ПІДТВЕРДЖУВАЛЬНЕ ПОВІДОМЛЕННЯ

Наказом Міністерства економічного розвитку і торгівлі України
від 30.12.2014 № 1494

EN 12101-8:2011

en: Smoke and heat control systems - Part 8: Smoke control dampers

прийнято як національний стандарт
методом підтвердження за позначенням

ДСТУ EN 12101-8:2014
uk: Системи протидимного захисту. Частина 8. Димові клапани
(EN 12101-8:2011, IDT)

З наданням чинності від 2016-01-01E

EN 12101-8

May 2011

UROPEAN STANDARD

NORME EUROPEENNE

EUROPAISCHE NORM

ICS

English Version

Smoke and heat control systems - Part 8: Smoke control
dampers

S

Rauch- und Warmefreihaltung - Tell 8:
Entrauchungsklappen

ystemes pour Ie controle des fumees et de la chaleur -
Partie 8: Volets de desenfumage

This European Standard was approved by CEN on 17 March 2011.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.



EUROPEAN COMMITTEE FOR STANDARDIZATION СОМІТЁ EUROPEEN DE NORMALISATION EUROPAISCHES KOMITEE FUR NORMUNG

M

Ref. No. EN 12101-8:2011: E

anagement Centre: Avenue Marnix 17, B-1000 Brussels

© 2011 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members

.Contents Page

Foreword 4

Introduction 5

  1. Scope 8

  2. Normative references 8

  3. Terms and definitions 9

  4. Smoke control damper requirements 12

    1. General 12

      1. Fire resistance 12

      2. General application 12

    2. Construction and components: characteristics 12

      1. Construction and operation 12

      2. Protection against corrosion 14

    3. Fire resistance performance criteria: Single compartment smoke control dampers 14

      1. Integrity, leakage, HOT400/30 14

      2. Durability 14

      3. Fire resistance classification and designation 15

      4. Other performance criteria 15

    4. Fire resistance performance criteria: Multi compartment fire resisting smoke control

dampers 16

    1. Integrity, insulation, leakage, HOT 400/30 16

    2. Durability 16

    3. Fire resistance classification and designation 17

    4. Other performance criteria 17

  1. Test methods 17

    1. Ambient Leakage Tests 17

    2. Fire resistance tests 18

      1. General 18

      2. Smoke control damper: integrity and insulation 19

      3. Leakage rated smoke control damper 19

      4. Response delay of a smoke control damper 19

    3. Salt Spray Exposure Test 20

    4. Cycling Tests 20

      1. Damper durability cycling 20

    5. Damper Aerodynamic Performance 20

  2. Evaluation of conformity 21

    1. General 21

    2. Initial type testing 21

      1. General 21

      2. Modifications 21

      3. Previous tests and product families 21

      4. T est samples 22

      5. Test report 22

    3. Factory product control (FPC) 22

      1. General 22

      2. General requirements 23

      3. FPC specific requirements 23

      4. Initial inspection of factory and FPC 25

      5. Continuous surveillance of FPC 25

      6. Procedure for modifications 25

    4. One-off smoke control dampers, pre-production smoke control dampers (e.g. prototypes) and smoke control dampers produced in very low quantities 26

  3. Marking and documentation 26

  4. Product, installation and maintenance information (documentation) 27

    1. Product specification 27

    2. Installation information 27

    3. Maintenance information 27

  1. (normative) Salt spray exposure test 28

A.1 General 28

A.2 Revised parameters 28

  1. (informative) Example of inspection and maintenance procedure 29

  2. (normative) Factory production control - test plan 30

Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU Construction Products Directive 31

ZA.1 Scope and relevant characteristics 31

ZA.2 Procedure for the attestation of conformity of smoke control dampers 34

ZA.2.1 System of attestation of conformity 34

ZA.2.2 EC certificate of conformity and EC declaration of conformity 35

ZA.3 CE marking and labelling 35

Bibliography 38Foreword

This document (EN 12101-8:2011) has been prepared by Technical Committee CEN/TC191 “Fixed firefighting systems”, the secretariat of which is held by BSI.

This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by November 2011, and conflicting national standards shall be withdrawn at the latest by November 2011.

Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.

This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s).

For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document.

This European Standard has the general title "Smoke and heat control systems" and consists of the following separate parts:

  • Part 1: Specification for smoke barriers,

  • Part 2: Specification for natural smoke and heat exhaust ventilators,

  • Part 3: Specification for powered smoke and heat exhaust ventilators,

  • Part 4: Installed SHEVS systems for smoke and heat ventilation (Technical Report (TR)),

  • Part 5: Guidelines on functional recommendations and calculation methods for smoke and heat exhaust ventilation systems (TR),

  • Part 6: Specification for pressure differential systems - Kits,

  • Part 7: Smoke duct sections,

  • Part 8: Smoke control dampers (this standard),

  • Part 9: Control panels,

  • Part 10: Power supplies.

According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom.

Introduction

This European Standard contains the basic performance and requirements for smoke control dampers that are to be used in conjunction with pressure differential systems and smoke and heat control systems. They can also be used to pressurise when gas extinguishing systems are used.

Particular reference is required to EN 1366-10, which defines the furnace testing associated with these products and EN 13501-4, which provides details on their fire resistance classification.

In addition to the prevention of transmission of smoke and combustion products from a fire zone, smoke control dampers are utilised to contain the spillage of otherwise harmful and toxic extinguishing gases from the affected area, and for the control of pressurising and excess air relief within pressurisation systems.

Smoke control systems are designed to fulfil the following basic functions. These are:

  1. the extraction of smoke from a single fire compartment to the outside of the building,

  2. the extraction of smoke from fire compartments of a building, using a SHEVS connected to one or more fire compartments. The smoke control system duct may or may not pass through other compartments of the building to reach the outside of the building,

  3. the use of pressurisation to maintain smoke free clear areas.

Smoke control dampers are commonly used in smoke and heat control systems as a means of limiting the number of ducts and high temperature fan units. The ducts into which such smoke control dampers are fitted generally serve a number of different fire compartments. The systems may be dedicated smoke extraction or possibly a combined environmental ventilation/smoke extraction.

The smoke and heat control system may remove smoke using either high temperature fans (in accordance with EN 12101-3) or natural ventilators (in accordance with EN 12101-2).

It may be necessary for a number of reasons (fire growth, smoke release, etc.) that the open smoke control damper(s) is (are) required to close and that the damper(s) previously closed is(are) required to open.

The tests defined in this standard are based on the assumption that when smoke is detected within a building, all smoke control dampers other than those serving the fire compartment/smoke reservoir (where the fire has initiated) remain closed or move to the closed position. All smoke control dampers serving the smoke affected fire compartment/smoke reservoir remain open or move to the open position, and the fan(s) started/natural vents opened.

NOTE Figure 1 gives examples of installation positions, but these are not the only positions where dampers may be fitted.



Key

  1. Fire compartment

  2. Smoke reservoir

  1. Air inlet

  2. Smoke barrier

  3. Powered smoke and heat exhaust ventilator (fan)

  4. Smoke control dampers for single compartments (FprEN 12101-8 and EN 1366-10)

  5. Smoke control ducts for single compartments (FprEN 12101-7 and EN 1366-9)

  6. Smoke control ducts for multi compartments (FprEN 12101-7 and EN 1366-8)

  7. Smoke control dampers for multi compartments (FprEN 12101-8 and EN 1366-10) mounted inside or outside of wall or floor

  8. Smoke control dampers for multi compartments (FprEN 12101-8 and EN 1366-10) mounted on the surface of the duct

  9. Electrical equipment

Figure 1 - Example of powered smoke and heat exhaust ventilation

Further guidance on the application of smoke control dampers may be found within the rest of the EN 12101 series of harmonised standards and technical reports.

The areas for which products supplied to this standard are considered applicable include for example:

  1. commercial premises,

  2. shopping and retail centres,

  3. hospitals,

  4. multi-residential buildings.

Smoke control dampers are intended for use in the following types of systems, including:

  1. pressurisation,

  2. pressure relief,

  3. extraction systems,

  4. ductwork systems,

  5. inerting fire suppression systems.

  1. It is realised that all the above systems do not address smoke directly, but similar properties are required of such smoke control dampers to limit leakage in a fire and smoke control situation.Scope

This European Standard applies to smoke control dampers, placed on the market and intended to operate as part of a pressure differential system or smoke and heat control system. This standard specifies requirements and gives reference to the test methods defined for smoke control dampers and their associated components, such as actuators which are intended to be installed in such systems in buildings. It also provides for the evaluation of conformity of these products to the requirements of this standard. Furthermore, provision on marking and information on installation and maintenance of these products are also given.

This European Standard distinguish between two categories of smoke control dampers, i.e. single compartment smoke control dampers and multi-compartment fire resisting smoke control dampers.

Smoke control dampers covered by this European Standard can be installed into smoke control system ducts or onto the ducts' surface. They can be installed also into a wall, floor or ceiling/roof elements or onto the surface of these elements.

To avoid duplication, reference is made to a variety of other standards. To this end, this standard is to be read in conjunction with EN 13501-4, EN 1366-10 and EN 1366-2, for details of the furnace testing.

This standard does not consider in detail the detrimental and/or corrosive effects that may be caused by process chemicals present in the atmosphere, which are drawn through the system intentionally or inadvertently.

  1. Normative references

The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

EN 1366-2, Fire resistance tests for service installations - Part 2: Fire dampers

EN 1366-10, Fire resistance tests for service installations - Part 10: Smoke control dampers

EN 1751, Ventilation for buildings - Air terminal devices - Aerodynamic testing of dampers and valves

prEN 12101 -9, Smoke and heat control systems - Part 9: Control panels

EN 12101-10, Smoke and heat control systems - Part 10: Power supplies

EN 13501-4, Fire classification of construction products and building elements - Part 4: Classification using data from fire resistance tests on components of smoke control systems

EN 60068-2-52:1996, Environmental testing - Part 2-52: Test methods, Test Kb: Salt mist cyclic (sodium chloride solution) (IEC 60068-2-52:1996)

EN ISO 5135, Acoustics - Determination of sound power levels of noise from air-terminal devices, air-terminal units, dampers and valves by measurement in a reverberation room (ISO 5135:1997)

EN ISO 13943, Fire safety - Vocabulary (ISO 13943:2008)

  1. Terms and definitions

For the purposes of this document, the definitions given in EN ISO 13943, together with the following, apply.

air inlet

device connected to outside air to allow the inlet of air from outside the building

    attended control room

    room with people, who have the duty to control the smoke exhaust system permanently (24 hours per day, seven days per week), monitor the incoming signals from the smoke control systems and put the smoke control system into operation in case of smoke alarm

    NOTE This ensures that the smoke control system is running and items such as dampers are in position within the system response time.

      elevated temperature

      temperatures in excess of normal ambient air, below those necessary for fire resistance testing, to which smoke and heat exhaust ducts for single compartments are tested, to gain classification

        fire compartment

        enclosed space, comprising one or more separate spaces, bounded by elements of construction having a specified fire resistance and intended to prevent the spread of fire (in either direction) for a given period of time

          interface control unit

          device which controls the operation of the actuator located at the damper or within the same fire zone as the damper

            multi compartment smoke control dampers

            smoke control dampers, which are fire resisting, for use in multi compartment areas, which may be associated with multi or single compartment smoke control ductwork and/or may be installed in a fire compartment structure

              multi compartment fire resisting smoke control ducts

              fire resisting smoke control ducts, built from more than one smoke control duct section, for use in multi compartment applications designed to transport smoke and/or hot gases away from the source of a fire [EN 12101-7]

              NOTE May also have a dual function as a normal air conditioning duct.

                natural smoke and heat control system

                smoke and heat ventilation system which uses natural ventilation

                NOTE Natural ventilation is caused by buoyancy forces due to differences in density of the gases because of temperature differences.

                3.9

                penetration seal

                product tested for use between the smoke control duct/damper and the fire compartment structure to maintain the fire resistance, at the position where a smoke control system duct passes through the element, or a damper is mounted in the element

                3.10

                powered smoke and heat exhaust system

                smoke and heat ventilation system, which utilises a number of hot gas fans that are suitable for handling hot gases for a limited period of time, which causes the positive displacement of gases

                3.11

                pressure differential system

                system of fans, ducts, vents and other features provided for the purposes of creating a lower pressure in the fire zone than in the protected space

                3.12

                remote signalling

                device located away from the damper which will indicate the damper position, open or closed

                3.13

                safety position

                position (open or closed) into which specific projects may require certain dampers to move, depending upon the fire location within the building

                3.14

                single compartment smoke control dampers

                smoke control dampers for use in single compartment areas, which may be associated with single compartment smoke control ductwork and/or may be installed in an external wall or roof

                3.15

                single compartment smoke control ducts

                smoke control ducts, built from more than one smoke control duct section, for use within single fire compartment application designed to transport smoke and/or hot gases away from the source of a fire [EN 12101-7]

                NOTE May also have a dual function as a normal air conditioning duct.

                3.16

                smoke and heat exhaust ventilation system (SHEVS)

                system consisting of products and/or components jointly selected to exhaust smoke and heat

                NOTE The products and/or components form a system in order to establish a buoyant layer of warm gases above cooler cleaner air.

                3.17

                smoke and heat exhaust ventilator (SHEV)

                device specially designed to move smoke and hot gases out of a construction works under conditions of fire

                3.18

                smoke barrier

                barrier to restrict the spread of smoke and hot gases from a fire, forming part of the boundary of a smoke reservoir or used as a channelling screen, or used as a void edge boundary

                3.19

                smoke control damper for systems with automatic activation

                smoke control damper that is applicable to the systems defined in 3.26

                3.20

                smoke control damper for systems with manual intervention

                smoke control damper that is applicable to the systems defined in 3.27 and 3.28

                3.21

                smoke control damper

                device automatically or manually activated, which may be open or closed in its operational position, to control the flow of smoke and hot gases into, from or within a duct

                3.22

                smoke control damper - horizontal installation

                smoke control damper fitted in-line across a vertical duct, or on the top and bottom surface of a horizontal duct

                3.23

                smoke control damper - vertical installation

                smoke control damper fitted in-line across a horizontal duct, or on the sides of a horizontal duct, or on any surface of a vertical duct

                3.24

                smoke control duct - section

                element of smoke control duct constructed to form part of a smoke control system [EN 12101-7]

                3.25

                smoke control system with automatic activation

                smoke control system (smoke and heat exhaust ventilation type or pressure differential type), that operates automatically on receipt of a smoke or fire alarm without any manual action/intervention

                NOTE A system with an attended control room can also be accepted as an automatic system. Once initiated, the system will not cause the damper position to be changed.

                3.26