EUROPEAN STANDARD

NORME EUROPEENNE

EUROPAISCHE NORM


EN 12101-7


May 2011


ICS


English Version

Smoke and heat control systems - Part 7: Smoke duct sections


Systdmes pour Ie controle des fumees et de la chaleur -
Partie 7: Trongons de conduit de desenfumage


Rauch- und Warmefreihaltung - Teil 7:
Entrauchungsleitungen


This European Standard was approved by CEN on 17 March 2011.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania. Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.


EUROPEAN COMMITTEE FOR STANDARDIZATION
СОМІТЁ EUROPEEN DE NORMALISATION
EUROPAISCHES KOMITEE FUR NORMUNG

M

Ref. No. EN 12101-7:2011: E

anagement Centre: Avenue Marnix 17, B-1000 Brussels

© 2011 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members.Contents Page

Foreword 4

Introduction 5

  1. Scope 8

  2. Normative references 8

  3. Terms and definitions 8

  4. Smoke control duct section requirements 10

    1. General 10

      1. Fire resistance - multi compartment smoke control duct section 10

      2. Fire resistance - single compartment smoke control duct section 11

    2. Construction and components: characteristics 11

      1. Construction and operation 11

      2. Structural supports used for smoke control duct sections 11

    3. Fire resistance performance criteria: Multi compartment fire resisting smoke control duct sections 12

      1. Integrity, insulation, leakage, 12

      2. Fire resistance classification and designation 13

    4. Fire resistance performance criteria: Single compartment smoke control duct sections 13

      1. Integrity, leakage 13

      2. Fire resistance classification and designation 13

  5. Test methods 14

    1. Ambient leakage tests 14

    2. Fire resistance tests 14

      1. General 14

      2. Smoke control duct section: integrity and insulation 14

      3. Leakage rated smoke control duct section 15

  6. Evaluation of conformity 15

    1. General 15

    2. Initial type testing (ITT) 15

      1. General 15

      2. Modifications 15

      3. Previous tests and product families 16

      4. Test samples 16

      5. Test report 16

    3. Factory product control (FPC) 17

      1. General 17

      2. General requirements 17

      3. FPC specific requirements 17

      4. Initial inspection of factory and FPC 19

      5. Continuous surveillance of FPC 20

      6. Procedure for modifications 20

    4. One-off smoke control duct sections, pre-production smoke control duct sections (e.g.

prototypes) and smoke control duct sections produced in very low quantities 20

  1. Marking and documentation 21

  2. Product, installation and maintenance information (documentation) 21

    1. Product specification 21

    2. Installation information 21

    3. Maintenance information 22

  1. (informative) Example of inspection and maintenance procedure 23

  2. (normative) Factory production control - test plan 24

Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU Construction Products Directive 25

ZA.1 Scope and relevant characteristics 25

ZA.2 Procedure for the attestation of conformity of smoke control duct sections 27

ZA.2.2 EC certificate of conformity and EC declaration of conformity 28

ZA.3 CE Marking 29

Bibliography 30Foreword

This document (EN 12101-7:2011) has been prepared by Technical Committee CEN/TC 191 “Fixed firefighting systems”, the secretariat of which is held by BSI.

This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by November 2011, and conflicting national standards shall be withdrawn at the latest by November 2011.

Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.

This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s).

For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document.

This European Standard has the general title "Smoke and heat control systems" and consists of the following separate Parts:

  1. Specification for smoke barriers,

  2. Specification for natural smoke and heat exhaust ventilators,

  3. Specification for powered smoke and heat exhaust ventilators,

  4. Installed SHEVS systems for smoke and heat ventilation (Technical Report (TR)),

  5. Guidelines on functional recommendations and calculation methods for smoke and heat exhaust ventilation systems (TR),

  6. Specification for pressure differential systems - Kits,

  7. Smoke duct sections (this standard),

  8. Smoke control dampers,

  9. Control panels,

  10. Power supplies.

According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom.

Introduction

This European Standard contains the basic performance and requirements for smoke control duct sections, which are to be used in conjunction with pressure differential systems and smoke and heat control systems. They may also be used to pressurise when gas extinguishing systems are used.

Particular reference is required to EN 1366-8 and EN 1366-9, which define the fire resistance testing associated with these products and EN 13501-4, which provides details on their fire resistance classification.

In addition to the prevention of transmission of smoke and combustion products from a fire zone, smoke control duct sections are utilised to contain the spillage of otherwise harmful and toxic extinguishing gases from the affected area, and for the control of pressurising and excess air relief within pressurisation systems.

Smoke control systems are designed to fulfil three basic functions. These are:

  1. the extraction of smoke from a single fire compartment to the outside of the building;

  2. the extraction of smoke from fire compartments of a building, using a SHEVS connected to one or more fire compartments. The smoke control duct may or may not pass through other compartments of the building to reach the outside of the building;

  3. the use of pressurisation to maintain smoke free clear areas.

Smoke control ducts are commonly used in smoke and heat control systems. They may serve single compartments or a number of different fire compartments. The systems may be dedicated smoke extraction or possibly a combined environmental ventilation/smoke extraction.

The smoke and heat control system may remove smoke using either high temperature fans (in accordance with EN 12101-3) or natural ventilators (in accordance with EN 12101-2).



Key

  1. Fire compartment

  2. Smoke reservoir

  1. Air inlet

  2. Smoke barrier

  3. Powered smoke and heat exhaust ventilator (fan)

  4. Smoke control dampers for single compartments (FprEN 12101-8 and prEN 1366-10)

  5. Smoke control duct sections for single compartments (FprEN 12101-7 and EN 1366-9)

  6. Smoke control duct sections for multi compartments (FprEN 12101-7 and EN 1366-8)

  7. Smoke control dampers for multi compartments (FprEN 12101-8 and prEN 1366-10) mounted inside or outside of wall or floor

  8. Smoke control dampers for multi compartments (FprEN 12101-8 and prEN 1366-10) mounted on the surface of the duct

  9. Electrical equipment

Figure 1 - Example of powered smoke and heat exhaust ventilation

Further guidance on the application of smoke control ducts may be found within the rest of the EN 12101 series of harmonised standards and technical reports.

The areas for which products supplied to this European Standard are considered applicable include for example:

  1. commercial premises,

  2. shopping and retail centres,

  3. hospitals,

  4. multi-residential buildings.

Smoke control duct sections are intended for use in the following types of systems, including:

  1. pressurisation,

  2. pressure relief,

  3. extraction systems,

  4. ductwork systems,

  5. inerting fire suppression systems.

  1. It is realised that all the above systems do not address smoke directly, but similar properties are required of such smoke control ducts to limit leakage in a fire and smoke control situation.Scope

This European Standard applies to smoke control duct sections, placed on the market and intended to operate as part of a pressure differential system or smoke and heat exhaust system. This standard specifies requirements and gives reference to the test methods defined for smoke control duct sections and their associated components (for example, hangers and other items proven at the time of testing), which are intended to be installed in such systems in buildings. It also provides for the evaluation of conformity of the products to the requirements of this standard. Furthermore, marking and information on installation and maintenance of these products are also given in this European Standard.

To avoid duplication, reference is made to a variety of other standards. To this end, this standard is to be read in conjunction with EN 1366-8, EN 1366-9 and EN 1366-1, for details of the fire resistance testing and EN 13501-4 for corresponding classification.

This standard has not considered in detail the detrimental and/or corrosive effects that may be caused by process chemicals present in the atmosphere, which are drawn through the system intentionally or inadvertently.

This European Standard also governs associated components used together with smoke control duct sections such as turning vanes and silencers, with the exception of natural and powered smoke ventilators and smoke control dampers, which are covered by separate standards.

Ducts for use other than in smoke and heat exhaust/control systems are not covered by this standard.

  1. Normative references

The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies).

EN 1366-1, Fire resistance tests for service installations - Part 1: Ducts

EN 1366-8, Fire resistance tests for service installations - Part 8: Smoke extraction ducts

EN 1366-9, Fire resistance tests for service installations - Part 9: Single compartment smoke extraction ducts

EN 13501-4, Fire classification of construction products and building elements - Part 4: Classification using data from fire resistance tests on components of smoke control systems

EN ISO 13943, Fire safety- Vocabulary (ISO 13943:2008)

  1. Terms and definitions

For the purposes of this document, the terms and definitions given in EN ISO 13943, together with the following apply.

air inlet

device connected to outside air to allow the inlet of air from outside the construction works

    elevated temperature

    temperatures in excess of normal ambient air, below those necessary for fire resistance testing, to which smoke and heat exhaust ducts for single compartments are tested

      fire compartment

      enclosed space, comprising one or more separate spaces, bounded by elements of construction having a specified fire resistance and intended to prevent the spread of fire (in either direction) for a given period of time

        natural smoke and heat control system

        smoke and heat ventilation system which uses natural ventilation

        NOTE Natural ventilation is caused by buoyancy forces due to differences in density of the gases because of temperature differences.

          penetration seal

          product used between the smoke control duct and the fire compartment boundary structure to maintain the fire resistance, when tested and having met the requirements of EN 1366-8, at the position where a smoke control duct passes through the element

            powered smoke and heat exhaust system

            smoke and heat ventilation system which utilises a number of hot gas fans that are suitable for handling hot gases for a limited period of time which causes the positive displacement of gases

              pressure differential systems

              system of fans, ducts, vents and other features provided for the purposes of creating a lower pressure in the fire zone than in the protected space, see EN 12101-6

                smoke and heat exhaust ventilation system (SHEVS)

                system consisting of products and/or components jointly selected to exhaust smoke and heat

                NOTE The products and/or components form a system in order to establish a buoyant layer of warm gases above cooler cleaner air.

                3.9

                smoke and heat exhaust ventilator (SHEV)

                device specially designed to move smoke and hot gases out of a construction works under conditions of fire

                3.10

                smoke barrier

                barrier to restrict the spread of smoke and hot gases from a fire, forming part of the boundary of a smoke reservoir or used as a channelling screen, or used as a void edge boundary

                3.11

                smoke control damper

                device automatically or manually activated, which may be open or closed in its operational position, to control the flow of smoke and hot gases into, from or within a duct

                3.12

                smoke control duct - horizontal

                smoke control duct which passes horizontally through vertical walls

                3.13

                smoke control duct - multi compartment fire resisting

                fire resisting smoke control ducts, built from more than one smoke control duct section, for use in multi compartment applications designed to transport smoke and/or hot gases away from the source of a fire

                NOTE May also have a dual function as a normal air conditioning duct.

                3.14

                smoke control duct - single compartment

                smoke control ducts, built from more than one smoke control duct section, for use within single fire compartment application designed to transport smoke and/or hot gases away from the source of a fire

                NOTE May also have a dual function as a normal air conditioning duct.

                3.15

                smoke control duct - section

                element of smoke control duct constructed to form part of a smoke control system

                3.16

                smoke control duct - vertical

                smoke control duct which passes vertically through horizontal floors

                3.17

                smoke layer

                layer of smoke that stabilises underneath the roof due to the affect of temperature gradient

                3.18

                smoke reservoir

                region within a building limited or bordered by smoke barriers or structural elements and which will, in the event of a fire, retain a thermally buoyant smoke layer

                3.19 smoke zone

                structural supports

                means of retaining the smoke control duct to the building structure

                4 Smoke control duct section requirements

                1. General

                  1. Fire resistance - multi compartment smoke control duct section

                The multi compartment smoke control duct section shall demonstrate the following and shall be classified in accordance with EN 13501-4:

                1. integrity: this shall be tested in accordance with test method in 5.2 and the integrity classification (E) declared;

                2. insulation: this shall be tested in accordance with test method in 5.2 and the insulation classification (I) declared;

                3. leakage: this shall be tested in accordance with test method in 5.2 and the leakage classification (S) declared;

                4. mechanical stability: this shall be tested in accordance with test method in 5.2 and forms part of the integrity classification (E) declared;

                5. maintenance of cross section: this shall be tested in accordance with test method in 5.2 and forms part of the integrity classification (E) declared.

                1. Fire resistance - single compartment smoke control duct section

                The single compartment smoke control duct section shall demonstrate the following and shall be classified in accordance with EN 13501-4:

                1. integrity: this shall be tested in accordance with test method in 5.2 and the integrity classification (E) declared;

                2. leakage: this shall be tested in accordance with test method in 5.2 and the leakage classification (S) declared;

                3. mechanical stability: this shall be tested in accordance with test method in 5.2 and forms part of the integrity classification (E) declared;

                4. maintenance of cross section: this shall be tested in accordance with test method in 5.2 and forms part of the integrity classification (E) declared.

                1. Construction and components: characteristics

                  1. Construction and operation

                Smoke control ducts are required to maintain a clear path for the extract of smoke and heat. To achieve this, the following shall be considered part of the smoke control duct section assembly and their performance in the tests shown in 5.2 recorded.

                1. Structural supports used for smoke control duct sections

                Structural supports used for smoke control duct sections ensure the mechanical stability and maintenance of cross section. Full details of the structural supports used for the fire test shall be recorded.

                1. Duct sealant materials used in or between smoke control duct sections

                Sealants are often used to reduce the air/gas leakage from smoke and heat exhaust ventilation systems. Failure of these sealants whilst the smoke and heat exhaust ventilation system is operating in its emergency mode may result in the failure of the duct’s leakage criteria. Full details of the sealants used for the fire test shall be recorded.

                The following general requirements for duct sealants shall apply.

                1. The sealants shall be suitable for the environment to which the smoke control duct is to be subject.

                2. The sealants shall be durable for the proposed life of the smoke control duct section.

                3. The sealants shall be resistant to mechanical damage during the installation of the smoke control duct section.

                4. Any deterioration of the sealant shall not cause the smoke control duct section to fail the leakage criteria for the duct classification.

                1. Penetration seals between fire compartments

                Penetration seals are required to reduce the air/gas leakage between compartments. Failure of these penetration seals, whilst the smoke and heat control system is operating in its emergency mode, may result in the failure of the system to maintain smoke-free areas. Full details of the penetration seals used for the fire test shall be recorded.