• Method B1: using conduits (3.7) and cable trunking systems (3.5) for holding and protecting conductors or single core cables;

  • Method B2: same as B1 but used for multicore cables;

  • Method C: multicore cables installed in free air, horizontal or vertical without gap

between cables on walls;

  • Method E: multicore cables in free air, horizontal or vertical laid on open cable trays (3.4).


IEC 1393/05



Conductors/single core cables in conduit and cable trunking systems

Cables in conduit and cable trunking systems


Cables on walls


Cables on open cable trays


Figure D.1 - Methods of conductor and cable installation
independent of number of conductors/cables

D.1.3 Grouping

Where more loaded conductors in cables or conductor pairs are installed, derate the values of Jz, given in Table 6 or by the manufacturer in accordance with Tables D.2 or D.3.

NOTE Circuits with Ib< 30 % of Iz need not be derated.



Table D.2 - Derating factors from /zfor grouping

Methods of installation (see Figure D.1) (see Note 3)

B1 (circuits) and B2 (cables)

C single layer with no gap between cables

E single layer on one perforated tray without gap between cables

E as before but with 2 to 3 trays, with a vertical spacing between each tray of 300 mm (see Note 4)

Number of loaded circuits/cables

2

4

6

9

0,80

0,85

0,88

0,86

0,65

0,75

0,77

0,76

0,57

0,72

0,73

0,71

0,50

0,70

0,72

0,66

Control circuit pairs < 0,5mm2 independent of methods of installation

0,76

0,57

0,48

0,40

NOTE 1 These factors are applicable to

  • cables, all equally loaded, the circuit itself symmetrically loaded;

  • groups of circuits of insulated conductors or cables having the same allowable maximum operating temperature. NOTE 2 The same factors are applied to

  • groups of two or three single-core cables;

  • multicore cables.

NOTE 3 Factors derived from IEC 60364-5-52:2001.

NOTE 4 A perforated cable tray is a tray where the holes occupy more than 30 % of the area of the base. (Derived from IEC 60364-5-52:2001).



Table D.3 - Derating factors from 7Zfor multicore cables up to 10 mm2

Number of loaded conductors or pairs

2

Conductors (> 1 mm ) (see Note 3)

Pairs (0,25 mm2to 0,75 mm2)

1

-

1,0

3

1,0

-

5

0,75

0,39

7

0,65

0,34

10

0,55

0,29

24

0,40

0,21

NOTE 1 Applicable to multicore cables with equally loaded conductors/pairs.


NOTE 2 For grouping of multicore cables, see derating factors of Table D.2.


NOTE 3 Factors derived from IEC 60364-5-52:2001.


D.1.4 Classification of conductors

Table D.4 - Classification of conductors

Class

Description

Use/application

1

Solid copper or aluminium conductors

Fixed installations

2

Stranded copper or aluminium conductors

5

Flexible stranded copper conductors

Machine installations with presence of vibration; connection to moving parts

For frequent movements

6

Flexible stranded copper conductors conductors that are more flexible than class 5

NOTE Derived from IEC 60228.



D.2 Co-ordination between conductors and protective devices providing overload protection

F

Design current Ib

igure D.2 illustrates the relationship between the parameters of conductors and the parameters of protective devices providing overload protection.

Current carrying capacity lz

1,45 x/2

Parameters of
conductors

Parameters of
protective devices


Acceptable range for
tripping current І2


Nominal current or current setting In


Figure D.2 - Parameters of conductors and protective devices

Correct protection of a cable requires that the operating characteristics of a protective device (for example overcurrent protective device, motor overload protective device) protecting the cable against overload satisfy the two following conditions:


where

/b is the current for which the circuit is designed;



(1)

IEC 1396/05

12 < 1,45 x Iz

(2)


/z is the effective current-carrying capacity, in amperes, of the cable for continuous service according to Table 6 for the particular installation conditions:

  • temperature, derating of lz see Table D.1;

  • grouping, derating of lz see Table D.2;

  • multicore cables, derating of lz see Table D.3.

In is the nominal current of the protective device;

NOTE 1 For adjustable protective devices, the nominal current I„ is the current setting selected.

I2 is the minimum current ensuring effective operation of the protective device within a specified time (for example 1 h for protective devices up to 63 A).

The current 12 ensuring effective operation of the protective device is given in the product standard or may be provided by the manufacturer.

NOTE 2 For motor circuit conductors, overload protection for conductor(s) can be provided by the overload protection for the motor(s) whereas the short-circuit protection is provided by short-circuit protective devices.

Where a device that provides both overload and short-circuit protection is used in accordance with this Clause for conductor overload protection, it does not ensure complete protection in all cases (for example overload with currents less than 12), nor will it necessarily result in an economical solution. Therefore, such a device can be unsuitable where overloads with currents less than I2 are likely to occur.

D.3 Overcurrent protection of conductors

All conductors are required to be protected against overcurrent (see 7.2) by protective devices inserted in all live conductors so that any short circuit current flowing in the cable is interrupted before the conductor has reached the maximum allowable temperature.

NOTE For neutral conductors, see 7.2.3, second paragraph.

Table D.5 - Maximum allowable conductor temperatures under normal
and short-circuit conditions

Type of insulation

Maximum temperature under normal conditions

°С

Ultimate short-time conductor temperature under short circuit conditions3)

°С

Polyvinyl chloride (PVC)

70

160

Rubber

60

200

Cross-linked polyethylene (XLPE)

90

250

Ethylene propylene compound (EPR)

90

250

Silicone rubber (SiR)

180

350

NOTE For ultimate short-time conductor temperatures greater than 200 °С, neither tinned nor bare copper conductors are suitable. Silver-plated or nickel-plated copper conductors are suitable for use above 200 °С.

a> These values are based on the assumption of adiabatic behaviour for a period of not more than 5 s.



In practice, the requirements of 7.2 are fulfilled when the protective device at a current I causes the interruption of the circuit within a time that in no case exceeds the time t where t < 5 sec.

The value of the time t in seconds shall be calculated using the following formula:

t = (k x S/Г)2

where:

S is the cross-sectional area in square millimetres;

/ is the effective short-circuit current in amperes expressed for a.c. as the r.m.s. value;

к is the factor shown for copper conductors when insulated with the following material:

PVC

115

Rubber

141

SiR

132

XLPE

143

EPR 143



The use of fuses with characteristics gG or gM (see IEC 60269-1) and circuit-breakers with characteristics В and C in accordance with the IEC 60898 series, ensures that the temperature limits in Table D.5 will not be exceeded, provided that the nominal current /n is chosen in accordance with Table 6 where /n < 7Z.Annex Е
(informative)

Explanation of emergency operation functions

NOTE These concepts are included here to give the reader an understanding of these terms even though in this part of IEC 60204 only two of them are used.

Emergency operation

Emergency operation includes separately or in combination:

  • emergency stop;

  • emergency start;

  • emergency switching off;

  • emergency switching on.

Emergency stop

An emergency operation intended to stop a process or a movement that has become hazardous.

Emergency start

An emergency operation intended to start a process or a movement to remove or to avoid a hazardous situation.

Emergency switching off

An emergency operation intended to switch off the supply of electrical energy to all or a part of an installation where a risk of electric shock or another risk of electrical origin is involved.

Emergency switching on

An emergency operation intended to switch on the supply of electrical energy to a part of an installation that is intended to be used for emergency situations.Annex F
(informative)

Guide for the use of this part of IEC 60204

F.1 General

This part of IEC 60204 gives a large number of general requirements that may or may not be applicable to the electrical equipment of a particular machine. A simple reference without any qualification to the complete standard IEC 60204-1 is therefore not sufficient. Choices need to be made to cover all requirements of this part of IEC 60204. A technical committee preparing a product family or a dedicated product standard (type C in CEN), and the supplier of a machine for which no product family or dedicated product standard exists, should use this part of IEC 60204:

  1. by reference; and

  2. by selection of the most appropriate option(s) from the requirements given in the relevant Clauses; and

  3. by modification of certain Clauses, as necessary, where the particular requirements for the equipment of the machine are adequately covered by other relevant standards,

providing the options selected and the modifications made do not adversely affect the level of protection required for that machine according to the risk assessment.

When applying the three principles a), b) and c) listed above, it is recommended that:

- reference be made to the relevant Clauses and Subclauses of this standard:

  1. that are complied with, indicating where relevant the applicable option;

  2. that have been modified or extended for the specific machine or equipment requirements; and

  • reference be made directly to the relevant standard, for those requirements for the electrical equipment that are adequately covered by that standard.

In all cases, expertise is essential to be able to:

  • perform the necessary risk assessment of the machine;

  • read and understand all of the requirements of this part of IEC 60204;

  • choose the applicable requirements from this part of IEC 60204 where alternatives are given;

  • identify alternative or additional particular requirements that differ from or are not included in the requirements of this part of IEC 60204, and that are determined by the machine and its use; and

  • specify precisely those particular requirements.

Figure 1 of this part of IEC 60204 is a block diagram of a typical machine and can be used as the starting point of this task. It indicates the Clauses and Subclauses dealing with particular requirements/equipment. However, this part of IEC 60204 is a complex document and Table F.1 can help identify the application options for a particular machine and gives reference to other relevant standards.



Table F.1 - Application options

Subject

Clause or Subclause

і)

Іі)

iii)

iv)

Scope

1


X



General requirements

4

X

X

X

ISO 12100 (all parts)

ISO 14121

Selection of equipment

4.2.2


X

X

IEC 60439 series

Supply disconnecting (isolating) device

5.3

X




Excepted circuits

5.3.5

X


X

ISO 12100 (all parts)

Prevention of unexpected start-up, isolation

5.4, 5.5 and 5.6

X

X

X

ISO 14118

Protection against electric shock

6

X



IEC 60364-4-41

Emergency operations

9.2.5.4

X


X

ISO 13850

Two-hand control

9.2.6.2

X

X


ISO 13851

Cableless control

9.2.7

X

X

X


Control functions in the event of failure

9.4

X

X

X

ISO 14121

ISO 13849 (all parts)

IEC 62061

Position sensors

10.1.4

X

X

X

ISO 14119

Colours and markings of operator interface devices

10.2, 10.3 and 10.4

X

X


IEC 60073

IEC 61310 (all parts)

Emergency stop devices

10.7

X

X


ISO 13850

Emergency switching off devices

10.8

X




Controlgear - protection against ingress of contaminants, etc.

10.1.3 and

11.3

X

X

X

IEC 60529

Identification of conductors

13.2

X

X



Verification

18

X

X

X


Additional user requirements

Annex В


X

X


Clauses and Subclauses of this part of IEC 60204 where action should be considered (shown by X) with respect to: i) selection from the measures given;

  1. additional requirements;

  2. different requirements;

  3. other standards that can be relevant.



Annex G
(informative)

Comparison of typical conductor cross-sectional areas

Table G.1 provides a comparison of the conductor cross-sectional areas of the American Wire Gauge (AWG) with square millimetres, square inches, and circular mils.

Table G.1 - Comparison of conductor sizes

Wire size

Gauge No

Cross-sectional area

d.c. resistance of copper at 20°C

Circular

mils

mm2

(AWG)

mm2

inches2

Ohms per km


0,2


0,196

0,000 304

91,62

387


24

0,205

0,000 317

87,60

404

0,3


0,283

0,000 438

63,46

558


22

0,324

0,000 504

55,44

640

0,5


0,500

0,000 775

36,70

987


20

0,519

0,000 802

34,45

1 020

0,75


0,750

0,001 162

24,80

1 480


18

0,823

0,001 272

20,95

1 620

1,0


1,000

0,001 550

18,20

1 973


16

1,31

0,002 026

13,19

2 580

1,5


1,500

0,002 325

12,20

2 960


14

2,08

0,003 228

8,442

4 110

2,5


2,500

0,003 875

7,56

4 934


12

3,31

0,005 129

5,315

6 530

4


4,000

0,006 200

4,700

7 894


10

5,26

0,008 152

3,335

10 380

6


6,000

0,009 300

3,110

11 841


8

8,37

0,012 967

2,093

16 510

10


10,000

0,001 550

1,840

19 735


6

13,3

0,020 610

1,320

26 240

16


16,000

0,024 800

1,160

31 576


4

21,1

0,032 780

0,829 5

41 740

25


25,000

0,038 800

0,734 0

49 338


2

33,6

0,052 100

0,521 1

66 360

35


35,000

0,054 200

0,529 0

69 073


1

42,4

0,065 700

0,413 9

83 690

50


47,000

0,072 800

0,391 0

92 756