Table 2 - Schedule of tetri
1 |
2 |
3 |
4 |
Het |
TettS |
Category d |
Tort metnod described in |
He |
|
1» to |
|
1 |
Etoetrfcrt ют?» |
|
|
1,1 |
fteoirtonco of conduct ore |
Tr R |
HO 21.2 |
1-2 |
Ineufaiion of roeistonco пнааигеїгелі |
T |
£C &O2 |
1.3 |
Voftago toot for 4 hours |
T |
№C 302 |
1,4 |
Діжепсе of fault t on IntuleUon. or 4000 V ac. |
ft |
|
1.3 |
Surface геммМу of ehoech |
T |
HD 22 Pert 1. СШЯ4 7 |
2 |
Рпууйит* oovorwig cwtryctipnol and dimonownol charactorrtice |
|
|
2.1 |
Checking of «мпріюп« with соїмігисміпаї pro* tofans |
T.4 |
Impaction & manual teete |
2,2 |
Meaoufememt of thickneea of ineufamn |
T. s |
HD 21.2 |
2,3 |
Meooufomonto of th«kn»*e of inner covering |
T, 5 |
HD 21.2 |
2.4 |
MoMUrornonls of thick пом of eherth |
T, Б |
HD 21.2 |
2 5 |
Meoturernenfa of overall demote* |
T, S |
HD 21.2 |
3 |
Mochenlosl DFOOettittfi Of Іґміиіеііюп |
|
|
3.1 |
Tontile тем before end olior ageing |
T |
ICC BO2 |
4 |
Mechanical propertee of ehaath |
|
|
4.1 |
Teneila toot before end idler ageing |
T |
HD БО6.1.1 eub-olouM 3.2 |
& |
Tert on ineulaboo |
|
|
Б J |
Hot set teat on іщцілїил |
T |
ICC 502 |
Б.2 |
Water «ЬОопНюп on emulation |
T |
IEC Б02 |
Б.З |
SwnMge teet of Ілеикміоп |
T |
ICC Б02 |
В |
Ргмбше wm luah teffiDrtrture |
|
|
B.1 |
Showh |
T |
HD 606.3.1 •ub-otouoo В |
Pegs 5-F-12 HD 604 51:1994
Part 5 Section F
Table 2 Icon eluded)
1 1 |
2 |
3 |
|
Mt |
|
Category Ы |
Test nwthoe daacrAad» । |
No |
|
teete |
|
T |
Bmdnn икі fenoact itreratfb at bw temperature* |
|
|
7 J |
Bendkig teal for іпеиіеікм* «1 taw temperatures b26 degrees Cl before agemg |
T |
HD SOB 2.4.1.4 |
72 |
Bendng test lor insula! km st tow temperatures [-И degree* Cl aft* ageing |
T |
HD 806 14.1.4 |
7.3 |
Bandog tear lor *h»ath «1 low temperature* (-2B deyeae C> belore ageing |
T |
HD «№ 2.4.1.4 |
7 4 |
Bendog f*M lor sheath ai low tempera ішеа LIB degree* C> alter egekig |
T |
HD 006 2 4.1.4 |
7Л |
Impact teat at tow temp» a lute |
T |
HD 5061Л |
|
(* 16 deuces Q on complete cable |
|
Oauao 3.6 |
a |
Meat tNrtk lest |
|
|
e.i |
Shaath |
T |
HD 605.3.1 Ctouae 8.1 |
0 |
Том Ы non eontam ангіом |
|
|
ri |
Тем on oompleta enbto |
T |
НОБО5.1.2 СІаим 6 |
10 |
Тем under Tfra eondtiont |
T. 8 |
HD 606 4.1.5 |
10.1 |
On complete cab*e |
T |
HD406.3 C«HK*V C |
11 |
Smoke emission |
T |
HD6O5 |
12 |
Acid pee enwMtqn |
T |
IEC 764-1 |
13 |
CofTPi^a ан •mtoeipr |
T |
HD6O2 |
Table 3 - Dimension for preferred designs
Number and nominal cross' sectional area of conductors |
Material and class of conductor |
Thickness of insulation |
Thickness of Inner Covering |
Thickness of Sheath |
|
|
Specified Value |
Approx. Value |
Specified Value |
{mmH |
1HD 3631 |
Imml |
(nvnl |
(mml |
lx 1.5 |
Co 1 |
0.8 |
o.e |
1Л |
1 к 2.5 |
Cu 1 |
0.8 |
0.6 |
1.5 |
1 x 4 |
Cu 1 |
0.9 |
0.6 |
1,5 |
1 x 6 |
Си 2 |
0.9 |
0.6 |
15 |
1 x 10 |
Си 2 |
1,1 |
0.7 |
1.6 |
1 x 16 |
Си 2 |
1,1 |
0.8 |
1,6 |
1 x 25 |
Си 2 |
1.3 |
0 9 |
1,8 |
2x 1.5 |
Си 1 |
0.8 |
0.6 |
1.5 |
2 M 2.6 |
Си 1 |
o.e |
0.6 |
1.5 |
2x 4 |
Си 1 |
09 |
0.6 |
1.5 |
2x 6 |
Си 2 |
0,9 |
0.6 |
1.5 |
2 x 10 |
Си 2 |
11 |
0,7 |
1.5 |
2 x 16 |
Си 2 |
1.1 |
0.8 |
1.6 |
2 x 25 |
Си 2 |
13 |
0.9 |
1.8 |
Table 3 (concluded)
Number and nominal cross- sectional area of conductors |
Material and class of conductor |
Thickness of insulation |
Thickness of Inner Covering |
Thickness of Sheath |
|
|
Specified Value |
Approx. Value |
Specified Value |
(mm1) |
(HD 383) |
(mml |
(ml |
(mml |
3 к 1*5 |
Cu 1 |
0*8 |
0.6 |
1*5 |
3x 2 5 |
Си 1 |
08 |
0.6 |
1.5 |
3x4 |
Cu 1 |
0.9 |
0.6 |
1*5 |
Зх в |
Cu 2 |
09 |
0.7 |
1.5 |
3 x 10 |
Cu 2 |
1Л |
0,7 |
1,6 |
3 x 16 |
Cu 2 |
1.1 |
0.8 |
1.6 |
3x25 |
Cu 2 |
1.3 |
0.9 |
1.8 |
4 x 1*5 |
Си 1 |
0.8 |
0.6 |
IS |
4x 2 5 |
Cu 1 |
0.8 |
0.6 |
1*5 |
4x4 |
Си 1 |
0 9 |
0.7 |
1*5 |
4x 6 |
Cu 2 |
09 |
0.7 |
1.5 |
4x10 |
Cu 2 |
1x1 |
0.8 |
1.6 |
4x16 |
Cu 2 |
1*1 |
0.8 |
1.6 |
4 x 25 |
Cu 2 |
13 |
0.9 |
1,8 |
5 м 1.5 |
Cu 1 |
0 8 |
0.6 |
1.5 |
5x 2*5 |
Cu 1 |
0 8 |
0.6 |
L5 |
5x 4 |
Си 1 |
0*9 |
0.7 |
1.5 |
5x 6 |
Cu 2 |
0*9 |
0.7 |
1.6 |
5 x 10 |
Cu 2 |
1*1 |
0.8 |
16 |
5x18 |
Cu 2 |
LI |
0.9 |
1*8 |
5 X 25 |
Cu 2 |
1.3 |
1.0 |
2.0 |
APPENDIX A
GUIDE TOUSE
S££tfi£
This Guide to Use is vabd foe the application of 0.6/1 kV crosslinked polyethylene and silicone rubber insulated and halogen-free compound sheathed single and multi-core cables with special fra performance properties, mainly intended for use in power plants and substations.
QfelsSH
The object of this document is to provide recommendations for the selection, storage, transportation and installation of the cables, specified under item 1, Scope,
NOTE: Safety reauiroments as well as rules of installation are пот considered in this Guide to Usa, as they are covered by relevant regulations and laws.
Recommendations for use
Permissible applications
Specified cables according to HD 604 Part 5 Section F may be indoors, also in wet locations, and outdoors for installations on walls and metallic structures. Direct burial in soil is allowed, as long as the relevant rules of installation are followed.
Highest permissible voltage
Cables rate at Uo/U = 0 6/1 кV may be used in DC systems having a rated operation voltage between conductors not higher chan 1.5kV. and between conductors and earth not higher than 0.9kV
Concennic conductor
The concentric conductor may be used as neutral, PE-conductor, PEN-conductor or as a screen in accordance with relevant regulations.
Recommandatmns for storaoe and transport
Delivery
The distance between the outer cable layer of a fil!ed-up-cable*delivery-drum and the head of the flange shall ba sufficiently high ю avoid damage to the cable.
СаЫа-end seakto
The cable-ends have to be sealed waterproof during transport, storage and laying.
Transport
4,3'1 For the transport of fiNed-up cable reels only suitable carriers shall be used.
Cable drums with fl ange diameters а хсееФпд 1 m have to be transported with the drum axis in the horizontal position. The drums have to be protected against movement. Loading and unloading shall be made by suitable devices to avoid damage to the cables and to the cable drums.Fil led'up cable drums shell be rolled only on short distances over plain solid ground in the diractitxi indicated on the cable drum. The cable ends have to be tightened.
4.3.2 Short cable lengths may be coiled to rings and trans ported and stored horlzomaly. The permissible bending radii shall not fall short of the values given in clause 5.4.
Recommendation for cable laving and installation
General recommendationa
The cable route, the laying method and the service comfit ions shad be taken into account when selecting the type of cable.
Cables shah be laid and operated in such a way that Шек properties are not endangered.
bn this context rhe following items shall be taken into account:
lai The service conditions. like concentrations of cable quantities, influence of external beat, specific earth resistance, protection against solar radiation, which form the basis for ths selection of the cable type;
(bj Leakage or stray currents and corrosion;
Movements of soil, vibrations (foundations of machines, bridges I, shakes;
The method of laying and the bedding material have io be selected in respect of the outer cable sheath to avoid mechanical damage;
Protection against outer influence, e.g, chemical solvents.
Cables shall be protected against mechanical damage occurring after installation.
Cables laid in ground are considered as being sufficiently mechanicaly protected, if relevant regulations and lews concerning laying depth in ground and protection are folk) wed
The laying depth in the ground shall be according co the relevant regulations and laws.
Inner diameters of ducts and pipes have to have at least a diameter of 1.5 times the cable diameter