Replace twice 'Physical' by 'Mechanical'.
8.3.4 Setting
Add the following after the last sentence:
In grade 1 l&HAS users at access level 1 may start setting (e.g. by a pushbutton) provided that this setting process may also be cancelled before completion by a user at access level 1 and means to start setting is located inside the supervised premises.
NOTE Starting of setting of the system by users at access level 1 should be used with caution.
Table 5 - Overriding of prevention of setting conditions
Replace 'АТЕ' by 'ATS' in table footnote b.
8.3.8.2 Unsetting - as specified in 8.3.7 b)
Replace the 3rd paragraph by the following:
When an intruder alarm condition occurs during the unsetting procedure the alarm condition shall be notified by a warning device or indicated. When remote notification is included in the intruder alarm system, the alarm condition shall not be remotely notified until the indicator or warning device has functioned for a minimum of 30 s and the entry timer has expired.
Renumber the two existing notes into NOTE 1 and NOTE 2 respectively.
Table 6 - Restoring
Replace by the following table:
|
Grade 1 |
Grade 2 |
Grade 3 |
Grade 4 |
Intruder |
Access level 2 or 3 |
Access level 2 or 3 |
Access level 2 or 3 |
Access level 2 or 3 |
Hold-up |
Access level 2 or 3 |
Access level 2 or 3 |
Access level 2 or 3 |
Access level 2 or 3 |
Tamper |
Access level 2 or 3 |
Access level 2 or 3 |
Access level 3 |
Access level 3 |
Fault |
Access level 2 or 3 |
Access level 2 or 3 |
Access level 3 |
Access level 3 |
Prime power source fault |
Access level 2 or 3 |
Access level 2 or 3 |
Access level 2 or 3 |
Access level 2 or 3 |
ATS fault |
Access level 2 or 3 |
Access level 2 or 3 |
Access level 2 or 3 |
Access level 2 or 3 |
Masking |
Access level 2 or 3 |
Access level 2 or 3 |
Access level 2 or 3 |
Access level 2 or 3 |
Significant reduction of range |
Access level 2 or 3 |
Access level 2 or 3 |
Access level 2 or 3 |
Access level 2 or 3 |
’ Except prime power source and ATS faults. |
Inhibit
Replace 'operation' by 'functioning'.
Isolate
In the 1st line, delete ‘the operation of.8.4.1 Intruder signals or messages
In the 3rd line, replace 'operation' by 'functioning'.
Table 7 - Processing of intruder, hold-up, tamper alarm and fault signals/messages
In NOTE 2, replace 'operation' by 'functioning'.
Replace NOTE 4 by the following:
NOTE 4 Requirements for indication should be read in conjunction with 8.5 and the functioning of indications is conditional upon the requirements of 8.5.
8.5.1 General
Add the following note after NOTE 1:
NOTE 2 Indications may be suppressed in certain cases, e g. to avoid an indication in the event of the activation of a hold-up device.
Delete the existing NOTE 2.
Table 8 - Indication
Replace by the following table:
Indications |
Grade 1 |
Grade 2 |
Grade 3 |
Grade 4 |
l&HAS set/Part set |
M |
M |
M |
M |
l&HAS unset |
M |
M |
M |
M |
Hold-up alarm condition |
M |
M |
M |
M |
Hold-up zone identification |
M |
M |
M |
M |
Intruder alarm condition |
M |
M |
M |
M |
Intruder zone identification |
M |
M |
M |
M |
Individual intrusion detector indication (see 8.5.4)a |
Op |
Op |
M |
M |
Detector alarm condition indicator (see 8.5.4) |
M |
M |
M |
M |
Inhibited |
M |
M |
M |
M |
Isolated |
M |
M |
M |
M |
Fault conditions (see Table 1) |
M |
M |
M |
M |
Tamper condition |
M |
M |
M |
M |
Masking (see 8.2.1) |
Op |
Op |
M |
M |
Range reduction (see 8.2.2) d |
Op |
Op |
Op |
M |
Pending indication(s) |
M |
M |
M |
M |
Alert indication |
M |
M |
M |
M |
Setting (see 8.3.4) b |
Op |
Op |
Op |
Op |
Completion of setting (see 8.3.7)b |
M |
M |
M |
M |
Entry indication (see 8.3.8.2) b&c |
M |
M |
M |
M |
Completion of unsetting (see 8.3.8.2)b&c |
M |
M |
M |
M |
Key: M = Mandatory Op = Optional NOTE When a function, e.g. hold-up, is not provided the associated indication is not required. |
||||
a Individual detector identification applies only to detectors with processing capabilities, see 8.5.4. b These indications are time limited. c These indications are mandatory only when the optional unsetting procedure described in 8.3.8.2 is used. d May be the same indication as masking. |
8.5.2 Availability of indications
Replace the 1st paragraph by the following:
Indications shall be available to users at access level 1 as specified in Table 9. The other indications included in Table 8 shall be available only to users who have accessed an l&HAS at access levels 2, 3 or 4.
Table 9 - Indications available during set and unset status at access level 1
Replace by the following table:
Indications |
Grade 1 |
Grade 2 |
Grade 3 |
Grade 4 |
|||||
Set |
Unset |
Set |
Unset |
Set |
Unset |
Set |
Unset |
||
l&HAS set/Part set [see 8.3.7 grades 1 & 2 c)] |
Op |
NA |
Op |
NA |
NP |
NA |
NP |
NA |
|
l&HAS unset [see 8.3.7 grades 1 & 2 c)] |
NA |
Op |
NA |
Op |
NA |
NP |
NA |
NP |
|
Alert indication |
NP |
M c |
NP |
Mc |
NP |
Mc |
NP |
M c |
|
Setting (see 8.3.4) a |
NA |
Op |
NA |
Op |
NA |
Op |
NA |
Op |
|
Completion of setting (see 8.3.7) a |
M |
NA |
M |
NA |
M |
NA |
M |
NA |
|
Entry indication (see 8.3.8.2) a & b |
M |
NA |
M |
NA |
M |
NA |
M |
NA |
|
Completion of unsetting (see 8.3.8.2) a&b |
NA |
M |
NA |
M |
NA |
M |
NA |
M |
|
Key: Op = Optional NP = Not Permitted NA = Not Applicable M = Mandatory. NOTE 1 In grades 3 and 4 l&HAS it is not considered acceptable to indicate, at access level 1, the set/unset state of an l&HAS. NOTE 2 When a function is not provided the associated indication is not required. |
|||||||||
a These indications are time limited. b These indications are mandatory only when the optional unsetting procedure described in 8.3.8.2 is used. c This indication is optional if the l&HAS is part set. |
8.6 Notification
Correct the 2nd paragraph to read:
The duration of the operational period of a WD may be subject to variation depending on local or national requirements.
In the 4th paragraph replace ‘EN 50136’ by ‘EN 50136-1-T.
In the last paragraph before Table 10, replace ‘operation’ by ‘functioning’.
Table 10 - Notification requirements
Add the following notes after NOTE 2:
NOTE 3 Where 2 ATS are specified it is recommended that the transmission paths are independent and use differing technologies, typically land-line and wireless.
NOTE 4 An SPT may be part of more than one ATS.
NOTE 5 The main and additional ATS shall meet their defined performance criteria when working normally. It is not a requirement of this standard for the performance of the additional ATS to change due to the failure of the main ATS.
After Table 10
In the 1st paragraph after Table 10, replace ‘EN 50136’ by ‘EN 50136-1-T.
Replace the existing note by the following:
NOTE 1 Annex В includes an extract of performance requirements specified in EN 50136-1-1.
NOTE 2 This standard refers to performance requirements specified in EN 50136-1-1 but does not include requirements relating to the classification of availability.
8.7.2 Tamper detection
Replace 'operate' by 'function' and 'operation' by 'functioning'.
Table 12 - Tamper detection - Components to include
Replace by the following table:
Components |
Grade 1 |
Grade 2 |
Grade 3 |
Grade 4 |
CIE/ACE a/SPT/WD/PS |
M |
M |
M |
M |
Hold-up devices a |
Op |
M |
M |
M |
Intrusion detectors b |
Op |
M |
M |
M |
Junction boxes c |
Op |
Op |
M |
M |
Key: Op = Optional M = Mandatory. |
||||
a Portable ACE and hold-up devices are not required to comply with the requirements of this table. b It is accepted that it may be impractical to provide tamper detection to magnetically or mechanically actuated switches. However in certain grades it may be necessary to protect magnetically actuated devices against tampering with an external magnetic or electro-magnetic source c In grade 3, when an l&HAS includes protection against the substitution of signals or messages, junction boxes need not be provided with tamper detection. |
Table 13 - Tamper detection - Means to be detected
Replace by the following table:
Means |
Grade 1 |
Grade 2 |
Grade 3 |
Grade 4 |
Opened by normal means |
M |
M |
M |
M |
Removal from mounting - Wire-free l&HAS components |
Op |
M |
M |
M |
Removal from mounting - Wired l&HAS components |
Op |
Op |
Mc |
M |
Penetration of audible WD |
Op |
Op |
Op |
M a |
Penetration of CIE/ACE/SPT |
Op |
Op |
Op |
Ma |
Detector orientation adjustment |
Op |
Op |
Mb |
Mb |
Key: Op = Optional M = Mandatory. |
||||
a Applies to CIE, ACE, SPT or WD when located outside the supervised premises. b When orientation adjustment is possible. c This requirement is optional for junction boxes and opening contacts (magnetic). |
8.8.3 Monitoring of interconnections
Add the following sentence at the end of the 1st paragraph:
The requirements specified in 8.8.3 do not apply to portable hold-up devices and portable ACE.
Power supply
Types of power supply
Add the following note after the last sentence.
NOTE Where the prime power source has finite capacity (e g. a battery) the power supply is considered to be of type C.
Requirements
Replace 'operation' by 'functioning' and 'operate' by 'function'.
Operational reliability
Replace 'operation' by 'functioning'.
Functional reliability
Replace the 1st sentence by the following:
l&HAS components shall comply with relevant standards. The design and the configuration of an l&HAS shall ensure the l&HAS functions in accordance with the requirements of this standard.
In the 7th dash item, replace 'operating' by 'working'.
Environmental requirements
Replace 'operation' by 'functioning'.
15 Marking/ldentification
Add the following after the 3rd dash item:
- standard to which the component claims compliance;
Annex A Special national conditions
Replace 'operate' by 'function'.
CE^ELEC
EN 50131-1/IS2
Interpretation 2
EN 50131-1:2006
English version
Foreword
This interpretation of the European Standard EN 50131-1:2006 was prepared by the Technical Committee CENELEC TC 79, Alarm systems. The text of the draft was submitted to the Unique Acceptance Procedure and was approved by CENELEC on 2010-07-09.
This document supersedes EN 50131-1:2006/IS1:2009.
Compared to EN 50131-1:2006/IS1:2009 the only change is the replacement of the 2nd paragraph of 8.5.4 by a new one for clarification’s sake.
EN 50131-1:2006, Alarm systems - Intrusion and hold-up systems - Part 1: System requirements, includes many requirements that may not match traditional intrusion systems in some countries. Additionally, standards are written in a style which can make them difficult to understand unless some explanation is given. This interpretation is intended to provide extra information to readers of the standard to assist in its understanding. It should be read in conjunction with the standard.
This interpretation varies in the depth of detail provided. More detail is given for areas that prompted significant questions during the development of EN 50131-1:2006.
This interpretation may also assist translators by clarifying the meaning of the standard.
This interpretation is informative and the standard shall be used to resolve any disputes.
ATTENTION - Numbering of clauses and tables:
In this document (sub)clause and table numbers written in italic (e.g. Table 7, Subclause 8.3.1) refer to subclauses and tables in EN 50131-1:2006. Numbers written normally (e.g. Table 2, Subclause 6.1.1) usually refer to this document but, when specifically stated, may refer to other documents.Contents
About this document 3
Scope 3
References 3
Definitions and abbreviations in this document 3
Brief guide on How to read the standard 4
Conventions used in standards (CENELEC Internal Regulations) 4
Definitions 4
Security grading 6
Environmental classification 6
Functional requirements 7
Power supply 19
Figures
- General processing 10
- Relationship of ATS and l&HAS 16
Tables
- Events - Cross references 11
- Excerpt of Table 7 12
- Contents of Table 8 and Table 9 14
- Clarification for Table 9 15
- Interpretation of some items of Table 22 18
In Clauses 3 to 9 of this document the section numbering
matches the clauses of EN 50131-1:2006.
Only interpreted clauses are given and therefore the numbers
are not continuous.
About this document
Scope
This document provides interpretation for the contents of EN 50131-1:2006 only. Other standards, Technical Reports or Technical Specifications in the EN 50131 series or EN 50136 series may be referenced but the interpretation is restricted to the scope and use of EN 50131-1:2006.
References
The standard that this document interprets is EN 50131-1: 2006, Alarm systems - Intrusion and hold-up systems - Part 1: System requirements.
Other standards referenced are those listed in the normative references of EN 50131-1:2006.
Definitions and abbreviations in this document
Definitions