C.4.4 High temperature test

Carry out the test at not less than the temperature and not more than the temperature + 25 °С and for the appropriate period of time specified in Table 2. Record electrical, flow and or pressure and temperature measurements at intervals not exceeding 2 min. Correct the static pressure measurements for the effects of density change due to temperature.

After 15 minutes, switch off the ventilator for 2 minutes, then restart the ventilator. During this period the temperature variation may exceed the specified limits. Add the time the ventilator is switched off to the period of the test.

C.4.5 High temperature test in accordance with temperature time curve

Increase the gas temperature at the intake plane of the ventilator in accordance with the standard time/temperature curve defined in ISO 834-1. Control the temperature to a tolerance of 0 to + 25 °С. Test the ventilator for a period of 30 minutes. Record electrical, flow and or pressure and temperature measurements at intervals not exceeding 2 min. Correct the static pressure measurements for the effects of density change due to temperature. At the end of this period switch off the ventilator for 2 minutes and then re-start the ventilator. During this period the temperature variation may exceed the specified limits. The test is completed once the fan has re-started and meets the requirements of C.l.

During the entire period of the test (for products intended to be installed within a building) observe the emissions of any smoke from the furnace coming from the housing of the ventilator due to distortion/leakage of the housing.

C.5 Test report

C.5.1 Prepare a test report after completion of the tests including the following information:

  1. name of the test laboratory;

  2. name of the sponsor;

  3. date of tests;

  4. name of supplier and trade name of the product;

  5. the reference to the test methods;

  6. the catalogue description, size and speed of the ventilator tested;

  7. the ancillaries tested;

  8. the temperature time class (see clause 6.1);

  9. the application classes (see clause 4.1);

  10. the product range approved by the tests in accordance with annex A;

  11. snow load class;

  12. details of the test arrangement including all equipment used for measurement of temperature, flow, pressure, current, voltage, electrical power and wind and snow load;

  13. observations, measurements and calculated results made before during and after the tests in accordance with annex C and E or D.

C.5.2 Prepare an additional report providing details of the complete product range approved including:

  1. fan model number or catalogue code;

  2. fan speed;

  3. impeller and hub diameter, tip clearance, length and number of blades;

  4. approximate blade cross sectional area;

  5. approximate hub cross sectional area;

  6. motor speed;

  7. motor model number or catalogue code;

  8. motor rating;

  9. bearing type, class of fit, lubricant and arrangement for motor and fan, if fan is indirectly driven;

  10. carcase, end cover and cooling impeller material;

  11. class of insulation and specification;

  12. which ancillaries have been approved.

Annex D

(normative)

Test method for resistance to temperature of electric motors for use in powered
ventilators

D.l Principle

The resistance to temperature of electric motors for use in powered ventilators is proved by testing the motor at elevated temperature either in a powered ventilator or in conjunction with a generator or other method of providing the load. The motor is shown to be functioning satisfactorily by continuing to give the required output power and meeting the requirements of clause 4.2 and 6.1.2.

D.2 General

Test motors mounted within the airstream for ventilator Class F200, F300, F400 and F600 to this procedure. Test motors that are mounted outside the airstream with the impeller mounted on the motor shaft and motors for ventilator Class F842 as a unit with the ventilator.

D.3 Tests in association with a powered ventilator

Test the motor in a powered smoke ventilator in accordance with annex C.

D.4 Tests in association with a load

D.4.1 Apparatus

D.4.1.1 Test installation

Mount the motor on a stable support in an enclosure that has a minimum radial dimension . twice the maximum motor dimension.

Link it via a coupling and transmission shaft to an adjustable external load, such as a generator, which will absorb the power output of the motor.

To circulate the hot gas past the carcase at the rated velocity fit either the normal integral cooling impeller if the motor is not normally mounted in the fan airstream or an external impeller if the motor is mounted within the fan airstream. Mount the external impeller either directly on the motor shaft or on the transmission shaft.

Provide means of applying axial and radial load to the motor shaft. For example apply the axial load by rigidly connecting the motor to an external load generator that is free to move axially and so can be used to convert a stationary axial load to one that rotates. See Figure D.l.




Key

  1. Motor to be tested

  2. Fixed support

  3. Sliding support

  4. Radial load (e.g. steel disc)

  5. Flexible couplings, torsionally rigid


  1. Generator

  2. Mass

  3. Axial load, induced by mass (7)

  4. Furnace

  5. Penetration point



Figure D.l — Typical method of applying radial and axial load to a motor

D.4.1.2 Temperature measurements

Fit a furnace thermocouple approximately 100 mm upstream of the motor on the motor axis of rotation to measure the temperature of the incoming gases. Fit a single device at the fins of the motor for surface temperature measurement.

D.4.1.3 Electrical measurements

Fit equipment to measure frequency, voltage, current, power and speed in accordance with IEC 34-2 and ISO 5801.

D.4.2 Test specimens

Select test specimens in accordance with annexes A and B.

D.4.3 Test procedure

D.4.3.1 General conditions

Carry out the tests at an ambient temperature between 15 °С and 40 °С.

D.4.3.2 Warm up period

Operate the motor at ambient temperature at its rated frequency and voltage at 80 % to 100 % of the maximum rated power, at the maximum speed or if the motor is a two speed motor designed for continuous operation at low speed only, at the lower speed. Monitor the surface temperature of the motor until the rate of temperature increase is less than 2 °С in 10 minutes. Record electrical and temperature measurements.

Increase the temperature at the air intake of the motor to that specified in Table 2 within a period of not more than 10 minutes or not less than 5 minutes. Record electrical and temperature measurements during this period. Adjust the motor input power to F times the rated power at a density of 1,2 kg/m3, where F is as follows:

0,88 at a temperature of 200 °С

0,80 at a temperature of 300 °С

0,76 at a temperature of 400 °С

0,60 at a temperature of 600 °С

These factors do not apply to motors approved in the fans in which they are to be used, as the change of temperature causes all the effects that will change the power. However the factors established for one range of fans cannot be used for another.

D.4.3.3 High temperature test

Carry out the test at not less than the specified temperature, and not more than the specified temperature + 25 °С and for the appropriate period of time specified in Table 2. Record electrical, flow and or pressure and temperature measurements at intervals not exceeding 2 min.D.5 Test report

D.5.1 Prepare a test report after completion of the tests including the following information:

  1. name of the test laboratory;

  2. name of the sponsor;

  3. date of tests;

  4. name of supplier and trade name of the product;

  5. the reference to the test method/s;

  6. the catalogue description, frame size, class of insulation and speed of the motor tested;

  7. the temperature time class (see clause 6.1)

  8. the application classes (see 4.1);

  9. the product range approved by the tests in accordance with annex A;

  10. details of the test arrangement including all equipment used for measurement of temperature, flow, pressure, current, voltage and electrical power;

  11. observations, measurements and calculated results made before during and after the tests in accordance with annex C or D.4.3.

D.5.2 Prepare an additional report providing details of the complete product range approved including:

  1. motor speed;

  2. motor model number or catalogue code;

  3. motor rating;

  4. bearing type, class of fit, lubricant and arrangement;

  5. carcase, end cover and cooling impeller material;

class of insulation and specification.Annex E
(normative)

Test method for operation under load

E.l Objective of test

The objective of this test is to establish the ability of the installed ventilator to operate at the critical operation condition, i.e. against an applied wind and snow load.

E.2 Test apparatus

Use a suitable test rig onto which the ventilator can be mounted and subjected to a test load equivalent to a wind pressure of 200 pa, when required as defined in 6.4, and a snow load as defined in 6.5. Apply the test load by one of the following methods:

  1. plates;

  2. bags containing up to 5 kg of solid particles or liquid;

Spread the loads over the whole of the external surface of the individual elements of the opening parts of the ventilator, to produce a uniformly distributed load.

E.3 Test specimen

A test on the largest ventilator of a range shall be considered representative of all ventilators in a particular range.

E.4 Test procedure

Mount the ventilator on the test rig in accordance with the supplier’s recommendations.

Apply the load using one of the methods given in E.2, increasing the load to the upper appropriate limit given in sections 6.4 and 6.5 and maintain the load for 10 ± 1 min.

Remove the load, actuate the ventilator and check that the dampers, flaps or louvres open to the design position.

Operate the ventilator against the design load three times, using the energy source as specified by the supplier and its fire activating mechanism. Determine if the fire operating position is reached each time.

E.5 Evaluation of test results

The ventilator meets the requirement of 6.4 and 6.5 if the test specimen achieves the operating position in each of the tests in less than 30 seconds. The test results may be applied to all ventilators of the same range., Annex ZA

(informative)

Clauses of this European Standard addressing essential requirements or other
provisions of EU Directives

ZA.O Scope of this annex

The scope as given in clause 1 is applicable.

ZA.l Clauses of this European Standard addressing the provisions of the EU Construction Products Directive

This European standard has been prepared under a Mandate given to CEN by the European Commission and the European Free Trade Association.

The clauses of this European standard shown in this annex meet the requirements of the Mandate given under the EU Construction Products Directive (89/106).

Compliance with these clauses confers a presumption of fitness of the construction products covered by this European standard for their intended use.

WARNING: Other requirements and other EU Directives, not affecting the fitness for intended use may be applicable to a Construction Product falling within the scope of this standard.

NOTE 1 In addition to any specific clauses relating to dangerous substances contained in this Standard, there may be other requirements applicable to the products falling within its scope (e.g. transposed European legislation and national laws, regulations and administrative provisions). In order to meet the provisions of the EU Construction Products Directive, these requirements need also to be complied with, when and where they apply.

NOTE 2 An informative database of European and national provisions on dangerous substances is available at the Construction web site on EUROPA (CREATE, accessed through http://www.europa.eu.int).”

Construction Product: Powered smoke and heat exhaust ventilators

Intended uses: Powered smoke and heat exhaust ventilators for smoke and heat control in construction works



Table ZA.l - Relevant clauses for all Powered smoke and heat exhaust ventilators

Requirements/ Characteristic from the Mandate:

Requirement Clause(s) in this or other European Standard(s):

Mandated levels and/or classes:

Notes:





Response delay

6.4 & 6.5.2


seconds

Operational reliability

6.7


Cycles

Effectiveness of smoke/hot gas extraction

Performance parameters under fire conditions

Resistance to fire:

  • Smoke leakage

  • Mechanical stability

6.1, 6.2, 6.3, 6.8

6.1.2

F200

F300

F400

F600

F842

Not classified

°С & minutes

Ability to open under environmental conditions

6.4, 6.5.1 & 6.6


Pa



ZA.2 Procedure for the attestation of conformity of Powered smoke and heat exhaust ventilators

Powered smoke and heat exhaust ventilators for the intended use listed shall follow the system of attestation of conformity shown in Table ZA.2.

Table ZA.2 - Attestation of conformity systems

Product

Intended use

Level(s) or class(es)

Attestation of conformity system

Powered smoke and heat exhaust Ventilators

Fire safety

-

1

NOTE System 1: See CPD Annex Ш.2.(і), wit

lout audit testing of samples



The product certification body will certify the initial type testing of all characteristics given in Table ZA.l, in accordance with the provisions of 8.2, and for the initial inspection of the factory and of the factory production control, and for the continuous surveillance, assessment and approval of the factory production control, all characteristics shall be of interest to the approved body, see 8.3.

ZA.3 CE Marking

The CE marking shall be shown on the component body. In addition, the CE marking shall appear on the packaging and/or on the accompanying commercial documents, together with the following characteristics:

  • identification number of the notified body

  • the name or identifying mark of the producer/supplier, and

  • the last two digits of the year in which the marking was affixed, and

  • the appropriate number of the ЕС-certificate of conformity, and

  • the number of this standard (EN 12101-3), and

  • type of product (powered ventilator), and

  • response delay (s), and

  • fire resistance class

  • Motor rating

Figure ZA. 1 gives an example of the information to be given on the accompanying commercial documents.

0123

Any Co Limited, P.O. Box21, B-1050
00

0123 - CPD - 001 EN 12101-3 Powered smoke and heat exhaust ventilators for use in Construction Works

Response delay 30 s at SL 125 Resistance to Fire class F200 Motor rating Class В/Class F

Figure ZA.l - Example CE marking information

In addition to any specific information relating to dangerous substances shown above, the product should also be accompanied, when and where required and in the appropriate form, by documentation listing any other legislation on dangerous substances for which compliance is claimed, together with any information required by that legislation.

NOTE European legislation without national derogations need not be mentioned.

ZA.4 EC certificate and declaration of conformity

The manufacturer or his agent established in the EEA, shall prepare and retain a declaration of conformity, which authorises the affixing of the CE marking. This declaration shall include:

  • name and address of the manufacturer, or his authorised representative established in the EEA, and the place of production,

  • description of the product (type, identification, use), and a copy of the information accompanying the CE marking,

  • provisions to which the product conforms (e.g. annex ZA of this EN),

  • particular conditions applicable to the use of the product [if necessary],

  • name and address (or identification number) of the approved body(bodies)

  • name of, and position held by, the person empowered to sign the declaration on behalf of the manufacturer or of his authorised representative.

For characteristics where certification is required (system 1), the declaration shall contain a certificate of conformity with, in addition to the information above, the following information:

  • the name and address of the certification body,

  • the certificate number,

  • conditions and period of validity of the certificate, where applicable

  • name of, and position held by, the person empowered to sign the certificate.

Duplication of information between the declaration and certificate shall be avoided. The declaration and certificate shall be presented in the language(s) of the Member State of use of the product.Bibliography

prEN 12094,

Fixed fire fighting systems - components for gas extinguishing systems

ISO 14520-1,

Gaseous fire-extinguishing systems

ISO 6944,

Method for determination of fire resistance of ventilation ducts

EN ISO 9001

Quality management systems - Requirements (ISO 9001:2000)EUROPEAN STANDARD NORME EUROPEENNE EUROPAISCHE NORM

EN 12101-3:2002/AC

March 2005

Mars 2005

Marz 2005ICS 13.220.20; 23.120

English version
Version Frangaise
Deutsche Fassung

Smoke and heat control systems - Part 3: Specification for powered smoke
and heat exhaust ventilators

Systemes pour Ie controle des fumees et Rauch- und Warmefreihaltung - Teil 3: de la chaleur - Partie 3: Specifications pour Bestimmungen fOr maschinelle Rauch- und les ventilateurs extracteurs de fumees et de Warmeabzugsgerate

chaleur

This corrigendum becomes effective on 2 March 2005 for incorporation in the three official language versions of the EN.

Ce corrigendum prendra effet Ie 2 mars 2005 pour incorporation dans les trois versions linguistiques officielles de la EN.

Die Berichtigung tritt am 2.Marz 2005 zur Einarbeitung in die drei offiziellen Sprachfassungen der EN in Kraft.


EUROPEAN COMMITTEE FOR STANDARDIZATION
СОМІТЁ EUROPfiEN DE NORMALISATION
EUROPAISCHES KOMITEE FOR NORMUNG

Management Centre: rue de Stassart, 36 B-1050 Brussels

© 2005 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members.

Tous droits d'exploitation sous quelque forme et de quelque maniere que ce soit reserves dans Ie monde entier aux membres nationaux du CEN. .

Alle Rechte der Verwertung, gleich in welcher Form und in welchem Verfahren, sind weltweit den nationalen Mitgliedern von CEN vorbehalten.

Ref. No.:EN 12101-3:2002/AC:2005 D/E/F

EN 12101-3:2002/AC:2005 (E/F/D)

English version

At the end of the list in 6.1.1 insert a new paragraph: "For products classified F400, the classification shall be followed by the time period, i.e. F400 (90) or F400 (120).".

In Table 2, which gives the classification, amend the entry against F400 to "90 or 120"