TABLE 1 і REQUIREMENTS FOR THE MON-ELECTRIC AL TEST FOR HALOGEN FREE COMPOUNDS [continued!

1

2

3

4

5

6

Ref. No.

Test

Unit

Insulation

Sheath

Teat Method

4.

Heat shock taat




HD SOS.3.1

4.1

Test condition*:

- temperature

duration of treatment

°С h

15Q±2 1

150±2 1

SubcUuM

9.1 and 9.2

4.2

5-

Result to be obtained

Pressure test ait Nah temperature


Absence of cracks

Absence of cracks

HD 506-3.1 Sub-ctause

8.1 and 8.2

5.1

Test condition*: - temperature

°С

70±2

70*2


5.2

Result to be obtained: - median of the depth of perwtritcn, max.

%

50

50


6.

Shrinkage test





6.1

Test condition*: - temperature - duration

°С h

80 ±2 1

80*2 1

HD S0S.1.3

a use 10

6.2

Result to be obtained: Мам, permissible shrinkage

%

4

4


7.

7.1

Waier absorption

Test conditions: - Temperature - Duration

°С h

70±2 10x24

70±2 10x24

HO 505.1.3

Sub-ctause 9.2

7,2

Result to be obtained

Max, variation of mass

mg/cm3

5

to




TAft_E 1 ; REQUIREMENTS FOR THE NON-ELECTRICAL TEST FOR HALOGEN-FREE COMPOUNDS
(concluded)

1

2

3

4

&

8

Ref. No.

Test

Unit

Insulation

Sheath

Test Method

0.

8.1

Bending test at low temperature

Test conditions:

- temperature

*c

-16±2

15±2

HD 50Б.1.4 Sub-dsuse

8.1 and 8.2

8.2

9.

Result to be obtained

ЕЮпоегюп test allow


Absence of cracks

Absence of cracks

HD 505.1.4 Sub clause


temperature




9,1

Test conditions: - temperature

c

-1S±2

-25 ±2

8.3 and 8.4

9J

Result to be obtained:

elongation without break, mki.

%

20

20


10.

10.1

Impact twi at low temperature

Test conditions:

' temperature

°С

*25±2

-25 ±2

HD 506.1.4 Sub-clause 8 5 with additional requirements given in thia sectkm, Sub dause 2.3.1

10,2

Result to be obtained


Absence of cracks

Absence of cracks


TABLE 2 ; SCHEDULE OF TESTS

1

2

3

4

5

Ref. No,

Test

Category of test

Test method described in

Requirement given in Clause*

1,

Electrical tests




1.1

Conductor resistance

L S

HD 60S, 3.1

4 XL 4.3.5 and HD 383

1.2

Voltage test on cable

T

-

2-3.3

1.3

Voltage tost on core

T

-

2,3.4

1.4

Insutauon resistance on insulated cores

T

HD 605. 3 X1

2X5

15

DC Voltage test on insulation

T

HD 605. 3.2.2.1

2.3.6

1,6

High voltage test

R

2.3.7

2.

Ptov.skxh coverirx) constructional and tfmensional characteristics




2.1

Conductor material and construction

T. s

HD 605. 2.14

Part L 5.1

2.2

Insulation:

(a) Application (Ы Thickness

s L S

Visual examination HD 605. 2.1 Л

Part L 5.2.2

4.3.2 and

Part L 5.2.3

2.3

Core identification

L s

Visual examination

2.1 and Part 1, 4

2.4

Laid up cores

s

Visual examination

4.3.3

2.6

Metallic covering

T. s

Visual examination

4.3.5

2.6

Over shea th (a і Thickness

(Ы Diameter and ovality

T, s

T, s

HD 605. 2.1.2

HD 605. 2.1.3

4,3.6 and Part 1,

5.6.3

2.3.2

2.7

3.

Cable markings

Mechanical properties

T# s

Visual examination

2.2 and

Part L 3.1

3.1

Insulation

T

Table 1

Part L 2.1.1.4

32

Oversheath

T

Table 1

Part L 2.1.1,4



TABLE 2 : SCHEDULE QF TESTS (concluded)

1

2

3

4

5

Ref. No.

Test

Category of test

Test method described in

Requirement given in Clause*

4,

CompgtibiHtv ttsi

T

HD 606

Tabb 1

Б.

Tutt rented to fire eondrtkxn




5.1

Асй gas emission

T

HD 602

2.3.8

5.2

HCHevel

T

IEC 754-1

2.3.8

5.3

Smoke test. 3m* cube

T

HD 606

2.3,8

5 4

Ra me retardancy on bunched cables

T

HD 405.3 (Cat. Cl

HD 405-3

Clause numbers refer to this section unless stated otherwisePape 5013 HD 604 51:1984 Рэп 6 Section 0

ІДЙіЛ

1

2

3

Cross'Sectional area

insulation thickness

Insulation resistance at 70°C

mm

mm

Magohmfem

1-5

0.8

0.024

2.5

0.8

0.020

4

VO

0.020

6

1.0

0.018

10

1.0

0.016

16

1.0

0.012

25

V2

0.012

35

1.2

0.010

50

1.4

0.010

70

V4

0.010

95

1.6

0,009

120

V6

0 009

150

1.8

0 008

185

2,0

0.008

240

2.2

0,007

300

2*4

0.006

400

2.6

0.006

500

2-8

0.005

630

ZB

0.005



TABLE 4

1

2

3

4

Cross-sectional

Metal screen

Thickness of over-eheath

area




гтип*

Max. resistance at 20°C ©hm/km

Nominal equivalent copper area mm1

mm

Copper




1,5

12.1

1.6

1-5

2.5

7Д1

2.5

1.5

4

4.61

4

1.5

6

3.08

6

1.5

10

1.83

10

1.8

16

1.15

16

18

25

1.15

16

L8

36

LIS

16

LB

50

0,727

25

L8

70

0.524

35

L0

95

0.387

50

2.2

120

0.268

70

2,2

150

0.268

70

2.2

185

0,193

95

2,6

240

0.153

120

2.6

300

0.124

150

28

400

0 0754

240

2.8

500

0.0754

240

3.0

630

0.0601

300

3.0

Aluminium




16

1.83

10

LB

26

1.83

10

LB

50

LIS

16

LB

95

0,524

35

2.2

160

0.387

60

2.2

240

0-268

70

2.6

300

0-193

95

2.8

400

0.124

150

2.8

500

0.124

150

3.0

630

0.754

240

3.0