start of the fire test exceeds 360 m3/(m2 h), cracks or openings in excess of given dimensions and ignition of a cotton pad and sustained flaming on the non-exposed side at the perimeter of the damper junction with the wall or floor occur. Ignition of the cotton pad shall be disregarded for dampers classified E only.

— Insulation

The performance level used to define insulation shall be the mean temperature rise on the unexposed face, limited to 140 °С above the initial mean temperature, with the maximum temperature rise at any point limited to 180 °С above the initial mean temperature.



— Smoke leakage (if necessary)

For dampers for which the S class is relevant the leakage through the fire damper shall not exceed 200m/(m2h), corrected to 20 °С at ambient temperature prior to the fire test, and shall not exceed 200 m3/(m2 h) corrected to 20 °С after the first 5 minutes of the fire test.

The performance criteria, taken from EN 1366-2, are given in Table 2.

Table 2 — Fire test performance criteria for fire resisting dampers

Classification

Size to be tested

Leakage limit at ambient temperature m /(h.m2)

10.3 of EN 1366-2:1999

Fire test

10.4 of EN 1366-2:1999




Leakage limit m3/hm2

Temperature rise limit °С mean/max

E

max

not required

360 а

not required

E-S

max

200

200 а

not required

min

200

no test

not required

El

max

not required

360 а

140/180

El-S

max

200

200 а

140/180

min

200

no test

no test

Leakage limits only apply after 5 min from the start of the test.7.2.3.4 Classes

The following classes are defined:

El 15 20 30 45 60 90

120 180 240

E 30 60 90

120



If the leakage rate shall be restricted further, S is added to the classification if the criteria specified in 7.2.3.3 are satisfied.

The classification shall indicate if the performance criteria are satisfied by fire from one side only or from both sides, and whether it applies to vertical or horizontal orientations or both. The additions “і -> о”, “о -> i” or “i o” shall be used respectively together with “ve” and/or “ho” to indicate orientation. For example, a classification El 30 (ve ho і <н>о) indicates a damper capable of satisfying 30 min integrity and insulation, from both sides in both vertical and horizontal applications.

The classification S shall be added, based on satisfaction of the ambient smoke leakage criterion. This shall be based on a pass/fail test for the leakage. For example, a classification El 30 (ve ho і <-> o) S indicates a damper with the same performance as above but additionally satisfying the leakage criterion (10 m3/(m2 h).

The functioning of the closing device of fire dampers has also to be assessed, with any damper failing the closing test being ineligible for fire resistance classification.

With respect to the reliability of the closing device, further tests could be necessary and reliability is not covered by this classification.

Failure of the suspension devices does not constitute failure of the test specimen unless it leads to failure of either E or El.Annex A
(normative)

Classification report

A.1 General

The aim of the classification report is to provide a harmonised way of presenting the classification of a construction product/element when classified, based on results obtained during tests in accordance with the relevant resistance to E> fire test method and/or through extended application process ®J.

A classification report shall detail the basis and the results of the classification process.

A.2 Content and format

The classification report shall have the following content and format illustrated below:

  1. identification number and date of the classification document;

  2. identification of the owner of the classification document;

  3. identification of the organisation issuing the classification document;

  4. details of the type and function of the classified element or product classification, including its commercial name;

  5. detailed description of the product/element:

Either reference shall be made to a detailed description of the element(s) or product as E) available in one of the test reports and/or the extended application report(s) in support of О this classification, or a detailed description shall be reproduced in this classification document. The detailed description shall include a full description and identification of all relevant components, the method of assembly etc.

It shall also list all relevant technical specifications applicable to the whole or parts of the classified product or element;

  1. E) test(s) and extended application(s) carried out: @3

  1. E) All test reports and extended application reports used in support of this classification shall be identified by:

  • name of the laboratory carrying out the tests;

  • name of the sponsor;

  • test and test report identification number.

  1. Identification of the tests carried out in accordance with this European Standard and the relevant field of application.

  2. Detailed test results for each test specimen and each test condition and/or extended application results for all relevant criteria (51 involved in the classification, including the stresses in the suspension devices.

  1. Classification and field of application:

  • reference to the relevant classification procedure in this European Standard, i.e. EN 13501-3,

  • classification of the construction element or product;

  • detailed description of the field of E) deleted text (51 application of this classification document.

  1. Additional statements:

  • any restrictions on the duration of the validity of this classification report;

  • warning ‘This European Standard does not represent type approval or certification of the product’.

The following shows the layout and format of the classification report.

LOGO/Letterhead of organisation undertaking classification

CLASSIFICATION REPORT OF PRODUCT/ELEMENT XYZ

IDENTIFICATION NUMBER OF THIS CLASSIFICATION REPORT

On behalf of

OWNER OF CLASSIFICATION DOCUMENT

Address 1

Address 2

Address 3

Address 4

  1. Introduction

This classification report defines the classification assigned to product/element XYZ in accordance with the procedures given in EN 13501-3:2005.

  1. Details of element

    1. Type of function

The product/element xyz is defined as a ‘type of classified element’. Its function is to resist fire in respect of integrity/insulation /resistance to smoke leakage*.

  1. Description

either

The product/element xyz Ю is fully described in the test report(s) and/or the extended application report(s) in support of <51 this classification listed in Clause 3.

or

The product/element xyz comprises:

'Detailed description of product/element’

This product/element complies with the following technical specifications:

— ‘list of relevant specifications’.

  1. E> Reports and results in support of this classification О

E) The following test report(s) and/or extended application report(s) are О presented in support of this classification.

  1. For ducts

NAME OF LABORATORY

NAME OF SPONSOR

UNIQUE REF No.

E

I

S

Direction (i-o)

Orientation (ho, ve)











3.2 For dampers

NAME OF LABORATORY

NAME OF SPONSOR

UNIQUE REF No.

E

I

S

Direction (i-o)

Orientation (ho, ve)











  1. E) Classification and field of application О

    1. Reference of classification

This classification has been carried out in accordance with EN 13501-3:2005.

  1. Classification

This product/element xyz has been classified:

  1. For ducts

E

I


t

t


(

ve


ho


і

<->

о

)


S